Short answer: yes — 230 VAC and 24 VDC input cards share one rack and one enclosure, and neither card needs a supply of its own. The voltage printed on the card is the field voltage its channels sense, not the card's operating supply. Every card on the rail draws its logic power from the backplane, so both card types are the same kind of load there. The care goes into the wiring. Group the AC cards at one end of the rail. Fuse each AC input group on its own line, keep the AC neutral off the 24 V 0 V bus, and run the two field bundles in separate wire duct. The worked example below uses placeholder card and sensor figures; replace each one with the datasheet value for your own hardware before you size a supply or a fuse.
What the voltage on the card actually means
The number in a card's designation — 24 VDC, 120 VAC, 230 VAC — names the process voltage: the potential the channels look for at the field terminals. The card's own logic takes its power from the backplane bus, the set of connector contacts that runs card to card along the rail. One rack supply feeds that bus; I/O selection guides describe it as the panel's low-voltage feed converted to backplane logic power, commonly 5 V DC. An AC card is not a heavier electrical animal than a DC card. It draws backplane current like any other module, and its field side simply reads line voltage instead of a sensor signal.
Two consequences shape the panel. The backplane does not reach the field: sensors and contacts take their power from the panel's field buses, not from the rail. And the card designation tells you what to bring to the field terminals, not which supply to bolt beside the rack.
What you need on the bench
- A meter that reads resistance plus AC and DC volts, proven on a known source.
- A fused terminal or small breaker for every AC input group, matched to the card's group layout.
- Two flame-retardant wire duct runs, one per bundle.
- Marking labels for the AC terminals and a warning label for the rack face.
- The datasheets for the CPU, the cards and both supplies, for the budget numbers two sections down.
Which supplies the panel needs
The supply answer is almost always none. Two feeds already in a normal panel cover a mixed rack, and the card mix changes neither of them.
- Backplane power. The panel's low-voltage control supply feeds the rack or chassis supply, which turns that input into backplane logic power. An AC card draws from the bus exactly like a DC card.
- AC field power. Line and neutral from the panel's AC distribution feed each input group through its own fuse. A panel already fed at line voltage has this distribution; a low-voltage-only cabinet does not.
- DC field power. The same low-voltage control supply runs the sensors, proximity switches and test pushbuttons on the DC card, as the article on wiring a 24 VDC load supply to I/O modules lays out.
Size that control supply for its field side with the control-panel supply selection guide, and keep the two budgets apart: the rack supply is budgeted in backplane current, the control supply in field devices, relays and the HMI. Blending the two feeds hides a fault that drops both at once.
The one case that adds hardware is a cabinet with no AC feed at all that now needs AC field sensors. Bring in a fused AC branch for the input groups, or change the sensors to DC types — a distribution decision, not a card requirement.
The budget check, with placeholder figures
Both budgets are one multiplication each, and the datasheets hand you the inputs. Backplane first: a rack with a CPU and eight input cards, datasheet backplane currents of 0.5 A for the CPU and 0.15 A per input card, sums to 0.5 + (8 × 0.15) = 1.7 A. A rack supply rated 2.0 A carries that at 85%, leaving 0.3 A of headroom — room for another card or two. Then the field side: a 16-point line-voltage input card whose datasheet lists 10 mA per point draws 16 × 0.010 A = 0.16 A per group, so a 0.5 A fuse gives about three times the group's load and stays clear of nuisance trips. Every figure here is a placeholder — card families differ, so take the backplane current, the per-point input current and the supply rating from your own datasheets before you buy anything.
Assign slots for the wiring, not for the voltage
The rail treats both card types identically, so assign slots for the wiring. Put the AC input cards together at one end of the rail and the DC cards together at the other. Each type's field wiring then leaves the rack as a single bundle into one duct, and a mixed rack becomes two clean runs instead of a braided one.
Mounting and space carry real numbers. Keep the rack horizontal; mount it vertical only where the controller's installation instructions publish a vertical-mount ambient. Most installation manuals ask for 2 in [50 mm] of free air above and below a rack, and that convection path matters: hold the enclosure's interior at or below 40 C (104 F), the ambient most controller electronics are built for. Site the panel so the center of the highest group-fuse handle sits no more than 2.0 m (6 ft 7 in) above the floor, as NEC 240.24(A) requires. Then leave the working space NEC 110.26(A) sets: clear access in front, a door swing of at least 90 degrees, and at least 3 ft (900 mm) of depth for equipment under 150 V to ground in Condition 1. For duct runs, rail spacing and fill arithmetic, the backplate and DIN rail layout guide carries the fundamentals.
Wire and fuse the AC field side
AC input channels work in groups. A set of channels shares one common terminal, the datasheet states how many channels per group — 8- and 16-channel cards group differently — and the groups are isolated from each other and from the backplane. Feed each group's line through its own fuse or small breaker, and take neutral for every group from the neutral bar. One fuse ahead of all groups turns a single fault into a rack of dead inputs.
Route the AC bundle in its own duct from the gland to the card faces, and mark every AC-fed terminal at the card face. Use flame-retardant nonmetallic duct: NFPA 79 permits nonmetallic duct inside an enclosure only when it passes the IEC 60332-1 flame test. Keep total fill at or under 50% of the duct's interior cross-section, the ceiling every duct maker's fill table applies when citing NFPA 79's percentage-fill rule. Where both bundles must share one duct, every conductor in it carries insulation for the highest voltage present — 600 V rated wire on a line-voltage circuit. Bring the AC field cable in through its own gland and cutout, specified as the cutouts, glands and windows guide describes.
Keep the low-voltage bus a separate system
The low-voltage side stays low-voltage because its wiring stays separated from mains. SELV and PELV describe exactly that: supplies whose output wiring keeps protective separation from other circuits, which is what lets a sensor cable share a panel with line voltage at all. Three habits hold it:
- Neutral and 0 V live on separate, labeled bars.
- Any earth reference for the 0 V bus comes from the panel's earth bar, not from the neutral conductor.
- Where the bundles must cross, they cross at right angles, each in its own duct.
Bonding neutral to 0 V for a 'common reference' undoes the separation. The low-voltage system loses its SELV/PELV status, an upstream open neutral can lift the DC common toward line potential, and an AC-side fault finds a return path through sensor wiring. The two systems also switch independently: opening the DC supply leaves the AC input circuits live, so carry a warning label at the rack face. For how the bars sit together, the panel earth and shield earth article and the grounding and bonding guide cover the arrangement, and the subpanel bonding article shows why neutral and earth meet at one point only.
Five checks before you close the door
Lock out and prove your meter on a known source before any terminal work.
- De-energized, connectors unplugged: measure resistance between every AC group common and the 0 V rail. Expect an open circuit; any reading means the references touch somewhere.
- De-energized: offer each AC-wired connector to a DC card. Keyed or coded connector systems refuse a connector wired for the wrong voltage, so keep the coding intact and build a fresh connector instead.
- AC distribution alone, guards in place: measure nominal line voltage at each fused group output, line to neutral, and 0 V across the still-dead DC bus.
- DC alone: measure the rack supply's output with the cards seated and confirm the backplane indicator is lit. Expect 20.4 to 28.8 V DC, the range IEC 61131-2 sets around the nominal bus voltage.
- Both live: the rack reaches RUN with no station fault. Apply line voltage to one AC input through a test lead and watch its LED follow, then actuate one DC sensor and watch that LED follow.
Mistakes that cost the panel
- One fuse ahead of all AC groups. Fuse each group on its own; a group fault should cost one group.
- Neutral bonded to the 0 V bus for a 'common reference'. Separate bars, and the earth reference from the earth bar.
- Both bundles woven through one duct in 300 V rated wire. Separate ducts, or 600 V insulation on every conductor in the shared duct.
- Duct filled past its 50% ceiling. The bundles merge, and the separation disappears at the first bend.
- A connector reworked to fit a card it was not wired for. Build a fresh connector with the right coding.
- Slots or backplane current run out and the first rack gets crowded. Add a second rail per the controller's extension instructions; the bus budget sets that limit.
When the enclosure itself is the constraint
Two ducts, a second terminal strip and the group fuses take backplate area, and a rack grown by a rail takes depth. If the mixed wiring cannot hold the separations above in the box you own, the box is the item to change, not the separations. We build custom stainless enclosures to your width, height, depth and every cutout from a single piece — a deeper body for two duct runs, a dedicated gland position for the AC bundle, a window over the rack face. Browse the custom enclosure options in 304 and 316L stainless; delivery is 10 business days from drawing approval, anywhere in the world.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Do 230 VAC input cards need their own power supply?
No. The label voltage is the field voltage the channels sense; card logic runs from the rack backplane, and an AC card draws backplane current like any other module. Bring line to each input group through its own fuse and neutral from the neutral bar — a panel already fed at line voltage has that distribution. Hardware gets added only when the cabinet has no AC feed at all: bring in a fused AC branch, or fit DC sensors instead.
Can 230 VAC and 24 VDC field wiring share one wire duct?
Keep them in separate ducts where the layout allows. Where both bundles must share one duct, every conductor carries insulation for the highest voltage present — 600 V rated wire on a line-voltage circuit — and total fill stays at or under 50% of the duct's interior cross-section, the ceiling NFPA 79's fill rule and duct makers' tables apply. Cross the bundles at right angles rather than running them side by side.
What fails when the AC neutral is bonded to the 24 V 0 V bus?
The low-voltage system loses its SELV/PELV separation from mains, so a fault on the AC side can reach the DC common through the bond. An upstream open neutral can lift the whole 0 V bus toward line potential, and an AC fault can return through sensor wiring. Keep neutral and 0 V on separate bars and take any earth reference for the DC common from the panel's earth bar.
What should the DC bus read before startup?
Between 20.4 and 28.8 V DC at the rack supply's output terminals — the range IEC 61131-2 sets around the nominal bus voltage. Measure with the cards seated and the sensors connected, because wiring drops pull the reading down at the rack. Below 20.4 V, cards can drop out or misread inputs; above 28.8 V, every device on the bus runs stressed.