Email us

Enclosure heat calculator

Enter the heat inside, the hottest ambient and your equipment's limit: the temperature rise, and the cooling a sealed enclosure needs.

Calculator

Heat dissipation and temperature rise

The method, step by step
The enclosure
Grade
Mounting

On a wall, the back face sheds no heat. Exposed on all sides means on an arm, a pedestal or free-standing, as an HMI housing usually is.

Heat and temperatures

In direct sun adds peak sun on the front to the heat inside: 1,040 W/m² × the outside H × W, as the product pages show it, before the brushed finish reflects part of it: an upper bound for sizing cooling, not a forecast of the inside temperature. The safety margin applies to the devices only.

Temperatures in

Heat inside: add the losses of every device from its datasheet; for a power supply, output power × (1 / efficiency − 1). Keep inside below: the lowest rated ambient of the devices inside, less a margin.

Result

44.5 W more than the walls shed at your 45 °C limit: sealed, it would reach about 60 °C.

  • Air-to-air heat exchanger (closed loop, keeps the seal): at least 4.4 W/K (2.47 W/°F). It works only while the air outside is cooler than the inside.
  • Enclosure air conditioner (closed loop, keeps the seal): at least 44.5 W of cooling.
  • Fan and filter (open loop): about 23 m³/h (13 CFM) at sea level. It brings outside air in, so the enclosure is no longer NEMA 4X unless the fan unit itself is rated 4X.
  • A larger size: the smallest of our stainless wall-mount sizes that sheds this load sealed is 42 × 36 × 8 in.
  • Or move a heat source, such as a power supply, outside the enclosure.

Next step

Open the 42 × 36 × 8 in product page with these numbersSend these numbers with a quote request

Effective surface, A
0.801 m² (8.62 ft²)
Heat transfer, k × A
2.96 W/K
Design heat load
74.1 W
Temperature rise, sealed
25.0 K (45.0 °F)
Inside, sealed
60 °C / 140 °F
Walls shed at your limit
29.6 W
Surface needed to stay sealed
2.00 m²
With the lowest published k
k = 1.94 W/m²K: rise 47.7 K

An estimate, not a rating: still air, no sun unless you tick it, one average inside temperature. Choose cooling with margin and from the cooling unit maker's data.

This enclosure heat calculator works out how much heat a sealed enclosure can dissipate and how hot it runs inside. Pick one of our sizes or enter your own, say how it is mounted and what it is made of, then enter the heat inside, the hottest ambient and the highest temperature your equipment allows. It gives the effective surface and the temperature rise and, when the walls are not enough, the heat exchanger, air conditioner or fan the load needs. The formulas and a worked example are below.

How it calculates

The formulas, in plain sight

The formulas the calculator uses
StepFormulaNotes
Effective surface, wall-mountedA = 1.4 · W · (H + D) + 1.8 · D · HIEC/TR 60890, a single enclosure on a wall: the back sheds nothing.
Effective surface, exposed on all sidesA = 1.8 · H · (W + D) + 1.4 · W · DOn an arm, a pedestal or free-standing. H, W and D in metres.
Heat the walls shedQ = k · A · ΔTΔT = inside air minus outside air, in K (the same as a °C difference).
Temperature rise, sealedΔT = Q / (k · A)Inside temperature = ambient + ΔT.
Air-to-air heat exchangerqw = (Q − k · A · ΔT) / ΔTSpecific output in W/K; only while the outside air is cooler than the inside.
Enclosure air conditionerQK = Q − k · A · (Ti − Ta)Cooling output in W; when the room is hotter than the inside, the walls add heat.
Fan and filterV = 3.1 · Q / ΔT (m³/h) · CFM = 3.16 · Q / ΔT(°F)Factor 3.1 up to 100 m altitude, 3.5 at 750–1,000 m; ignores the walls, so it errs high.
Heat transfer coefficients, still air
Materialk used hereLowest published value
Stainless steel, unpainted3.7 W/m²K1.94 W/m²K
Painted sheet steel5.5 W/m²K4.26 W/m²K
Plastic or non-metallic3.5 W/m²KSame

Published coefficients for unpainted stainless differ by about a factor of two, because bare stainless radiates heat less well than paint. The calculator uses 3.7 W/m²K, as our product pages do, and shows the rise with the lowest published value as a check. Where each number comes from.

Worked example

24 × 20 × 8 in, 74.1 W, 35 °C room, 45 °C limit

  1. Heat load. The heat guide's example panel loses 59.3 W (power supply, PLC, switch, small PC, relays). With the 25% margin: 59.3 × 1.25 = 74.1 W.
  2. Allowed rise. The lowest-rated device allows 50 °C; we design for 45 °C inside on a 35 °C day: ΔT = 45 − 35 = 10 K (18 °F).
  3. Effective surface. The 24 × 20 × 8 in enclosure on a wall, H, W, D = 0.610, 0.508, 0.203 m: A = 1.4 × 0.508 × (0.610 + 0.203) + 1.8 × 0.203 × 0.610 = 0.801 m².
  4. What the walls shed. k × A = 3.7 × 0.801 = 2.96 W/K; at the allowed rise, 2.96 × 10 = 29.6 W.
  5. Sealed, it would reach. ΔT = 74.1 / 2.96 = 25.0 K, so about 60 °C inside: above the limit, 44.5 W more than the walls shed.
  6. Cooling. Heat exchanger: (74.1 − 29.6) / 10 = 4.4 W/K. Air conditioner holding 45 °C: at least 44.5 W; holding 35 °C inside in a 45 °C room: 74.1 + 2.96 × 10 = 104 W. Fan and filter: 3.1 × 74.1 / 10 = 23 m³/h (13 CFM), open loop.
  7. Or a larger size. To stay sealed the walls need A = 74.1 / (3.7 × 10) = 2.00 m², 2.5 times this enclosure. The smallest of our sizes with that much surface is the 42 × 36 × 8 in (2.02 m²).

The heat calculation guide works the same example with the plain surface area (0.764 m², the five faces that are not against the wall); the IEC/TR 60890 surface used here and on the product pages gives 0.801 m², within 5%.

Assumptions

What the numbers assume

By size

Heat our sizes shed sealed

What a sealed stainless enclosure sheds (k = 3.7 W/m²K, IEC/TR 60890 surface)
SizeEffective surfaceShed on a wall, 10 KShed on a wall, 20 KShed exposed on all sides, 10 K
12 × 10 × 6 in0.25 m²≈ 9 W≈ 18 W≈ 10 W
16 × 12 × 8 in0.41 m²≈ 15 W≈ 30 W≈ 17 W
20 × 16 × 8 in0.59 m²≈ 22 W≈ 44 W≈ 25 W
24 × 20 × 8 in0.80 m²≈ 30 W≈ 59 W≈ 34 W
30 × 24 × 10 in1.22 m²≈ 45 W≈ 90 W≈ 52 W
36 × 30 × 12 in1.80 m²≈ 67 W≈ 133 W≈ 77 W
10.1" HMI housing on an arm0.20 m²––≈ 8 W
15.6" HMI housing on an arm0.36 m²––≈ 13 W
21.5" HMI housing on an arm0.54 m²––≈ 20 W

Every size, with its inside, panel and depth: the enclosure size chart.

Buying guides

Heat, moisture, sun and size.

All guides

Walls not enough?

More surface, or the cooling built in

The enclosure builder makes the size with the surface your load needs, and adds an air-to-air heat exchanger, an air conditioner, a fan and filter, a heater or a sun shield, in 3D. Drawn for your approval and delivered in 10 business days.

Asked and answered

Enclosure heat calculator: questions

How do I calculate enclosure heat dissipation?

Multiply the heat transfer coefficient k by the effective surface A and the allowed temperature rise: Q = k × A × ΔT. A 24 × 20 × 8 in stainless enclosure on a wall has A = 0.801 m², so at k = 3.7 W/m²K and a 10 K rise it sheds about 30 W.

How do I calculate the temperature rise inside an enclosure?

Divide the heat load by k × A: ΔT = Q / (k × A). 74.1 W in that enclosure gives 74.1 / 2.96 = 25 K, so about 60 °C inside on a 35 °C day.

Which heat transfer coefficient should I use for stainless steel?

Published values for unpainted stainless differ: enclosure climate-control catalogues give about 3.7 W/m²K, one heat exchanger selection guide about 1.94. Both are lower than painted steel (about 5.5), because bare stainless radiates heat less well than paint. The calculator uses 3.7, as our product pages do, and shows the rise with 1.94 as a check.

Does mounting change how much heat an enclosure sheds?

Yes. On a wall the back sheds nothing; exposed on all sides, the same enclosure has more effective surface. For the 24 × 20 × 8 in enclosure, IEC/TR 60890 gives 0.801 m² on a wall and 0.925 m² exposed on all sides.

When does a sealed enclosure need a heat exchanger or an air conditioner?

When the walls cannot shed the load at the rise you can allow. A heat exchanger keeps the enclosure sealed but only works while the outside air is cooler than the inside; an air conditioner can hold the inside below ambient. A fan and filter is cheaper but open loop: the enclosure is no longer NEMA 4X unless the fan unit is rated 4X.