Wire ferrules on spring clamp terminals: when they fit

Ferrule stranded conductors up to about 22 AWG (0.25–0.5 mm² bands); at 18 AWG the finished barrel runs about 1.8 mm against the 1.6 mm opening of a 28–14 AWG spring clamp, so twist the strands and clamp them bare. Measure the finished barrel with calipers before it goes in.

NEMA4 Enclosure engineering team · Published November 14, 2026 · 6 min read

Short answer: ferrule your stranded wire up to about 22 AWG, in the 0.25–0.5 mm² bands, and land 18 AWG and larger as bare, lightly twisted strands. A spring clamp rated 28–14 AWG is built around the bare conductor, and 14 AWG measures 1.63 mm [0.064 in] across. A 0.75 mm² ferrule crimped onto that signal wire finishes near 1.8 mm [0.071 in], which the cage reads as a 13 AWG conductor, one size past its maximum. That is why insertion turns snug and removal takes wiggling. The finished barrel is what fits or fails, so measure it with calipers; the table below makes the call for each size you are likely to land.

The clamp opens for the conductor, not the gauge

A spring-cage terminal presses the conductor between a fixed current bar and a sprung cage, and the slot the conductor passes through decides the fit. On a block rated 28–14 AWG, that slot follows the largest rated conductor, 14 AWG, whatever you feed it. Here is where spring cages and screw-clamp terminal blocks part company: a screw lifts as far as its wire guard allows, while the cage keeps one fixed opening.

Two consequences follow. A crimped barrel sits 0.6–0.8 mm wider than the strands inside it at these sizes, and a square die flattens it further. And the terminal's data usually prints a connecting capacity with ferrule next to the bare range, a smaller number your ferruled wire has to live within. Measure across the finished crimp, flats and tool marks included, and compare that figure with the slot.

Your stranded wire Copper area Bare diameter Ferrule band Finished barrel, round die Call for a 1.6 mm slot
24 AWG 0.2 mm² 0.51 mm 0.25 mm² about 1.2 mm Ferrule it
22 AWG 0.34 mm² 0.64 mm 0.25–0.34 mm² about 1.3 mm Ferrule it
20 AWG 0.5 mm² 0.81 mm 0.5 mm² 1.5–1.6 mm Measure, then decide
18 AWG 0.75 mm² 1.02 mm 0.75 mm² about 1.8 mm Clamp it bare
16–14 AWG 1.3–2.1 mm² 1.31–1.63 mm 1.5–2.5 mm² 2 mm and up Clamp it bare

Barrel dimensions and collar colours follow DIN 46228, which gives each cross-section its own band; 1.0 mm² and 1.5 mm² collars look alike in poor light, so work from a marked strip. The range runs up to 16 mm² [about 6 AWG], territory for screw terminals and busbar hardware rather than I/O cages.

The 18 AWG case in numbers

Take the classic case: a stranded signal wire on a pluggable I/O block rated 28–14 AWG.

  • The slot follows 14 AWG, so 1.63 mm is your usable opening.
  • The stranded wire is 1.02 mm bare: 1.02 ÷ 1.63 = 0.63, so bare strands use 63 % of the slot and sit with margin.
  • The correct band for that copper is 0.75 mm², and a round die finishes at about 1.8 mm. That is 1.8 − 1.63 = 0.17 mm of oversize — 1.8 ÷ 1.63 = 1.10, so 10 % over.
  • To the cage, 1.8 mm is a 13 AWG conductor (1.83 mm), one size past the maximum.

Cut the ferrule off and clamp the wire bare, with a quarter-twist to keep the bundle together. Twist-and-clamp is one of the serviceable joints worth choosing for field wiring, and a cage grips stranded copper along the full slot width. If your drawing insists on a ferrule here, the 0.5 mm² band is the only candidate: it takes these strands only when they run thin, and its barrel finishes at 1.5–1.6 mm, right at the limit. Measure it, and send anything over 1.6 mm back to bare.

What you need

  • Insulated ferrules to the DIN 46228 form, 0.25 and 0.5 mm², on marked strips
  • A ratchet crimper with dies engraved for those bands, hex or square profile
  • Calipers that read to 0.05 mm
  • The release key supplied with the block, or a 2.5–3 mm flat screwdriver that enters the tool slot freely
  • Wire stripped to the barrel length; 10 mm [0.39 in] is the common barrel

One band suits one copper area: the conductor fills the barrel, with strands visible at the barrel end after the crimp. Cages hold solid and stranded conductors alike with the wire bare, so the ferrule question rides on stranded wire only; the solid versus stranded choice is a separate decision.

Crimp and land it, step by step

  1. Pick the band from the table by copper area: 24–22 AWG takes 0.25–0.34 mm², 20 AWG takes 0.5 mm², and the 0.75 mm² wire goes in bare.
  2. Strip to the barrel length — 10 mm [0.39 in] on the common ferrule — and seat the insulation into the collar.
  3. Crimp in the matching die and let the ratchet finish its cycle. A barrel you can still turn on the strands is a joint that runs hot later.
  4. Measure the finished barrel at its widest, flats included. Under 1.6 mm on a 28–14 AWG block, carry on; at 1.6 mm or over, cut the ferrule off, re-strip and land the wire bare.
  5. Open the cage with the key and hold it. A square-crimped barrel enters with its flats lined up on the slot, so rotate it until it drops in.
  6. Push the ferrule, or the lightly twisted strands, straight in to full depth with finger pressure alone. Resistance part-way down means oversize, and step 4 has the answer.
  7. Release the key, then pull the wire straight back with about 20 N [4.5 lbf] — the pull of a 2 kg [4.4 lb] mass, as a field check. The conductor stays put.
  8. Label the point and repeat down the row.

Prove it holds

Two checks close out each termination, and both take seconds:

  • Tug: pull straight along the wire as in step 7. Movement, or a barrel that slides, sends you back to step 3.
  • Movement: with the loop powered and your meter on the 4–20 mA reading, wiggle the wire at the terminal and rock the connector body lightly. The reading holds through the wiggle on a good point.

Look at the insulation while you are in there. It ends at the collar with every strand inside the barrel; a short strip leaves the cage gripping insulation, the same failure you see when wire falls out at the strip on a screw terminal.

A cage that has already been forced

These symptoms point at the clamp rather than the wire:

  • The ferrule seats only under force, with the cage held open
  • Removal needs wiggling and turning after the cage is released
  • A light tap on the connector drops one analogue input to zero
  • The point has history with a snug ferrule

In order of likelihood, the cause is:

  1. A finished barrel over the slot, forced in and dragged back out. Crimp flats and tool marks act as barbs and bend the cage fingers on the way past.
  2. A square-crimped ferrule rotated inside the slot while being worked out.
  3. A spring fatigued by repeated opening with an oversized screwdriver.
  4. Insulation in the clamp from a short strip.

Cut the old termination off, re-strip to the barrel length, land the conductor bare and run both checks. When the reading still drops on a wiggle, replace the block: on a pluggable I/O block that is a swap, and on fixed wiring it means the block or its carrier. Power the rack down and lock it out first, because the logic side can carry 24 V DC and the field side more.

While the block is out, drop the housing colour from the suspect list. Most I/O families sell a standard block and a gold-contact version for thermocouple and millivolt signals, and the clamp is the same part in both. A black housing grips exactly like a grey one, so an intermittent input is a termination problem either way.

What to order for the panel

  • Ferrule stock in the bands your wires use; for signal work, 0.25 and 0.5 mm² covers 24–20 AWG
  • One ratchet crimper with the dies engraved for those bands
  • A few spare terminal blocks, because forced ferrules claim cages
  • A point count, so the ferrules you buy match the wires you will land — counting terminal points, not blocks keeps that honest

When the block count starts to size the box, the enclosure selector takes DIN module count as an input, and the backplate and DIN rail layout guide sets the rail and duct spacing those blocks need.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
6 × 6 × 4 in304 stainless6 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
8 × 6 × 4 in304 stainless8 x 6 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
10 × 8 × 4 in304 stainless10 x 8 x 4 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Do ferrules belong on screw-clamp terminals too?

Yes, and at any size your panel uses. A screw clamp lifts as wide as its wire guard, so a 0.75 mm² ferrule seats with finger pressure, and ferrule stock runs to 16 mm² [about 6 AWG] for feeder lugs. The finished-barrel limit bites only on spring cages, where the opening is fixed at the maximum conductor diameter.

Can I land two ferruled wires in one spring-clamp point?

Use a twin ferrule, one barrel marked 2 × 0.5 mm² that crimps both conductors together, so the cage still grips a single barrel. Two separate ferrules side by side spread the spring unevenly and leave both joints loose. One conductor per point is the rule; counting points rather than blocks keeps the panel honest.

Should I ferrule solid wire?

Ferrules are for stranded conductors. Solid wire has nothing to bundle, so the crimped barrel only adds diameter, about 0.8 mm on a 0.75 mm² band, and buys you nothing. Land solid conductors bare and let the cage or the screw bear directly on the copper.

What makes a 4–20 mA input drop to zero when the connector wiggles?

Nine times in ten it is a stressed cage, usually from forcing an oversized ferrule in and dragging it back out. Re-terminate the wire bare, tug it at about 20 N [4.5 lbf], then wiggle the connector while you watch the loop. A stable reading closes the case; a drop to zero means you replace the block.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start a junction box from 6 × 6 × 4 inRequest a custom quote

Stainless junction boxes: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides