Short answer: "weatherproof" on a box label is usually NEMA 3R — a rain, sleet and external-ice rating, proven with a 5 in/h [127 mm/h] shower falling straight down for 1 h. Nothing in that test sprays sideways or pushes water through a seal. A box that can be hit by a hose, splashed or beaten by wind-driven rain needs NEMA 4 or 4X, proven with a 65 gal/min [246 L/min] hose jet from 10 ft [3 m] for 5 min. "Waterproof" is not a rating at all; read the number behind the word before you hang the box.
What each rating is actually tested for
The words on the label are marketing; the number under them is the rating. NEMA 250 defines the enclosure Types, and the manufacturer tests its own boxes and declares the rating. NEMA publishes the definitions and does not test, certify or endorse enclosures. A UL listed enclosure has been evaluated by UL to UL 50E, the listing standard for the same water, ice and corrosion tests. In a US installation, NEC 110.28 keeps the two families apart: an ip code does not stand in for an enclosure Type. Table 110.28 lists which Type suits which location.
| What the test covers | Type 3R, the usual "weatherproof" | Type 4 / 4X, the hose rating |
|---|---|---|
| Rain from above | 5 in/h [127 mm/h] for 1 h | covered |
| Hose-directed water | not in the test | 65 gal/min [246 L/min] through a 1 in [25.4 mm] nozzle from 10 ft [3 m] for 5 min |
| Splashing water | not in the test | part of the NEMA 250 Type 4 definition |
| Sleet and external ice | tested | tested |
| Windblown dust | not covered | in the NEMA 250 Type 4 definition |
| Corrosion | not tested (Type 3RX adds a 200 h salt-spray test) | 4X adds a 200 h salt-spray test against an AISI 304 specimen |
The IEC 60529 digits describe water differently. IPX4 means splashing water, IPX5 means a jet through a 6.3 mm nozzle at 12.5 L/min, and IPX6 means a powerful jet through a 12.5 mm nozzle at 100 L/min from 2.5 to 3 m for at least 3 min. The NEMA hose test does the same job with 246 L/min through a 1 in nozzle from the same 3 m standoff: 2.5 times the flow through a nozzle twice the bore. Same intent, different tests. The IP-to-NEMA conversion article shows how the pairs line up, the IP rating chart guide lists every digit, and the 4X vs IP66 guide shows where the pairing holds and where it does not.
How much water each test throws at a 10 x 8 in box
The scale of the difference is easiest to see as water volume. Take, for this example, a wall-mount junction box with a 10 x 8 in [254 x 203 mm] top — a common footprint for a splice-and-terminal box — and run both tests against it.
The inputs, each from NEMA 250's test set-up: rain at 5 in/h [127 mm/h] for 1 h (Type 3R); hose flow at 65 gal/min [246 L/min] for 5 min (Type 4); conversions 1 US gal = 231 in³ = 3.785 L.
The rule in words: rain volume is rainfall depth times the box footprint; hose volume is flow rate times duration.
Rain: 10 in x 8 in = 80 in² of top. 80 in² x 5 in = 400 in³. 400 in³ / 231 in³ per gal = 1.73 gal [6.5 L] over the hour.
Hose: 65 gal/min x 5 min = 325 gal [1,230 L], thrown at every face, not just the top.
325 / 1.73 = about 190 times the water. That ratio is the decision. A gasket, a drip edge and a weep hole are a rational strategy for the 1.73 gal a vertical shower leaves behind. They are not a strategy for 325 gal arriving as a jet. Once the exposure is a stream, the box itself has to carry the jet rating: Type 4, or 4X where corrosion rides along.
Where a weatherproof 3R box is the right rating
Type 3R covers rain from above, sleet and external ice, and it does that job well where rain is all the box meets: under an eave or canopy, on an interior plant wall, on a pole out of every spray path. Choose it when no hose, wash-down or driven rain can reach the box and the air is mild and inland, away from salt. Where temperature swings breed condensation, add a bottom drain: NEC 314.15 permits approved drainage openings of 1/8 in [3 mm] to 1/4 in [6 mm] in boxes installed in wet locations. The 3R vs 4 fundamentals lay out the two tests side by side, and the soaked-junction-box article traces what to do when a correctly rated 3R box still takes water.
Where the hose-rated 4X box earns its keep
Specify Type 4 where water arrives sideways: splash zones near wash-down, outdoor walls that storms sweep, anything a hose can reach. Specify 4X — the same tests plus a 200 h salt-spray corrosion test — wherever the water is also aggressive: salt air, sanitizers, coastal plants. Match the metal to the water: 316L stainless near salt and chlorides, 304 inland. Our own wall-mount boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed. You can see them at 316L wall-mount enclosures and in the junction-box sizes for the small splicing footprints.
One rule keeps the rating alive after installation: the weakest opening sets the rating. A 4X box with an unrated cord grip or a field-cut hole is a lower-rated box, whatever the label says. For a food-plant hose-down schedule, the wash-down article picks between 4 and 4X, and the outdoor 3R vs 4X article compares rust life beside the rain rating.
Why a soaked box needs a rating change, not a weep hole
A weep hole has a real job: it empties the condensate and the odd blown-in splash that even a correct 3R installation collects. NEC 314.15 sizes that job — approved drainage openings of 1/8 to 1/4 in [3-6 mm], bottom face, wet locations — and a 6 mm hole is exactly as big as that job. Under a 246 L/min jet it is nothing; the box fills faster than it drains, and the drain you drilled becomes the place the water gets in. Mounting holes act on a rating the same way: every hole you add is a new place water can test.
The fix is a rating change, in this order. Name the water the box meets: rain only, or hose and splash. Select the Type that matches. Seal every entry with fittings rated to the same Type. Keep a drain only where the exposure stays rain-level. Before you open a box that has been sitting wet, de-energize the circuit and verify absence of voltage at the terminals.
The decision by environment
| Where the box sits | Rating to specify | Why |
|---|---|---|
| Under an eave or canopy, inland, vertical rain only | Type 3R | the test matches the exposure; add a 1/8-1/4 in bottom drain where condensation collects |
| Exposed outdoors, wind-driven rain | Type 4 (4X stainless) | the test throws jets, not just rain |
| Splash zone or daily wash-down | Type 4X, 316L | hose and salt-spray tests; 304 only inland |
| Coast, salt air within sight of water | Type 4X, 316L | the 200 h salt-spray test is the point |
| Soil line, standing water, immersion | not a 3R-vs-4X choice | direct-burial listed equipment or a custom design review naming depth and duration |
If you inherit a box labelled only "weatherproof", read it as a rain claim until you find the Type number. The next water event — a hose, a storm driven sideways — is the one that fills it. The outdoor enclosures page carries the material and rating choices for the exposed cases.
What to put on the order
- Rating line: the Type number and the exposure together — "Type 4X, hose wash-down" or "Type 3R, under-canopy rain only".
- Material: 316L where salt or sanitizers reach the box; 304 inland.
- Entries: a gland or hub at every cable opening, rated to the enclosure Type and sized to the cable OD.
- Drain: 1/8-1/4 in [3-6 mm] bottom drain where condensation is expected and the exposure stays rain-level.
- Cutouts: factory-cut to the drawing; the cutout and gland guide shows what the drawing needs.
Every box is delivered in 10 business days, anywhere in the world — counted from your order, or from your approval of the drawing on custom work.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 316L stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 316L stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is a NEMA 4X enclosure waterproof enough to sit under water?
No. Type 4X is a jet rating: water thrown at the box, never held around it. Temporary submersion starts at Type 6, whose nearest IP code is IP67 — 1 m of water for 30 min — and prolonged submersion is Type 6P. Our stock stainless boxes are manufacturer-rated NEMA 4X / IP66 and carry no immersion rating, so a box that can sit under water is a custom design review with depth, duration and fluid named.
Can I drill a weep hole in a weatherproof junction box?
Yes, within the drain rule: NEC 314.15 permits approved drainage openings of 1/8 in [3 mm] to 1/4 in [6 mm] in the bottom of a box installed in a wet location. Keep it in the bottom face and deburr it. Treat it as condensate management only — at hose flows of 65 gal/min [246 L/min] a 6 mm hole is overwhelmed, so wash-down duty still calls for a Type 4X box.
What rating does a box set into wet soil need?
None of the rain or jet ratings covers soil contact: Types 3R, 4 and 4X are tested against water arriving from outside, not against earth packed around the box. A box in or under wet ground calls for equipment listed for direct burial, or an above-grade mount with sealed entries. For splash-level wetness around the base, Type 4X in 316L holds up; for real submersion, take it to a custom review with depth and duration.
Does weatherproof also cover dust and oil?
No. NEMA 3R is tested for rain, sleet and external ice, and dust never enters its test. NEMA 250's Type 4 definition adds windblown dust to the water protection. Indoors, where the enemies are dust and dripping oil, the matched rating is NEMA 12. Its closest IEC pairing is IP54 — dust-protected, not dust-tight.