Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

VFD on a 240 V high leg: RFI filter and connection checks

Measure the supply first: on a grounded 240 V high-leg delta, all three line-to-line pairs read 240 V, but line to ground you find 120 V, 120 V and about 208 V. Feed the drive through an isolation transformer, or use a drive whose manual lists the grounded center-tap delta and remove its RFI jumper exactly as the manual directs. Never lift the protective earth; the jumper only lifts the filter capacitors.

NEMA4 Enclosure engineering team · Published November 11, 2026 · 7 min read

Short answer: measure the supply before you connect anything. A grounded 240 V high-leg delta reads the same on all three line-to-line pairs. From line to ground you will find 120 V, 120 V and about 208 V, and that 208 V corner decides the connection. Feed the drive through an isolation transformer, or use a drive whose installation manual lists the grounded center-tap delta and remove its RFI jumper exactly as that manual directs. The jumper lifts the input filter's capacitors clear of the supply; it leaves the protective earth alone. Work on a locked-out panel, and write the jumper position on the drawing so the next person finds it.

Why a balanced-looking supply stresses the drive

The rectifier inside a drive sees line-to-line voltage only, and all three pairs match, so the power path looks routine. The stress lands on a different set of parts: the input filter holds capacitors wired from each supply line to earth, and what those see is each line's voltage to ground. On a high leg those three voltages are nothing like equal.

Worked example for the common North American service, a 240 V delta secondary with one winding center-tapped and that midpoint grounded:

  • Each end of the center-tapped winding: 240 V / 2 = 120 V to earth.
  • The third corner, across both windings: 240 V × 1.732 / 2 = 208 V to earth, the same figure you get from 120 V × 1.732.
  • All three line-to-line pairs equal, so a meter on one pair reports a perfectly ordinary supply.
  • For comparison, a grounded-wye service at the same line voltage puts a symmetric 240 V / 1.732 = 138.5 V on every line; the high leg rides 208 / 138.5 = 1.5 times that, continuously, on one phase.

These are calculated values for the ideal source; a real service lands within a few volts of them. The parts between line and earth take the beating, which is why a drive on a high-leg feed can run fine for a long stretch and then fail while the motor never misbehaves.

Measure the supply before you connect anything

Use a true-RMS meter rated CAT III 600 V or better, and make the readings with the covers on and hands clear. Six numbers tell you what you actually have:

Reading Value on a high-leg service What it tells you
L1–L2, L2–L3, L3–L1 240 V each Supply magnitude; all three pairs should match
L1 to ground, L2 to ground 120 V each The center-tapped winding and its grounded midpoint
L3 to ground (high leg) 208 V The wild leg
Neutral to ground near 0 V Bonding lives at the service, not in this panel
Every line to ground 240 V each A corner-grounded delta, a different configuration

The NEC calls for the high leg to be marked orange where it lands on a panel, so treat the orange conductor as the suspect until the meter proves it. The center tap is grounded once, at the service; neutral–ground bonding happens only there, and your drive panel adds no second bond. If the six readings show the full line voltage to ground on every line, you have a corner-grounded delta: manufacturer and utility guidance discourages it for new work, so read the manual's permitted-supply list before anything else.

What you need

  • A true-RMS meter rated CAT III 600 V or better
  • The drive's nameplate model number and its installation manual
  • A lockout kit and a voltage indicator you trust
  • A torque screwdriver for the manual's input-terminal values
  • A delta-delta isolation transformer, if the manual does not list your supply
  • The maker's RFI jumper procedure for the exact model, not one from memory

Choose the feed: transformer or jumper

Two connections hold up on a high-leg feed.

Path one: the manual lists the grounded center-tap delta, which some manuals call a high-leg or unbalanced-ground supply. Remove the RFI jumper per the maker's procedure and connect the three lines; the drive runs as designed minus some filtering.

Path two: the permitted-supply list does not cover your service. Feed the drive through a delta-delta isolation transformer and set the secondary to a configuration the list does cover, most simply one left ungrounded. Grounding a secondary corner instead would put the full 240 V on every line to earth, so leave the secondary floating unless the manual names another grounded arrangement. The transformer buys a supply the manual understands. It does not always save the jumper, because a floating IT-style supply is exactly the case where manuals call for removal.

Size the transformer from the drive's rated input current on the nameplate. Worked stand-in: a 5 hp drive. The NEC full-load current tables list 15.2 A for a 5 hp, 230 V three-phase motor, and a drive draws roughly that from the line. A 7.5 kVA three-phase unit at 240 V secondary delivers 7,500 / (1.732 × 240) = 18 A, about 1.2 times the drive input, enough margin for a steady rectifier load. For heat, count on 1 to 3 % of the rating lost in the windings: 75 to 225 W going into the box at full load.

If drive and transformer share one of our stainless enclosures, rated NEMA 4X / IP66 by the manufacturer; not UL listed, resize for the added watts and depth. Sizing a VFD enclosure from heat and clearance walks that arithmetic. When the cabinet already carries a control-power transformer, decide who gets a dedicated unit; one transformer or two for a remote outdoor power cabinet covers that split.

Bond the secondary once, in the configuration you chose, and land the protective earth on the drive's PE terminal. The NEC calls the conductor path back to the source the effective ground-fault current path. The earth is not part of it, which is why the transformer frame, the enclosure and the drive bond through conductors. The enclosure grounding and bonding guide carries the details.

Set the jumper and land the conductors

  1. Lock out every feeder that can energize the panel, then prove the dead condition at the drive terminals with the meter.
  1. Wait out the drive's discharge interval — the label inside drives in the 1 to 10 hp range commonly calls for 5 to 10 minutes — and measure the DC bus terminals before touching anything.
  2. Repeat the six supply readings at the drive's input terminals and mark which line is the high leg.
  3. Remove or reposition the RFI jumper exactly as the maker's procedure shows for the configuration you confirmed. Tape the removed jumper inside the door with the date and the manual page.
  4. Land L1, L2 and L3 on the drive input and the protective earth on the PE terminal, torqued to the manual's values. The drive input wants three lines and earth; the 120 V loads run off the neutral on their own circuit.
  5. Inspect for stray strands and crossed conductors, refit the covers, and clear the locks.
  6. Apply power, take the six readings at the drive terminals once more, and only then start the motor.

Checks that prove the connection

  • The six readings at the drive terminals match the design: the line-to-line pairs all equal, and the line-to-ground set you planned for — 120 V, 120 V and 208 V on the direct feed, or a symmetric floating set behind the transformer.
  • On a floating secondary, record the line-to-ground readings at commissioning. A ground fault downstream shifts them, so the same six numbers at the next visit catch it.
  • Phase current at full load sits within the drive's input rating, 15.2 A in the 5 hp stand-in.
  • Run the noise check with the motor spinning: watch nearby instruments, encoders and network traffic while the drive works. A powered drive at idle proves nothing about interference. If noise appears, separate the low-voltage signal runs from the power wiring first; running 24 V control wire beside 120/208 V power wiring gives the spacing logic.
  • The jumper position and the supply readings live on the panel drawing, not in someone's head.

Four mistakes that cost the drive

  • Leaving the jumper in because the drive runs. Field reports describe drives on high-leg feeds that ran a long stretch, then tripped an "orP" fault once the filter parts gave out. The jumper comes out as a cure before the damage, not after; a write-up of the "orP" fault and its RFI-jumper fix follows one such case end to end.
  • Lifting the protective earth to quiet a filter complaint. The jumper was never wired to PE, and the fault path runs through the conductors you just landed.
  • Judging the supply from one pair. High-leg, corner-grounded and plain delta all read alike line to line; only the line-to-ground set tells them apart.
  • Adding an ordinary line filter afterward. Most add-on filters pack line-to-earth capacitors and bring back the exact stress the jumper removed. Earn quiet another way: shorten the motor cable, separate signal wiring, and pick any filter for the supply configuration you actually run.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
60 × 36 × 16 in304 stainless60 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
48 × 36 × 16 in304 stainless48 x 36 x 16 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
60 × 36 × 12 in304 stainless60 x 36 x 12 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Can a 240 V drive run directly on a high-leg delta?

Only when the installation manual lists the grounded center-tap delta among its permitted supply configurations, with the RFI jumper removed exactly as the manual directs before first power. Measure first: equal line-to-line readings with 120 V, 120 V and 208 V to ground identify the high leg. If the manual's list does not cover the supply, feed the drive through an isolation transformer.

What does the RFI jumper actually disconnect?

The input filter holds capacitors wired from each supply line to earth. The jumper lifts that line-to-earth network out of circuit while the line-to-line parts and the protective earth stay exactly where they were. That is why removal changes the conducted-noise performance of the drive but never removes its ground connection, and why the jumper setting follows the supply grounding, not the motor.

What size isolation transformer feeds a 5 hp drive?

Start from the drive's rated input current, not the horsepower alone. The NEC tables give roughly 15 A of line current for a 5 hp, 230 V three-phase motor, and a drive draws about that. A 7.5 kVA three-phase unit sized for that secondary delivers about 18 A, roughly 1.2 times the drive input — enough margin for a steady rectifier load.

Would grounding the high leg itself fix the problem?

No. Grounding a corner makes a corner-grounded delta, where every line sits the full line-to-line voltage above earth instead of the 120 V, 120 V and 208 V pattern. That is a different supply configuration the manual must also list, and manufacturer and utility guidance discourages it for new work. Source grounding is set once, at the service.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the plant-floor PLC cabinet buildRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides