Mark the full-load current. A panel whose loads add to less than 1 A still carries its FLA on the UL 508A nameplate. The 2020 text requires the electrical rating, and the third-edition documents we checked keep the same rule; we read UL's summary of requirements and the March 2022 revision of Supplement SA. The exception language that does exist turns on where the power comes from, not on how little the panel draws. Components fed entirely from a low-voltage limited energy source sit outside some component requirements, at 24 V DC maximum and 60 V dc open circuit. The SCCR marking stands either way, because fault current at the terminals never scales down with the load. Your plate ends up reading 0.9 A and 5 kA side by side, and the edition question is settled with the controlled text, not with a memory.
What the electrical rating on the nameplate carries
NEC 409.2 defines an industrial control panel as an assembly of two or more power circuit components, control circuit components, or both. UL 508A is the standard for listing one. The marking section puts the panel's electrical rating on the nameplate: supply voltage, number of phases, frequency and full-load current.
The full-load current is a sum, not a measurement. You add the rated input currents of everything connected to the supply, counting the largest combination your controls can run at once. A 24 V DC supply contributes its input rating, not its 2.5 A output. A pilot light counts too, if it can be on while the rest runs. The nameplate article walks every required line in order, and the panel standards overview shows where UL 508A sits beside NFPA 79 and the NEC.
NEC 409.110 adds one more line to the same plate: the enclosure type number. On our stainless wall-mount boxes that number is a manufacturer rating — rated NEMA 4X / IP66 by the manufacturer; not UL listed — while the UL 508A label covers the finished panel built inside the box. The difference between a box rating and a panel listing is the subject of the UL 50E listing guide.
What the 2022 documents actually say
The memory of a 2022 change deserves testing against paper. When UL published the third edition, it also published two things your shop can read without buying anything: a summary of the requirements and a page that tracks effective dates for changes to the standard. The 2022-era texts we read — the summary and the March 2022 revision of Supplement SA — carry the same component exception as the October 2019 text. Its idea, in our words: electrical components whose every electrical connection is made to a low-voltage limited energy source sit outside the component requirements Supplement SA would otherwise apply to them. Nothing in those pages keys any marking omission to the panel's amperage.
If a sub-1 A exception exists in the edition your shop builds to, it lives in the controlled copy and on UL's effective-dates page. A change you cannot point to in either place is not a change you can mark to. Do not release a nameplate on a remembered clause; release it on the text, with the edition noted in the panel file.
The exception that exists: limited-energy sources
UL's third-edition summary gives the working numbers for limited energy: circuits operating at 24 V DC maximum. The source itself reaches at most 60 V dc open-circuit secondary. The Supplement SA exception covers components, and it applies when all of a component's electrical connections land on such a source.
Two consequences follow for a panel with a 120 V AC incoming terminal. First, that terminal is not limited energy, whatever the loads inside draw, so the rating lines stay marked. Second, SELV is a construction classification, not a bench finding: a supply earns it through its separation design, and its certification document states it — a meter reading alone does not make it so. If your panel genuinely runs on a certified limited-energy source, that choice was made at design time with the supply documents in hand, and the edition you build to still says what gets marked for it. For the panel in front of you with a 120 V AC supply, that route is closed: mark the current.
Worked example: a 0.82 A panel, marked
Take a small panel on a 120 V AC, single-phase, 60 Hz supply, with two loads on that supply:
| Load | Input rating from its label |
|---|---|
| 24 V DC switching supply, output 2.5 A | 0.8 A at 120 V AC |
| LED pilot light on the door | 20 mA (0.02 A) |
Full-load current = 0.8 A + 0.02 A = 0.82 A, so the plate reads 0.9 A. A rating may round up; it never rounds down. When a label states watts instead of amps, divide: a 60 W door heater at 120 V AC and power factor 1 draws 60 / 120 = 0.5 A. Three-phase machine loads run the same division with 1.732 and the power factor added — calculating nameplate full-load amps for three-phase machines shows that arithmetic step by step.
The short-circuit side needs its own numbers. Say the supply's certification lists a rated short-circuit current of 5 kA rms symmetrical and the power terminal blocks are rated 10 kA. The lowest rated device in the power path sets the panel, so the plate reads SCCR 5 kA rms symmetrical. Neither the 0.82 A you summed nor the 0.9 A you marked moves that 5 kA.
SCCR rides the same plate
The sub-amp load has nothing to do with the fault. Available fault current at the panel terminals is set by the utility supply, the conductors and any transformers upstream of the box. A panel that consumes 0.82 A can still sit where 10 kA or more is available at its line side. That is why the SCCR determination walks the power circuit and takes the lowest rated device, rather than the smallest load. A current-limiting protective device at the front end can raise the rating the panel is marked with; the Supplement SB article follows how that determination changed, and terminal block SCCR shows the same lowest-device logic on one component family.
Mark both lines together. FLA and SCCR sit on the same plate, and the question of omitting one never reaches the other.
Settling the edition question in the shop
A shop that applies the UL 508A mark works under UL's Follow-Up Service. Its procedure names the edition the shop builds to. A designated manufacturer's technical representative (MTR) answers marking questions like this one with the panel file open; the MTR has passed UL's exam for the program. That is the fastest correct route, and it costs a conversation, not a guess.
The argument for your manager fits in three sentences. OSHA 29 CFR 1910.303(a) requires electrical equipment to be approved. Approved there means accepted, certified, listed, labeled or otherwise determined safe by a nationally recognized testing laboratory. A nameplate answered from memory is how inspection findings start. The standard text comes from UL or its authorized distributors, and the summary of requirements plus the effective-dates page settle what changed in the third edition in ten minutes, at no cost. How a panel gets the UL 508A label walks the shop-side process.
What to put on the order
The nameplate lives on the enclosure, so give it a home before you order the box. Leave a flat zone of door, clear of the gasket line, the hinges and the latch, sized for the shop's plate. Adhesive foil plates bond well to cleaned #4 brushed stainless; screw- or rivet-mounted plates take small holes you add to the cutout drawing. Our custom stainless boxes take the whole layout at once, every cutout and the plate zone on one drawing. Delivery is 10 business days from your approval of the drawing. Build it in 304 for most washdown lines and 316L where chlorides ride the hoses (316L wall-mount enclosures, custom enclosures).
Fit the plate after the box is mounted and the devices are in, and re-check the rating the enclosure keeps once every hole is cut (what a panel keeps after you cut it). Then the plate reads one honest set of numbers: 120 V AC, 1 phase, 60 Hz, 0.9 A, SCCR 5 kA rms symmetrical.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does UL 508A let you leave the FLA off a panel under 1 A?
Mark it. The electrical rating carries supply voltage, phases, frequency and full-load current, and no edition we could read — the 2020 text, UL's third-edition summary, the March 2022 Supplement SA revision — writes an omission below any amperage. Sum the input currents of everything the controls can run together: 0.8 A plus 0.02 A is a 0.9 A marking after rounding.
What counts as a low-voltage limited energy source in UL 508A?
UL's third-edition summary describes the allowance: circuits operating at 24 V DC maximum, fed by a source with an open-circuit secondary voltage up to 60 V dc. The source's certification carries that classification and the circuit's separation construction backs it. A 120 V AC incoming terminal is not limited energy no matter how small the loads are, and the Supplement SA exception applies only where every electrical connection lands on such a source.
Can I declare my panel SELV and skip the current marking?
Skip nothing. SELV names a separation construction: the supply keeps its output apart from hazardous voltage by design, and the supply's certification states that property. A 24 V DC reading on a meter is a voltage, not a classification. Take the classification from the supply documents, read the limited-energy rules in the edition you build to, and expect the rating lines to be marked in either case.
Does the SCCR marking disappear on a panel that draws under 1 A?
It stays. Short-circuit current rating comes from the withstand and interrupting ratings of the power-circuit components, and fault current at the panel terminals is set by the supply upstream, not by the 0.9 A the panel draws. In the worked example the supply's certification gives 5 kA and the power blocks 10 kA, so the plate reads SCCR 5 kA rms symmetrical beside a 0.9 A full-load current.
Where does the nameplate go on a stainless enclosure?
Outside, where it stays readable after installation: a flat area of door clear of the gasket line, the hinges and the latch, on the #4 brushed face. Adhesive foil plates bond well to cleaned brushed stainless; screw- or rivet-mounted plates add two to four holes to the cutout drawing. On a custom box you name the plate zone with the rest of the layout, delivered in 10 business days from drawing approval.