Skip the separate compartment. Mount the servo drives, the control supply, the relay bank and the motion controller on one bonded plate in one grounded steel cabinet. Put your effort into the wiring instead: keep motor leads and signal wiring about 12 in [300 mm] apart, bond each signal shield to chassis at one end with a full-circumference clamp, and snub every relay coil. Drive housings and cabinet steel already do the shielding — the EMC standard for drives tests the assembled system to emission limits inside that housing, and at 35 MHz, where fast PWM edges put their energy, the wavelength is 8.6 m, so a 3 mm cabinet seam couples almost nothing while a 5 m motor cable is a working antenna. The sections below give the separation, shield-termination and suppression numbers, one worked example, and the three cases where steel partitioning still pays.
Do PWM servo drives need their own metal compartment in the cabinet?
Mount all three drives, the 24 V supply, the relay bank and the motion controller on one bonded plate: at the frequencies PWM edges generate, the cabinet steel already outperforms any sub-compartment you could add, and the drive makers design and test for exactly that layout.
A PWM servo amplifier is a tested emission source in a closed metal housing, not a bare oscillator. The maker declares the whole power drive system — housing, motor cable, earthing — against the emission limits, so the shielding work your compartment would repeat is already done. A compartment also fails at its own boundary. Every motor lead and encoder cable pierces the wall at the exact frequencies you care about, and each penetration needs the same gland and clamp discipline as the main cabinet. Walls without entry discipline leak where it matters. Put the sheet metal into backplate area and duct grouping instead — both ship in our builds — and keep all three drives, the control supply and the controller on one bonded plate.
What does the drive's own housing already shield?
The drive's own steel housing is the first shield, and the EMC standard for adjustable-speed drives (IEC 61800-3) sets emission and immunity limits the drive must meet as tested — in that housing, with the motor cable and earthing the maker specifies.
Inside the housing, the switching field between bus and motor terminals stays put. Datasheets list carrier frequencies of 4 to 16 kHz for most servo sizes — audio, not radio. The radio content comes from the edges: a fast output edge throws energy into the tens of megahertz, and the housing holds that within its lapped seams and gland walls. What no housing holds is the common-mode current the drive injects into its own motor leads. Stray capacitance in the cable and motor returns switching current through earth, and the cable becomes the radiator. The housing ends at its gland; the cable system after it is your design. Treat the motor-lead run as the project: shield it where the drive manual calls for it, bond that shield at both ends, and keep it clear of feedback wiring — the motor-cable shielding article for VFDs in a steel enclosure walks the same path.
Where does servo RF actually escape a steel cabinet?
Through the cables, not the seams: at 35 MHz the wavelength is 8.6 m, a 3 mm gasket seam couples a vanishing share of any field, and a 5 m motor lead is already 0.58 wavelengths of live antenna — the worked example below puts the arithmetic on all three.
A seam only matters once its longest dimension approaches a half-wavelength; below that, it couples little of the field. The worked example puts numbers on the three leak paths for a three-axis retrofit box.
Worked example — assumed inputs: a 10 ns output-edge rise time and a 5 m motor-lead run. Read both from your drive datasheet and your layout; the method stays the same with other values.
- Edge bandwidth: 0.35 / 10 ns = 35 MHz, by the usual bandwidth ≈ 0.35 / rise-time rule.
- Wavelength there: 300 / 35 ≈ 8.6 m, so a slot couples efficiently only near a half-wave: 4.3 m.
- Cabinet seam: a 3 mm gasket gap is 0.07% of that half-wave. The steel leaks essentially nothing at these frequencies.
- Motor lead: 5 m works out to 0.58 λ — a functioning antenna for common-mode current, radiating into the room and back into any cable that re-enters the cabinet.
- Shield pigtail: a 2 in [50 mm] tail of drain wire, at roughly 1 nH per millimetre of straight wire, is 50 nH. At 35 MHz that is reactance 2πfL = 2π × 35 MHz × 50 nH ≈ 11 Ω in series with a screen that should read 0 Ω. A full-circumference clamp reads near zero.
The ranking falls straight out of the arithmetic: the cable is the radiator, the pigtail is the second loss, and the seams come last. Spend your hour where the numbers point.
How close can motor leads run to encoder and command cables?
Drive installation guides ask for about 12 in [300 mm] between motor leads and encoder, resolver or command wiring; inside a crowded cabinet, cross the two groups at 90° where paths meet and add a bonded steel barrier along any run that stays closer.
Distance works because coupling between parallel runs drops fast with spacing, and because the groups want opposite things: the motor lead exists to dump switching current, the encoder pair exists to carry a quiet reference. Run each class in its own duct or conduit, and keep a hand-width of air between conduit runs that share the machine path. Do not share one conduit between motor leads and encoder cable — the cross-talk article on VFD output cables sharing one conduit shows the failure you buy. Where a crossing is unavoidable, make it at 90°; the coupling capacitance stays tiny for the few centimetres the crossing lasts. What moves the 12 in: a shielded motor cable bonded at both ends, exactly as drive manuals specify, lets the routing tighten; a long unshielded run at high current — say, a 10 A axis — wants more, not less. Inside the cabinet, group the ducts by class and keep feedback on the opposite side of the plate from the drive ducts; the servo-drive and computer wiring separation article lays those zones out.
| Wiring group | Carries | Separation from motor leads | How it is handled |
|---|---|---|---|
| Motor leads (U, V, W) | Chopped DC at the 4-16 kHz carrier | — | Own conduit; shield bonded at both ends per the drive manual |
| Encoder / resolver feedback | Low-level counts | 12 in [300 mm] | Shielded cable; one 360° clamp at the controller chassis |
| Command and ±10 V analog | Microamp references | The same distance | Twisted pairs in their own duct |
| Relay and contactor coils | Opening transients | Any | Suppressed at every coil |
Where do encoder and feedback shields terminate?
Once per cable, at the controller or drive end, on a full-circumference (360°) clamp to bare chassis metal: a drive maker's motion installation guide credits that chassis bond with canceling the common-mode voltage induced on the shield, and it keeps loop current off the board ground.
One end, because two ends close a loop: the shield then conducts between two earthed points, and any potential difference between them drives current through it — building-ground hum and switching edges both find that path. Chassis, not board ground: a board ties its signal ground to chassis through bypass capacitors, so shield current dumped on the board modulates the analog reference the encoders count against. The analog ground-offset article shows that failure mode, and the shield-grounding article for VFD control cables applies the same one-end rule. Terminate with a full-circumference clamp on bare metal, and scrape the plate under the clamp first — NEC 250.12 requires paint and other nonconductive coatings removed from the contact surfaces at bonding connections. The worked example tells you why the clamp beats a folded-back braid: the tail's series impedance is a wall only until you rebuild it from wire. At the far end, trim the shield short, insulate it, and land only the conductors. The plate-to-cabinet bond underneath all of it is covered in the grounding and bonding guide.
What keeps relay and contactor coils from injecting spikes?
Fit an RC suppressor across every AC coil and a flyback diode across every DC coil: the catalog pair of 0.1 µF in series with 100 Ω, listed for 24 V relay coils, clamps the opening spike at the coil instead of letting it ride the 24 V bus.
A coil stores energy in its iron while energized; open the contact and the collapsing field delivers a spike that arcs across the opening contact and couples into every run near it. At the coil, the suppressor sits millimetres from the source. Across the panel, the same spike rides the bus past the feedback electronics as a wired antenna. For AC coils, fit the RC pair across the coil terminals. For DC coils, a flyback diode does the same job, rated at the coil current, cathode to the positive side. Suppress switched motor loads too: coolant pumps and fan motors fed through relays put the same transient on their power pair, so the suppressor belongs across the load terminals as well. Feed the rail from a switching supply, which holds its regulation while coils switch, and choose the rail's reference deliberately — the grounding article on 24 V DC in a control enclosure walks that choice. On longer runs, twisted pairs keep the loop area small; the twisted-pairs article for grounded enclosures shows when it pays.
When does a steel partition earn its place in the cabinet?
Three cases need the steel: the drive manual calls for a barrier, sub-micron scale feedback sits beside drive outputs, or a small cabinet must hold a high-current axis with the motion controller — say, a 20 A axis in a box just bigger than its drives.
The barrier works only when it is bonded and its entries are planned: continuous steel from plate to cabinet wall, screwed through bare contact spots top and bottom, with every cable crossing made through a clamped gland in the barrier — never a bare hole with a loose grommet. A partition floating on paint is decoration. The decision, case by case:
- Three-axis retrofit, standard-count encoders, axes up to about 10 A: skip the compartment. Separation, one-end chassis bonds and coil suppression carry the cabinet — that is the worked example's build.
- Glass scales or sub-micron feedback sharing plate space with drive outputs: bonded steel barrier between the power ducts and the feedback ducts.
- The drive manual or the project spec calls for a barrier or compartment: build what the document shows — the maker tested its emission margins that way.
One safety note before reworking a cabinet that has run: lock out and verify absence of voltage at the drive terminals before the first screw comes out. Then run the axes with the drives switching and watch the encoder counts; the proof lives in the counts, not the walls.
What do you put on the order?
Order one steel cabinet with the cable entries split by group — motor leads entering low on one wall, feedback and command entering high on the opposite wall — and give every entry its own cutout sized to its gland or clamp plate.
Send the cable groups with the drawing: which wall each group enters, gland sizes, and where the shield clamps land, and we cut every entry to match, from one piece, delivered in 10 business days from your approval of the drawing. Split the entries the way the plate is zoned: motor leads low on one wall, feedback and command high on the other, I/O wherever the duct lands. The custom enclosure page takes the cutout layout, and the backplate layout guide sets the duct and rail grouping that keeps the classes apart. For washdown, brine or salt air, order the same build in 316L: the 316L wall-mount enclosures are rated NEMA 4X / IP66 by the manufacturer and are not UL listed, with a hinged gasketed door and a removable mounting panel. One steel cabinet, one bonded plate, entries split by group — that is the whole compartment a servo cabinet needs.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a bonded steel partition do the same job as a separate compartment?
For nearly every cabinet, yes. A partition bonded top and bottom between the drive-output group and the feedback group blocks the coupling path that matters. A compartment helps only when its cable openings are partitioned too: a 3 mm seam leaks almost nothing against a wavelength measured in metres, so the walls were never the leak. Reserve a full compartment for the cases the drive manual itself demands, because the maker tested its emission margins that way.
Can the 24 V supply share the cabinet with three servo drives?
Yes. Feed the rail from a switching supply, route its output with the control group instead of beside the motor leads, and suppress every coil it feeds — an unsuppressed 24 V coil can spike to tens of volts when its contact opens. Decide the reference on purpose: bond the 0 V terminal to the plate at one point, or leave it floating by design. Either works when it is chosen once and kept consistent.
What happens if an encoder shield is bonded at both ends?
You close a loop between two earthed points. Any potential difference between them drives current through the shield — 100 mV across 10 mΩ of braid is 10 A — and that current modulates the ground the encoder counts against. Bond feedback shields at one end, the controller chassis. Motor-cable shields are the exception: bond them at both ends, exactly as the drive manual shows, because that braid screens the switching current itself.
Do the same rules cover a stepper drive cabinet?
Yes. A stepper chops its winding current the same way, with edges just as fast, so keep motor leads and logic wiring apart by the same 12 in [300 mm], cross at right angles where space runs out, bond each logic shield once at the controller chassis, and snub every coil. An open-loop stepper holds position through small noise but still loses steps when a logic line picks up a switching edge.