Short answer: choose the connector before the port count, because ST stops at 12 ports. The 6-port and 12-port DIN rail LIUs — rail-mount fiber patch panels — accept SC, ST and LC. The 24-port accepts SC or LC only, so an ST plant above 12 fibers runs two 12-port units on the same rail. All three clip onto 35 mm DIN rail with a splice tray inside, and a passive panel adds nothing to the heat load. The enclosure around it carries the rest of the decision: about 2 in [50 mm] of clear rail above the housing for the tray, and a bend budget of 30 mm [1.2 in] static, 60 mm [2.4 in] under pull, for the cord between tray and gland.
Pick the connector before the port count
The port count settles itself once the connector is fixed, so settle the connector first. The three rail-mount housings differ in capacity and in what they accept at the faceplate:
| Housing | Ports | Connectors | Termination | Best fit |
|---|---|---|---|---|
| 6-port LIU | 6 | SC, ST, LC | Fusion splice or direct | One or two drops in a tight box |
| 12-port LIU | 12 | SC, ST, LC | Fusion splice or direct | Machine panels, camera and CCTV runs, spares |
| 24-port LIU | 24 | SC or LC | Fusion splice or direct | Fiber-heavy panels, several incoming cables |
ST is the constraint. Both smaller housings list SC, ST and LC; the 24-port lists SC or LC. Above 12 ST ports, your decision is two 12-port units side by side on the same 35 mm rail, which keeps one connector family and one spares bin.
LC buys density. An LC duplex coupling occupies roughly half the faceplate width of an SC duplex, which is how 24 ports fit one housing; choose it when the spares must ride in the same unit. SC is the ubiquitous, rugged choice that matches most existing plant cords. All three housings take fusion splicing with pigtails in the tray or direct termination of the connector onto the fiber, so pick one style per plant standard — the tray holds either. The case for DIN-rail patch panels that protect fixed PLC network cabling is the same on glass: fixed links terminate on the rail, never on dangling couplers.
Where the housing sits on the backplate
Clip it to the 35 mm rail on the low-voltage side of the plate, in the row with your electronics or on its own short piece. Leave about 2 in [50 mm] of clear space above the housing: the splice tray lifts out upward, and a wire duct above it turns a ten-minute splice into a strip-down.
Fiber carries light, so it needs no separation from power wiring for electrical noise. The 50 % wire-duct fill ceiling that one duct maker ties to NFPA 79-2012 13.5.2 governs round copper conductors, and your fiber rides outside the duct. Give it mechanical room instead: clear of duct edges, the hinge side, and anything the closing door could crush. The backplate and DIN rail layout guide handles the copper row, and finding the minimum enclosure depth for DIN rail devices walks the depth check — a LIU adds the cord's pulling radius in front of the faceplate.
The bend radius sizes the run
Cable installation guides give every fiber cable two radii: a static one for the installed cable at about 10 × outside diameter, and a larger one while it is under tension at about 20 × OD. For the 3.0 mm duplex cord these links usually use, that arithmetic is 3.0 mm × 10 = 30 mm [1.2 in] installed and 3.0 mm × 20 = 60 mm [2.4 in] while you pull or dress it. Bare fiber inside the tray follows its own rule of thumb, 300 × the cladding diameter; the standard 125 µm cladding puts that at 300 × 0.125 mm, about 38 mm [1.5 in].
| Fiber in the run | Rule of thumb | Radius to keep |
|---|---|---|
| Duplex cord, installed | 10 × OD | 30 mm [1.2 in] |
| Duplex cord, under pull | 20 × OD | 60 mm [2.4 in] |
| Bare fiber in the splice tray | 300 × 125 µm cladding | about 38 mm [1.5 in] |
The numbers scale with jacket: the same two rules give a 5 mm cord 50 mm [2 in] static and 100 mm [3.9 in] under pull. Turn them into clear space — the pulling radius below the housing before the first gland, 30 mm [1.2 in] at any fixed corner the cord wraps on the way, and bare-fiber slack coiled in the tray where the posts already hold its radius.
Through the wall without losing the rating
Plan one gland per incoming cable, each sealing on the cable jacket. The clean route in a sealed box is bulk cable through a small gland and fusion splicing in the tray: the hole stays small and the seal closes on a round jacket. To bring a fitted connector through instead, use a split or disconnectable gland sized for its boot — getting a connector through a cable gland without leaks covers that trade, and cord grip hole sizes by knockout gives the drill sizes. UL 50's Table 71-1A ties standard fitting threads to their hole diameters, which is what a cutout list is built from.
Match the gland rating to the box. An assembly carries the rating of its weakest part — NEMA's own enclosure FAQ makes that point for the whole box — so glands on a Type 4X enclosure carry a matching rating of their own with the seal compressed on the jacket. Our stainless junction boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.
Have the holes cut before the box ships. The cutout designer lays out the gland row and checks spacing on catalog and custom sizes alike, and the cutouts, glands and windows guide collects the dimensions. Factory-cut holes leave the gasket flange intact, which is most of what a sealed box is.
A 12-port LIU for four camera drops in one box
The case: an outdoor cabinet feeds four camera drops and wants spares. Inputs, each with its source:
- 4 fiber drops, each one duplex cable = 2 fibers — the design count; put your own here
- 4 spare ports, two spare duplex drops — a design choice
- Connector: SC, matching the plant's existing cords
- Incoming cable: 3.0 mm duplex jacket, the example cable in cable-makers' bend guides
- Mount: stainless junction box rated NEMA 4X / IP66 by the manufacturer, 35 mm rail inside
- Gland row 75 mm [3 in] below the LIU's cord exit — a layout choice you set on the drawing
The rule in words: ports needed = drops × 2 + spares; take the smallest housing that covers the total with your connector; then hold two clearances, 2 in [50 mm] above for the tray and the 20 × OD pulling radius on the way down to the gland.
The arithmetic:
- Ports in service: 4 drops × 2 fibers = 8
- With spares: 8 + 4 = 12 → the 12-port housing, which accepts SC
- Installed bend radius: 10 × OD = 30 mm [1.2 in]
- Dressing radius: 20 × OD = 60 mm [2.4 in]
- Run available: 75 mm − 60 mm = 15 mm of margin
Decision: order the 12-port SC LIU, a box whose panel takes the rail with 2 in [50 mm] above it, four glands sealing on the cord jacket, and one blanked spare hole. If your drawing gives the gland row less than that pulling radius of run, drop the LIU one rail position or move the row — the 20 × OD radius is the threshold. For the box itself, walk how to size an electrical enclosure once the rail load is known.
What to put on the order
| Item | What to specify |
|---|---|
| LIU | 6, 12 or 24 ports and the connector family |
| Termination | Fusion splice with pigtails, or direct termination |
| Enclosure | 304 stainless for dry indoor rooms, 316L for washdown and coastal air; type to suit the location |
| Cutouts | One gland hole per cable plus a blanked spare, the pulling radius or more below the rail line |
| Glands | Rating matched to the box, sealing range closing on the cord jacket |
| Rail space | 35 mm rail with 2 in [50 mm] clear above the housing |
Decide by case. One or two drops in a tight junction box: the 6-port. A machine panel or a camera ring with spares: the 12-port. A fiber-heavy panel with several incoming cables: the 24-port in SC or LC — or two 12-ports when the plant stays ST. Washdown or coast: 316L. Clean electrical room: 304. Every enclosure is made to order and delivered in 10 business days anywhere in the world, counted from your order; for custom cutouts, from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 10 × 8 × 6 in | 304 stainless | 10 x 8 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Which DIN rail patch panels take ST connectors?
The 6-port and the 12-port: both accept SC, ST and LC. Beyond those counts you are doubling up 12-port housings on the same rail. ST also has the widest coupling housing of the three, so allow a little extra front clearance before the door closes.
Can I leave spare fiber coiled in the splice tray?
Yes, the tray is built for it: it holds the fusion splices and a service loop. Coil jacketed cord at 10 × its outside diameter, 30 mm [1.2 in] for 3 mm cable, and bare fiber at 300 × the 125 µm cladding, about 38 mm [1.5 in]. Slack in the tray also buys a re-termination later without pulling new cable.
Can I pass a fitted LC connector through the gland instead of splicing?
Yes, with a split or disconnectable gland whose bore clears the connector boot; the seal still closes on the duplex cord's jacket. In a sealed box the tidier route stays bulk cable through a small gland and fusion splicing in the tray: smaller hole, round seal surface.
Does the LIU add heat to the enclosure?
No. A patch panel is passive glass and plastic and adds 0 W to the heat budget. The media converter or industrial switch beside it is the part that dissipates, so add the watts printed on its datasheet when you size cooling and count the LIU as zero.
Does a fiber gland change the enclosure's NEMA 4X rating?
Only if the gland is the weaker part. The assembly takes the rating of its lowest-rated component, so a Type 4X / IP66 box needs glands rated to match, sealed on the cable jacket. Our stainless enclosures are rated NEMA 4X / IP66 by the manufacturer and not UL listed; where a spec calls for a listed box, source one carrying a UL 50E listing.