Short answer: one RTU cabinet carries four power domains, not one voltage. The RTU logic rides the station battery — 125 V nominal, about 135 VDC at float — while 24 VDC wets the status and alarm inputs and 120/240 VAC arrives only as the service circuit for lights, receptacles and ancillaries. Analog channels see instrument-transformer secondaries, scaled back to primary values. Your three build decisions: give the RTU its own fused DC feed sized at the end-of-discharge current, split the voltage levels into separate wireways, and keep every survival load on the battery side of the cabinet.
Four domains in one cabinet
Before you order a terminal block or a fuse, decide which domain you are wiring. Installed RTUs run on anything from 24 VDC to 135 VDC; utility station batteries come in 24, 48, 125 and 250 V nominal systems, and 125 V is the nominal the switchgear standards recognize.
| Domain | Typical level | Source | What it feeds |
|---|---|---|---|
| RTU logic supply | 125 V nominal, ~135 VDC at float | Station battery and charger | CPU, comms cards, Ethernet switches |
| Status and alarm wetting | 24 VDC | Battery-derived or AC-derived supply | Digital input cards, auxiliary contacts |
| Service circuit | 120/240 VAC | Station service AC | Lights, receptacle, heater, test equipment |
| Analog inputs | CT and PT secondaries | Instrument transformers | Analog input card |
The AC main is the one to respect and the one to distrust: it powers the lower-voltage supplies and the cabinet accessories, and it dies with the station. Battery power is the RTU's survival power, and a cabinet that wires the logic to the AC side loses the whole reason the RTU exists.
Why the logic rides the battery
A total station outage is exactly when dispatch must still see the substation, so the RTU, its radio and its switches hang on the battery, not on station service AC. A 125 V nominal lead-acid string floats near 135 V at the RTU terminals in normal service — about 2.25 V per cell on 60 cells — climbs toward 140 V (2.33 V per cell) during equalize charge, and sags to about 105 V (1.75 V per cell) at end of discharge. Order a supply module whose stated input range covers that whole window; a module sold for a 125 VDC system can still reject the equalize voltage, so the datasheet range decides. Lithium-titanate strings built to replace 125 V VRLA banks stay inside 98-125 VDC, within the same window, and a station charger holds ripple under 100 mV RMS on a 130 V system.
Include the RTU in the battery duty-cycle calculation of IEEE 485: every continuous load runs for the whole autonomy period at end-of-discharge voltage. Feed it from the DC distribution panel through its own fuse or breaker, so a shorted comms card can never compromise protection or tripping circuits. Treat the DC system as floating: the battery stays insulated from earth, a ground-detection relay watches for the first accidental ground, and you keep every DC conductor insulated end to end. The cabinet itself still bonds to the equipment grounding conductor like any panel; the grounding and bonding guide covers that side of the box.
Size the DC feed at end of discharge
A constant-power supply draws its highest current at the lowest battery voltage, so float amps flatter you and end-of-discharge amps size the fuse. Worked example with assumed inputs — swap in your nameplate watts. Suppose the RTU draws 60 W, the radio 40 W and the Ethernet switch 20 W: 120 W of continuous load. At the 135 V float voltage the current is 120 / 135 = 0.89 A. At the 105 V end-of-discharge voltage it is 120 / 105 = 1.14 A, about 29 percent higher. Treat it as a continuous load and apply the 125 percent continuous-load factor the NEC uses for overcurrent sizing: 1.14 × 1.25 = 1.43 A, so a 2 A DC-rated fuse covers the group with margin. At under 2 A the conductor ampacity never binds, so choose the wire for solid terminations and low voltage drop. Fuse each device off a small DC distribution block if you want one fault to take out one device rather than the group.
The wetting circuit for statuses and alarms
Digital input cards are usually wetted at 24 V even where the logic runs on battery voltage: low-voltage contacts erode less, commodity relays fit, and dense terminal blocks get easier clearances. Match the card to the loop before you order it, because a card specified for 125 VDC inputs never crosses its ON threshold with a 24 V loop, and the point reads dead forever.
Where the wetting supply comes from is the decision that matters most. Derive it from the AC service circuit and every point on that card goes dark during an AC outage while the RTU stays alive — your telemetry freezes at the worst possible moment. Feed the points that must survive from a battery-derived converter, and leave convenience points on the AC-derived supply only when you accept that trade.
Inside the cabinet, give the wetting-voltage field wiring its own duct and its own terminal-block section, apart from the battery-voltage control wiring, and label both levels at every terminal. Mixed-voltage strips are the most common source of card damage at commissioning. The panel cable segregation article sets the duct habits, and the mixed-voltage troubleshooting article covers working such a panel safely. Confirm each card's common arrangement before you land the first field wire — many cards share one common per group of 8 or 16 points, sinking or sourcing.
The AC service circuit is ancillaries only
The AC main powers the DC supplies, the light, the receptacle, any heater and your test equipment. It is the circuit you switch off to work in the box, so give it its own disconnect and label it as the service circuit — the battery-fed DC stays live with it off. Keep the AC wiring in its own duct from its own entries, and land the neutral on an isolated neutral terminal with the grounds on the ground bus, because NEC 250.6 aims to keep neutral current off metal parts. The network switch cabinet article walks the disconnect and door rules for this same kind of AC feed.
Analog inputs: scale to primary values
Where copper still carries the measurements, CT and PT secondaries land on an analog input card, and the point scaling must multiply them back to primary values so dispatch reads line amps and bus volts: primary = secondary × ratio. A 1200:5 CT gives 1200 / 5 = 240, so 5 A of secondary displays as 1200 A. A 14400:120 PT gives 14400 / 120 = 120, so 120 V of secondary displays as 14,400 V. Read the ratio from the nameplate or the substation one-line rather than an old drawing, and confirm whether the card takes the secondary directly or needs an interposing transducer, since direct-input current channels carry a defined continuous and short-time rating. One safety rule owns this section: short the CT test block before you pull any wire from the card, because an open CT secondary develops a hazardous voltage.
The newer architecture removes that copper entirely. Relays, meters and regulator controls report over Ethernet or serial links with DNP3 or Modbus, the scaling moves into each device's settings, and the RTU becomes a protocol concentrator. Your cabinet then trades insulated analog terminations for shielded network cabling — the shielded ethernet grounding article covers bonding it — but the power plan stays the same: switches and radios still ride the battery.
What to specify
For an outdoor yard the box is a stainless cabinet rated NEMA 4X / IP66 by the manufacturer; not UL listed — the NEMA 4X enclosure category covers what that rating means — with a mounting plate zoned by voltage domain, following the backplate and DIN rail layout guide for rail and duct spacing. Put these on the order or in the wiring standard:
- A DC distribution block with a fused feed for the RTU group, sized at the end-of-discharge current as the worked example shows.
- Three wireway runs and three terminal sections — battery-voltage DC, wetting DC, 120/240 VAC — labeled at every terminal.
- A ground-detection point for the floating DC system, with the cabinet bonded to the equipment grounding conductor.
- A service-circuit disconnect, labeled, plus a receptacle for test gear.
- The heat check: converter losses and radio transmit draw warm a sealed box, and the enclosure sizing guide walks the load math.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can an RTU run from 24 VDC instead of the 125 V station battery?
Yes. A 24 VDC RTU in a 125 V station gets a DC/DC converter, and its loss counts in the battery duty: a 120 W load through a 90 percent efficient converter draws 133 W, which is 1.27 A at the 105 V end-of-discharge voltage. Feed it from the battery side rather than the AC service circuit whenever the points on it must survive an outage.
How long must the station battery carry the RTU load?
For the whole autonomy period, because the RTU, its radio and the Ethernet switches are continuous loads. Remote sites commonly plan 4 to 8 hours; 120 W carried for 8 hours is 960 Wh before converter losses. Momentary loads such as breaker close coils go into the same duty-cycle calculation separately: they size the string's short-time capability, not its ampere-hour capacity.
Does the cabinet's equipment ground conflict with the floating DC system?
No, they are separate systems. Bond the enclosure, door and mounting plate to the equipment grounding conductor the way every panel does. Keep the DC positive and negative insulated from that bond: a single accidental ground then only alarms the ground-detection relay, and the second ground is the one you hunt down before it finds a trip coil.
How do I prove the analog scaling before energizing?
Inject known secondary values at two points and read the display in primary units. On a 1200:5 ratio, 1.25 A injected should display 300 A, and 5 A should display 1200 A. Repeat the two-point check after any card swap or firmware change, not only at commissioning.
Does the AC service circuit need its own disconnect?
Yes, and label it so nobody expects the RTU to die with it. NEC 240.24(A) keeps the center of the handle grip, in its highest position, no more than 2.0 m (6 ft 7 in) above the floor or working platform. Open it for cabinet work and the RTU, radio and switches keep running from the battery; only the light, the receptacle and any AC-derived 24 V go dark.





