Buy the cable for its 120 ohm characteristic impedance and its pair construction, not for a twists-per-metre figure. The RS-485 specification recommends, but does not dictate, 120 ohms, and industrial cable for this service is sheathed twisted pair of 22 to 24 AWG. Put both signal conductors in the same twisted pair, run the network as a daisy chain, and terminate only the two physical bus ends with 120 ohm resistors. Keep the pair at least 8 in [200 mm] from drive output cables. That set of decisions, checked against the cable datasheet, is what makes a two-wire bus run for years. A twist count is not on the list.
What the cable datasheet must say
The RS-485 standard defines the electrical interface, so the cable you feed it needs four numbers and one construction fact. Read them off the datasheet before you order, and compare each against the connected equipment's instructions.
| Datasheet item | What to look for | Why it matters |
|---|---|---|
| Pair construction | Both signal conductors in one twisted pair | Keeps the loop small and the interference balanced, so the differential receiver can reject it |
| Characteristic impedance | 120 ohms nominal for RS-485 service | Matches the termination resistors and controls reflections |
| Conductor size | 22-24 AWG typical for industrial runs | Sets DC resistance, and with it the resistive drop over long runs |
| Conductor resistance | Stated in ohms per km for one conductor | Loop resistance is twice this for the two-conductor circuit |
| Capacitance | Low conductor-to-conductor capacitance | Loads the drivers and rounds the signal edges on long runs |
Check the shield and jacket against the environment, not the datasheet's marketing line. A washdown or outdoor run wants a jacket that survives the site. The stainless junction boxes for the splices should carry the rating the site needs, and the outdoor enclosure guide explains which type suits which weather. Where the bus passes through a wall or into a box, the entry hardware matters as much as the cable. The cutouts and glands guide covers gland selection per entry.
Why twist count is not the number
Twisting does two jobs: it makes both conductors see external interference nearly equally, and it shrinks the loop area that couples magnetic fields into the circuit. The RS-485 receiver responds to the voltage difference between the conductors. Interference that arrives balanced is rejected; interference that lands on one conductor more than the other is not. Twist geometry supports both jobs, but no published RS-485 requirement sets a minimum twists-per-metre value. Two cables with very different twist pitches can both hold 120 ohms well.
What actually moves reliability, in order: pair integrity, impedance match, termination, topology, routing distance from power circuits, and the shield and reference scheme. If someone hands you a cable and quotes only its twist rate, ask for the impedance and resistance figures instead. A shield cannot rescue the wiring error of taking one conductor from each of two different pairs. Check that the same physical pair reaches every device before you blame the cable.
Installing the run: the steps that decide it
-
Trace the path before you cut cable. Walk the route from the master port through every junction and drop to the last device. Record where each junction box sits and what enters it.
-
Select the cable from its datasheet. Confirm one twisted pair for the signals and the nominal impedance the datasheet states. Check a conductor size that suits the run length, and a loop resistance your run length can afford; the worked example below shows the arithmetic.
-
Daisy-chain the drops. Wire device to device in a line, with the two end devices at the physical ends of the bus. A star layout sends reflections from every leg. Stubs longer than roughly 1 m [3 ft] at ordinary baud rates start to behave as transmission lines of their own, so keep each drop as short as the panel layout allows.
-
Terminate only the two ends. Fit one resistor equal to the cable impedance, 120 ohms for standard cable, across the pair at each physical end. Remove or switch off any termination built into intermediate devices. Two end resistors, no more.
-
Route for separation. Keep the pair 8 in [200 mm] or more from drive output cables and other switched power. Where a crossing is unavoidable, cross at right angles. If a long run must share a tray with power circuits, the VFD output cable article explains why those leads radiate and what shielding buys you.
-
Bond the shield per the instructions. Read the connected equipment's shield and signal-reference terminals, and treat them as two different jobs. The shield controls coupling. A separate reference conductor, where the equipment calls for one, keeps every transceiver's common-mode voltage inside its limits. The shield and signal-common article works through the both-ends case and when it drives shield current.
-
Test end to end. Check continuity and polarity of each conductor from master to last device against the terminal diagrams. Letter labels alone are unreliable between makers. Then put the bus on line and confirm every device answers.
For the junction points, use a stainless junction box sized for the splices and terminals. Land the shield on its own terminal rather than twisting and taping it. The RS-485 junction enclosure article covers selection for signal wiring in detail.
Sizing a 300 m run
Inputs. Run length 300 m, taken from the site route. Conductor resistance about 84 ohms per km for 24 AWG copper, from the standard copper conductor resistance tables. Cable characteristic impedance 120 ohms nominal, from the cable datasheet. Baud rate 9,600, the setting the devices use.
The rule in words. The differential signal travels out on one conductor and back on the other. The resistive drop it sees is the loop resistance: twice the single-conductor resistance, times the length.
The arithmetic. 84 ohms/km per conductor doubled gives 168 ohms/km of loop resistance. Over 0.3 km: 168 ohms/km x 0.3 km = 50.4 ohms of loop resistance.
The result and the decision. At 9,600 baud, a twisted pair with the specified impedance and a 50 ohm loop resistance over 300 m sits comfortably inside the commonly cited limit of about 1,200 m [4,000 ft] for low-baud RS-485. The standard industrial cable is the right order. If the run tripled to about 1 km, the loop resistance would reach 168 ohms and the drop would start to squeeze the drive margin. At that length step up to 22 AWG, whose per-conductor resistance of about 54 ohms/km halves the loop figure. That gives about 32 ohms over the same 300 m, and about 108 ohms over 1 km. Copper resistance also rises about 0.39 percent per kelvin, so a hot roof run loses a little more margin than a basement one. On these numbers the shift is small.
Checks when the bus is on line
- Every device answers at the configured baud rate with no retries logged at the master.
- Termination measures 60 ohms from A to B with the bus powered down: the two end resistors in parallel, and the reading confirms exactly two terminations.
- No conductor of the pair is broken, swapped or taken from two different pairs, proven by the end-to-end continuity check.
- Shield lands on its designated terminal at the points the equipment instructions name, and no shield section is interrupted or taped over.
- The pair keeps its 8 in [200 mm] separation from drive output cables for the whole route.
If the network still drops characters after these pass, the most likely cause is a device with built-in termination left enabled somewhere mid-bus. Switch it off and keep the two end resistors as the only ones. If drops persist, the RS-485 surge protection article covers the port side.
What to put on the order
Order cable marketed for RS-485 or industrial fieldbus service, specified as one twisted pair at the nominal impedance its datasheet states. Size the conductors for runs up to a few hundred metres, and add a shield and a jacket rated for the environment it crosses. Add two termination resistors per bus, one for each physical end, shield terminal blocks for each junction box, and the glands each entry needs. Our stainless wall-mount and HMI enclosures are custom-cut to your entry layout and delivered in 10 business days; the custom enclosure page shows the material and cutout options. For the communication side of the panel, the twisted pair inside a metal enclosure article explains when the box itself helps and when it cannot. If two bonded cabinets sit at different earth potentials, the RS-485 isolation article says when a node needs isolation. And once the cable is in, keep the pair's geometry intact to the terminals: the bus that survives is the one wired as one pair, one line, two resistors.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 6 × 6 × 4 in | 304 stainless | 6 x 6 x 4 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How many twists per metre does RS-485 cable need?
No twist count appears in the RS-485 electrical standard, and the number that decides reliability is the cable's characteristic impedance and balanced pair construction, both printed on the datasheet. Buy cable marketed for RS-485 or industrial fieldbus service; its twist pitch is already set by the maker to hold the impedance. A twist count alone, without the impedance and capacitance figures, tells you nothing about how the bus will behave.
Can I use 100 ohm termination resistors on a 120 ohm RS-485 bus?
Match the resistor to the cable, not to a habit: the RS-485 specification recommends a characteristic impedance of 120 ohms, so terminate a 120 ohm cable with two 120 ohm resistors, one at each physical end. A 100 ohm resistor on a 120 ohm line loads the bus harder than the reflection it suppresses, and two 100 ohm resistors draw about 20 percent more bias current than two 120 ohm resistors at the same voltage. If a cable datasheet states 100 ohms nominal, use 100 ohm resistors with that cable.
How far can an RS-485 bus run on twisted pair?
The commonly cited figure is about 1,200 m [4,000 ft] at low baud rates such as 9,600 baud with 24 AWG twisted pair, and the practical limit is the cable's DC loop resistance and capacitance, not its twist pitch. For a 300 m run of 24 AWG, the copper loop resistance is about 50 ohms, which leaves most of the drive margin intact. Cut the figure roughly in half for higher baud rates in the hundreds of kilobits, and read the transceiver manufacturer's rate-versus-length guidance for the exact curve.
Do I ground the RS-485 shield at both ends or one end?
Grounding both ends controls high-frequency interference best, but it drives shield current when the bonded cabinets sit at different earth potentials, so follow the connected equipment's instructions and the site bonding design. Inside our stainless junction and panel enclosures, rated NEMA 4X / IP66 by the manufacturer; not UL listed, land the shield on a dedicated shield terminal bonded to the backplate, and run a separate signal-reference conductor where the devices require one. A shield is interference control, never a signal return.