Short answer: the drive is big enough for three 3 kW motors, but 90 m of summed motor cable on an unfiltered output is what stops it. Keep the total motor cable at or below the limit in the drive's own table (about 50 m screened and unfiltered on a typical 400 V drive, 100 m or more with a dv/dt filter), bond every cable screen 360 degrees to the drive's gland plate, and fit an overload at each motor. Work through the checks below before you blame the drive.
Why does one drive trip or reset when three motors start?
The symptom that points at the cable, not the drive, is a fault with no overcurrent or overvoltage code: the operator panel blanks, the drive reboots, and nothing on the trip log explains it. That is common-mode noise from the motor cables upsetting the drive's control and serial wiring, not a protection trip. Each IGBT edge charges the capacitance of every metre of motor cable to ground; that charging current returns through the drive and radiates into anything nearby, including the panel's own analog and communication wiring.
Three motors multiply the effect because their cable capacitances add in parallel. The same edge that charges 30 m of cable for one motor charges 90 m for three, so the leakage current is roughly three times higher at the same switching frequency. The drive size was never the problem.
How long can the total motor cable be?
Add the three run lengths together and compare the sum with the drive manual's cable table for your switching frequency and filter option. The number is a drive-specific limit, not a physics constant: a 400 V drive with a low dv/dt output stage might allow more, an older fast-edge drive less. Two anchors are worth knowing. A project rule applied on many installations is no output filter under 50 ft [15 m] of run, with reactors on the longer ones. Manufacturers' long-cable tables exist because shielded cable has higher line-to-ground capacitance than the same wires in conduit, which raises the charging current the drive must absorb.
Worked example, with assumptions you should replace with your own drive's table:
| Item | Value | Note |
|---|---|---|
| Motors | 3 x 3 kW, 400 V, 4-pole | about 6 A rated current each |
| Total motor current | 18 A | 3 x 6 A, summed |
| Drive rating | 11 kW, about 25 A output at 400 V | read the nameplate |
| Thermal use | 18 A / 25 A = 72% | fine at steady state |
| Cable runs | 25 m + 30 m + 35 m | screens bonded both ends |
| Total cable | 90 m | over a typical 50 m unfiltered screened limit |
So the sizing passes and the cable fails. The fix is a dv/dt filter or sine filter at the drive output, sized for the summed cable length and the full 18 A, not for one motor.
Lowering the drive's switching frequency (the PWM frequency setting, usually a single parameter in the drive's commissioning menu) helps as a second lever: dropping from 4 kHz to 2-3 kHz cuts the leakage current roughly in proportion, at the cost of a little more motor noise. Never exceed the drive's derating table for the cable length you end up with.
Does every motor cable need a screen, and where does it land?
Yes: screened (shielded) VFD cable on every run, screen bonded at both ends. At the drive end the screen lands on the bare metal of the enclosure, not on a terminal. This is 360-degree bonding: the screen passes through an EMC gland or under EMC saddle clamps so its whole circumference touches the gland plate over a length of millimetres. IEC 61800-3's EMC installation guidance calls this 360-degree termination, and it is the difference between a screen and a length of decoration.
Our stainless enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and they come with a removable mounting panel, so specify a bare stainless gland plate as the screen landing: one plate, all three motor cables, each screen under its own clamp. Where the cables land and how far apart the glands sit is covered in the guide to cutouts, cable glands and HMI windows, and in the article on cable gland spacing on an enclosure wall. If the plate thickness leaves the gland threads short, use the fix in the article on a cable gland adapter for a thin enclosure plate. A qualified clamp bond, not a foil twisted under a screw, is what carries the leakage current back to the drive; the page on cable foil grounding and qualified gland bonds goes into that bond in detail. Keep the screens continuous through any motor disconnect as well, as described in the article on keeping the VFD cable shield continuous at a motor disconnect, and finish the entry bonding as shown in the article on shielded VFD motor cable grounding at the enclosure entry.
A pigtail, a screen gathered into one wire and landed on a ground terminal, has about 1 microhenry of inductance per metre at PWM frequencies, which blocks exactly the current the screen exists to carry. Replace every pigtail with a clamp.
Can one drive protect three motors?
Only one way: give each motor its own overload. The drive's internal thermal model sees a single output current, and three motors on one chain never share load equally, so the drive cannot know that motor C is at 120% while A and B are fine. Fit a thermal overload relay or a PTC/PT100 trip in each motor terminal box, set to that motor's 6 A rated current, wired to drop the drive's run command.
Shared drives also require mechanically coupled motors: one chain, one shaft, one speed. Independently started motors each need their own drive or their own contactor-and-overload starter off a fixed supply, because a VFD output must never be switched while a motor is on it. If you are considering sharing or switching outputs, read the article on switching one VFD output between two machines safely first.
Why did the analog setpoint wander?
A 0-10 V setpoint that wanders about 0.5 V at the drive while the PLC output is steady is a wiring reference problem, and it is solved at the terminals. Drive analog inputs of this class are differential: the signal lands on the + and - input pair, and a factory link between the - input and the 0 V reference exists only for a potentiometer or other floating source. When the source is a PLC output that already references its own 0 V, remove that link, because leaving it ties the two 0 V systems together through the link and any ground potential difference between the cabinets becomes setpoint error. With the link out, the differential pair rejects the common-mode noise that long cable runs and PWM leakage put on the ground reference. Keep the analog and communication wiring at least 200 mm [8 in] from the motor cables inside the enclosure, in their own duct run.
What fixes this in order, and what do you order?
Work in this sequence, and verify absence of voltage on the drive input and output terminals before opening the cabinet:
- Measure the three cable runs and add them; compare the sum with the drive manual's table at your switching frequency.
- Bond every motor screen 360 degrees at the drive gland plate and at each motor terminal box; remove all pigtails.
- If the sum exceeds the unfiltered limit, fit a dv/dt filter or sine filter rated for the total current and cable length.
- Fit an overload in each motor terminal box at its rated current.
- Check the analog input wiring: differential pair to the PLC, no 0 V link.
- Lower the PWM frequency one step and retest; confirm the drive stays within its derating.
On the order: one enclosure with a gland plate sized for three screened cables plus the filter, EMC clamps to match each cable's outside diameter, and a small stainless terminal box at each motor for its overload. A 304 box handles routine washdown; for brine or chlorine sanitizers step up to 316L wall-mount enclosures. Custom sizes and cutouts, built and delivered in 10 business days, come through custom stainless enclosures; the smaller wall-mount sizes used as junction and pull boxes are in stainless steel junction boxes, and the washdown selection is in washdown enclosures. Before you close the door, run the VFD enclosure wiring checklist: stop, bond, filter, then measure the leakage and setpoint stability again under load.
If a motor still runs hot after all this, the mismatch is mechanical, not electrical: a chain that loads one motor harder than the rest. Individual overloads will find it before the windings do.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How many motors can one VFD drive?
As many as the drive's output current covers: size the drive on the sum of the motor rated currents plus about 10-20% margin. Three 3 kW motors at 400 V draw about 18 A together, so an 11 kW drive rated near 25 A carries them at about 72% of its output. Only motors on one mechanically coupled shaft or chain may share a drive, because a drive protects one speed.
What is the maximum motor cable length with multiple motors?
Add every run together and compare the sum with the drive manual's table for your switching frequency and filter. A common unfiltered limit on a 400 V drive is about 50 m of screened cable; with a dv/dt filter or sine filter the same drive typically allows 100 m or more. At 90 m total, plan on an output filter.
Can the VFD's motor thermal model protect all three motors?
No. The drive models one motor current, and three separately loaded motors never share current equally. Fit a thermal overload relay or a PTC/PT100 trip in each motor terminal box, sized to that motor's rated current of about 6 A, so each winding trips on its own load.
Does a pigtail screen bond really lose that much?
Yes. A screen brought to a single wire and landed on a terminal presents an inductance of roughly 1 uH per metre of pigtail at PWM frequencies, which is exactly the band where the leakage current lives, so the screen stops working as a screen. A 360-degree EMC clamp on the gland plate turns the shield into a low-inductance path of milliohms.