Short answer: close the cabinet up before the truck comes. Cap every cutout with a plug or bolted blank, refit the door so the gasket compresses, and hang 50-100 g of silica gel per 50 L of air volume. Moving a machine control cabinet goes wrong the same way every time. A stripped cabinet with the door off and the exchanger in a crate collects snow, dust and meltwater. The water ruins drives and terminals long before the sheet metal complains. Work this list the evening before loading, again at the truck, and once more the morning you power up.
The night before: strip in the order you can undo
The damage rarely starts on the road. It starts the evening someone pulls the door, the exchanger and the glands off and leaves six holes open to the weather. Strip with the reassembly in mind:
- Lock off the supply and verify absence of voltage before the first cover comes off.
- Photograph the interior: terminal positions, which cable entered which hole, which plug sat where. The photos are your reassembly drawing.
- Bag the fasteners with the part they hold and label the bag with its hole.
- Leave the transformer and the big drives bolted to the mounting plate; they ride safer inside a closed box than loose in a crate.
- Pull the door only when a doorway forces it. A door off for a week lets the gasket take a set that latch pressure never recovers.
- List every opening you create and write it on the cabinet in marker. On a machine cabinet with two power glands, two signal glands, a console entry and an exchanger cutout, that is six holes to cap.
Recheck the list against the photographs before loading: every hole on it carries a cap or a blank.
Cap every cutout
One open 25 mm hole passes meltwater faster than a worn door gasket ever will, and the lowest opening sets what the whole box survives. Cap everything, and cap it to last:
- Gland holes: screw in the blanking plug made for the hole diameter you cut, washer against the panel. Match the plug to the hole, not to the thread name on the old gland.
- Conduit and armoured-cable hubs: fit the screw-in cap for that hub size.
- The exchanger or filter-fan cutout: a bolted sheet blank over a gasket strip, at least one fastener per corner. Mastic alone pumps loose at highway vibration.
- Unused knockouts: the spring-steel knockout plug, seated flush.
Tape is for labels. Rubber-adhesive tapes lose their grip near 0 C [32 F], so a hole taped shut in a warm workshop opens itself on a freezing flatbed. A capped box also keeps the rating on its label. Ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed. Any such rating assumes the door is on and every hole is filled. The cutouts, glands and windows guide covers hole sizing, and blanking a large cutout with a plate and gland shows the bolted-blank method on a rectangular opening.
Refit the door and give the gasket a cold check
The door goes back on with its full gasket:
- If the gasket came away with the door, glue it to the door leaf, not the frame, exactly where it sat.
- Close every latch so the gasket compresses evenly; an unlatched door flaps and pumps dust past the seal.
- After the ride, press the gasket hard with a thumb. A live seal springs back; one that stays dented has taken a set and gets replaced.
Cold hurts a gasket less than storage does:
| Rubber | Typical low limit | Ride at -10 C [14 F] |
|---|---|---|
| Silicone | -60 C [-76 F] | flexible |
| EPDM | -50 C [-58 F] | flexible |
| Neoprene | -40 C [-40 F] | flexible |
| Nitrile | -30 C [-22 F] | flexible |
These are typical O-ring-handbook values; your gasket's datasheet wins where it differs. A night at -10 C sits inside all four ranges, so the ride leaves the seal fine. A door stored flat under crates does the real damage, so lay it gasket-up where nothing rests on the seal. The foam or rubber door gasket comparison picks the compound for a seal that also has to live outdoors afterwards.
Desiccant and wrap for the ride
A -10 C yard and a 20 C cab are 30 K apart, and every swing pushes air in and out of a sealed box through the gasket. The desiccant rule is 50-100 g of silica gel per 50 L of air volume, 1-2 g per litre. The low end matches the packaging rule of one 28 g desiccant unit per cubic foot (28 L). That MIL-D-3464 unit is sized to hold at least 3 g of water at 20% RH. Take the top of the range for an open or below-freezing ride, or if the box sits more than a few days.
Worked example, a stripped machine cabinet of 600 × 800 × 400 mm (about 24 × 32 × 16 in) outside:
- Volume: 0.6 × 0.8 × 0.4 m = 0.192 m³, so 192 L.
- The mounting plate, rails, transformer and drives displace roughly a fifth, leaving about 150 L of air.
- Freezing ride at the top of the range: 150 L × 2 g/L = 300 g, six 50 g sachets.
- Tape the sachets spread across the mounting plate; spread gel adsorbs hours faster than one lump.
| Box air volume | Dry indoor move, 1 g/L | Freezing or open ride, 2 g/L |
|---|---|---|
| 50 L | 50 g | 100 g |
| 100 L | 100 g | 200 g |
| 150 L | 150 g | 300 g |
| 200 L | 200 g | 400 g |
Tape a humidity indicator card beside the door; pink spots on arrival mean the gel spent itself and the box took water. Stretch film over the closed cabinet works as the dust and rain cover. Film holds condensation against cold steel, so film the machine, add the desiccant, and unwrap the same hour you arrive. Strap to the frame, not through the door, and keep the box upright.
On arrival: dry, test, then power
A cabinet that rode at -10 C [14 F] and lands in a 20 C [68 F] shop at 50% RH faces a dew point near 9 C [48 F]. Every surface below 9 C sweats; anything still below 0 C frosts first and melts after. Then:
- Unwrap, open the door, pull the sachets, and wipe any meltwater off the roof and the drive fins.
- Wait about 3 hours before the first power-up. The arithmetic: 150 kg of cabinet steel at 0.46 kJ/kg·K holds 69 kJ per kelvin; about 2 m² of surface in still air sheds 24 W per kelvin (12 W/m²K); 69,000 ÷ 24 = 2,875 s, a 48-minute time constant. Three hours is nearly four time constants, leaving the steel within 1 K of the room.
- Insulation-test every outgoing circuit at 500 V DC before the first energization; IEC 60364-6 sets the pass mark at 1 MΩ for circuits up to and including 500 V.
- Anything meltwater soaked — drives, breakers, fuses, electronics — is replaced, not dried and re-energized. That is NEMA's water-damage guidance, and an insulation reading does not bring a soaked part back.
- Vacuum the dust the loading shook loose before you re-energize; cleaning a cabinet without damage covers the method.
Refit the exchanger or air conditioner with its own gasket; the box rating rides on that fit. The heat-exchanger requirements for drive enclosures spell out what the opening has to keep. The condensation checks before repairing a cabinet air conditioner matter the first week it runs again. If the machine now sits between jobs, the anti-condensation heater sizing and setup guide keeps the interior above the dew point for good.
What to send if the move found damage
Moves find bent doors, gouged gasket faces, a 40 mm hole where a console cable used to enter. Replace a damaged face rather than fight it:
- Measure outside: width × height × depth, plus the mounting-plate size.
- Pick the grade: 304 stainless for most plants, 316L where salt, brine or chemicals touch the box.
- Draw the cutouts from your arrival photos in the cutout designer and export the layout with the quote request.
- Photograph the damage and the old gland positions; they settle hole questions before cutting starts.
We build that face from one piece and deliver it in 10 business days from your approval of the drawing. Start at the custom enclosures page, or check the nearest stock size in the stainless size finder. If this move is really a relocation, with the cabinet living outside the machine from now on, spec it as that job. The outdoor relocation checklist covers what changes.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much desiccant goes in a control cabinet for a move?
Use 50-100 g of silica gel per 50 L of air volume, which is 1-2 g per litre. The packaging basis is one 28 g MIL-D-3464 desiccant unit per cubic foot (28 L), sized to hold at least 3 g of water at 20% RH. A stripped 600 x 800 x 400 mm cabinet with 150 L of air takes 300 g on a freezing ride: six 50 g sachets spread over the mounting plate. Spent gel recharges in an oven at about 120 C for two hours.
Can the cabinet ride with the door off, wrapped in film?
Wrap film over a closed, latched door only. Rubber-adhesive tape loses its grip near 0 C, so a taped-over hole opens itself on a freezing truck; plugs and bolted blanks hold at any temperature. If you film the whole machine, double the desiccant to 2 g per litre and unwrap the same hour you arrive, because film holds the day's condensation against cold steel.
The cabinet sat out in snow overnight — what do I test before power-up?
Let the steel reach room temperature first, 3 hours or more for a cabinet that rode at -10 C, then test each circuit at 500 V DC against the IEC 60364-6 mark of 1 MΩ for circuits up to and including 500 V. Meltwater that actually soaked a drive, breaker or fuse ends that part: NEMA's water-damage guidance says replace it, because an insulation reading does not bring a soaked part back.
How long before a cold-soaked cabinet is safe to energize?
The walls track the room within about 3 hours. A 150 kg cabinet holds 69 kJ per kelvin and sheds about 24 W per kelvin in still air, a 48-minute time constant, so 3 hours leaves the steel within 1 K of the room. A drive heatsink bolted inside can lag another hour; feel it with the back of a hand before you close the last cover.