The internal fan of a drive follows the Run command alone, and no setting keeps it spinning while the drive sits stopped. That matters less than it seems, because that fan was never cooling your enclosure: it pushes air across the heat sink and drops the heat straight into the panel air. Standby still burns watts. External control power keeps the control unit and its supply alive, and the working estimating rule puts drive heat near 3% of the rating, so a 5.5 kW unit pours about 165 W into a sealed box all shift. Give that heat its own exit: a filtered intake fan low in the box, an exhaust filter high on the far side, powered independently of the drive. At a 30 °C site holding the interior to 40 °C, the arithmetic asks for about 51 m³/h of airflow.
What the symptoms point to
Standby heat leaves a pattern, and each sign points at a different part of the heat path:
- Control unit and upper housing warm, internal fan still, Run command off. The electronics are doing what powered electronics do; what is missing is enclosure airflow, not a drive repair.
- Box hottest at the top, cooler near the bottom wall. Air is stratifying in a sealed box, and nothing is exchanging it with the room.
- Overtemperature warning at midday, quiet in the morning. Sun on the box or dryer discharge is lifting the intake air as the site heats up.
- Enclosure fan running but the interior stays hot. Look past the fan: loaded filters, an intake placed in hot air, or a stream that loops without crossing the drive.
- The trouble appeared when a new HMI or PLC went in. Always-on watts grew past what the walls can shed.
Causes in order of likelihood
- No enclosure ventilation at all. The internal fan moves air across the heat sink and discharges it into the panel air; it exchanges nothing with the room. With the control unit powered externally, watts flow into a sealed box all shift, and the top of the box is where you feel it first.
- Ventilation that stops when the drive stops. A panel fan wired through a run-feedback contact, or sized from running losses, quits exactly when the standby heat is left on its own.
- Intake air hotter than the 30 °C you planned around. Sun on the box face or a grille facing the dryers' discharge does this. At 35 °C intake against a 40 °C limit, the usable rise halves to 5 K and the airflow need doubles to about 102 m³/h.
- Air that short-circuits. Intake and exhaust filters mounted close together let the air loop between them without sweeping the drive.
- A box too small for its always-on watts. A sealed 600 × 400 × 200 mm stainless wall sheds about 33 W at a 10 K rise; 165 W of standby heat is five times that. The worked example below runs the sum.
How to check each one
Measure first, then follow the air:
- Temperatures with the Run command off. Read the shaded air at the planned intake and the air at the drive inlet, 30 minutes after the box settles. About 40 °C inside against 30 °C outside confirms causes 1 or 2.
- The fan transition. Watch the internal fan across a stop-to-run transition: it starting with the Run command is design behavior, not a fault.
- What switches the enclosure fan. A continuous supply, a thermostat and its setpoint, or a drive contact. A fan that quits at standby is cause 2.
- The filters. Hold each mat to the light; loaded media strangles flow. Clean or replace, then measure again.
- The stream. A paper strip should pull inward at the intake and push outward at the exhaust. For a number instead of a paper strip, measure air speed at the grilles and compare it with the guidance on troubleshooting airflow velocity inside enclosures.
- The sun. An IR thermometer on the sunlit face and the shaded face tells the truth: a 10 to 15 K spread between faces means the intake air is warmer than the site ambient you wrote down, cause 3.
The fix: ventilation that ignores the drive
Fit airflow that runs on its own schedule:
- Filtered intake low, exhaust filter high, opposite faces or corners. Set the stream to sweep past the drive before it leaves; the placement rules are in the enclosure fan placement article for hot components.
- Positive pressure. Push filtered air in and let it escape through the outlet media, so dusty shop air can only enter through a filter; the approach is worked through in the positive-pressure and filtered-fan article for dusty enclosures.
- Power independent of the drive. Run the fan continuously, or set a thermostat about 5 K below the drive's permitted ambient: 35 °C switching for a 40 °C limit.
- Shade an outdoor box, and keep the intake grille out of the dryers' discharge path.
The one move to skip is starting the drive to spin its fan: it changes machine state, energizes the power stage, and adds heat while removing none from the box. When the choice between a plain fan, a filter fan and sealed cooling is not obvious, the hot-shop decision between fan, filter fan and cooling unit sorts them by ambient and dirt load.
Wherever the box is hosed down, a filter fan is off the table: an open fan-filter opening drops the assembled enclosure below its NEMA 4X / IP66 rating. Washed-down boxes keep the seal and take sealed cooling instead, an air-to-air heat exchanger or an enclosure air conditioner. Our 304 and 316L washdown boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed.
Sizing the fan for a 5.5 kW drive standing by at 30 °C
The case: a 5.5 kW drive powered for control but not running, in a 600 × 400 × 200 mm stainless wall-mount box, 30 °C shade air at the intake, interior held at or below 40 °C.
| Input | Value | Basis |
|---|---|---|
| Drive rating | 5.5 kW | the drive's rating plate |
| Standby heat | 165 W | the 3% estimating rule: 5.5 kW × 0.03; a documented loss figure replaces it |
| Permitted internal air | 40 °C | the ambient most drive datasheets permit |
| Intake air | 30 °C | measured shade ambient at the grille |
| Allowed rise | 10 K | 40 °C − 30 °C |
| Stainless wall conductance | 3.7 W/m²K | the reference value this site's guides use |
Two rules carry the sum. A stainless wall sheds about 3.7 W from every square metre for each kelvin of rise. And at sea level each cubic metre per hour of moving air carries about 0.32 W per kelvin, so airflow in m³/h is 3.1 × watts ÷ rise. Panel-building rules of thumb compress this same physics into factors like 5.5 and 0.053; the article on where the cubicle heat-rise factors come from unpacks that pair.
Walls first. Surface area of the box: 2 × (0.6 × 0.4) + 2 × (0.6 × 0.2) + 2 × (0.4 × 0.2) = 0.48 + 0.24 + 0.16 = 0.88 m². At a 10 K rise the walls carry 0.88 × 3.7 × 10 = 32.6 W, call it 33 W. Left sealed, the drive's 165 W would drive a rise of 165 ÷ (0.88 × 3.7) = 51 K and park the interior near 81 °C.
Airflow next: 3.1 × 165 ÷ 10 = 51.15, so about 51 m³/h has to move through the box.
Decision: above about 33 W of always-on heat, this box cannot hold a 10 K rise on its walls alone, and every watt from there up is sized at 3.1 × W ÷ K. Standby alone is five times the threshold, so the fan is not optional: 51 m³/h of delivered flow. Free-air ratings overstate what a loaded filter delivers, so take the next nominal size up; compact filter fans commonly step around 45 and 90 m³/h, and this case lands on a 90 m³/h unit. Above about 1000 m of altitude, thinner air carries less heat per cubic metre, so add roughly 10 to 15%. Anything else that stays energized, HMI and 24 V supply included, adds its watts to the 165 W before you pick the size.
Keeping it fixed
- Put the filters on a round: monthly in a plant running dryers, wash or replace the mats, then re-measure.
- Hold the measured rise, internal air minus intake air, at or below the design 10 K at the worst standby condition, Run command off.
- When the panel gains an always-on device, add its watts and size again. The enclosure heat calculation guide carries the full method from load to cooling, and the enclosure heat calculator runs the numbers for your box and its target temperature.
When to re-specify the enclosure
- Shade-side ambient reaches the drive's permitted 40 °C. No fan cools below the air it breathes; move to sealed cooling, and the fan, air conditioner and heat exchanger comparison lays out the trade-offs.
- The panel keeps gaining electronics. Size the next box from heat and clearance rather than parts count; the electrical enclosure sizing guide starts from the heat load.
- Washdown, brine or chlorine sanitizer. Stay sealed and step up to 316L; the washdown enclosure category sorts the material and rating choice. A custom 316L box sized from the heat load and your cutouts is delivered in 10 business days from drawing approval.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can I keep the drive's internal fan running without a Run command?
The fan follows the Run command alone and offers no always-on setting, so the fix sits outside the drive: an enclosure filter fan powered independently of it. A 5.5 kW unit standing by dissipates about 165 W at the 3% estimating rule, and a 10 K rise asks for roughly 51 m³/h of airflow at sea level.
How much heat does a drive give off while standing by?
Estimate about 3% of the drive rating when the loss table is not at hand: a 5.5 kW unit gives roughly 165 W with the Run command off. Add every other device that stays energized, because control supplies, HMIs and PLCs idle with the drive. A documented power-loss figure from the drive's data replaces the 3% estimate.
Does a filter fan keep a NEMA 4X or IP66 rating on the box?
An open fan-filter opening drops the assembled enclosure below its NEMA 4X / IP66 rating, so hosed-down boxes keep the seal and take sealed cooling instead, an air-to-air heat exchanger or an enclosure air conditioner. Our washdown boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and that rating belongs to the sealed assembly.
Where should the enclosure fan and filter sit, and when should the fan run?
Intake filter fan low on one face, exhaust filter high on the opposite face, so the stream crosses the drive before it leaves and the box holds positive pressure.