Short answer: a panel with three 24 V power supplies, one compact PLC, two remote I/O heads carrying 8 and 12 modules, five breakers and two terminal rows fits an 800 x 600 x 300 mm [31.5 x 24 x 12 in] enclosure with 20% spare. Three equipment rows sit on 150 mm [6 in] centers, two terminal rows below them on 120 mm [4.7 in], with 100 mm [4 in] clear to the closed door. Which catalog you buy that box from is the last decision, not the first. The size comes out of four sums - module widths, row pitch, depth and heat - and this walkthrough does them on a representative build.
Count the width in modules
DIN rail parts are specified in modules, and one module is 18 mm [0.71 in] of rail. One pole of a breaker takes one module. Most 5 A power supplies run about six modules, a compact PLC CPU about the same, and single I/O modules one to two each. Pull the real width from the datasheet of the part you bought, then check it against the budget below.
| Row | Contents | Width sum | Total |
|---|---|---|---|
| Power | 3 x 5 A supply + 5 one-pole breakers | 3 x 108 + 5 x 18 mm | 414 mm |
| Controller | PLC CPU + head 1 (adapter + 8 modules) | 108 + 60 + 8 x 18 mm | 312 mm |
| I/O and spare | head 2 (adapter + 12 modules) + 4 spare slots | 60 + 12 x 18 + 4 x 18 mm | 348 mm |
| Terminals | 48 feed-through, 2.5 mm2 | 48 x 6 mm | 288 mm |
| Terminals | 48 feed-through, 2.5 mm2 | 48 x 6 mm | 288 mm |
The adapters that power each I/O head run 45-90 mm across makers, and a 2.5 mm2 feed-through terminal is 5.2-6.2 mm in most catalogs, so 6 mm is the safe budget. Count your terminals from the I/O schedule; this build carries 96.
The longest row is the power row at 414 mm. A 600 mm [23.6 in] wide body gives about 540 mm [21.3 in] of rail after the walls, the door flange and one vertical duct run, and the shop drawing prints the exact figure. Twenty percent spare puts the requirement at 497 mm and twenty-five at 518 mm, so both fit. At 30% you sit at 538 mm with 2 mm in hand, so call 30% the ceiling of this width. A fourth supply later, or 10 A supplies at 8-10 modules each, moves you to a 700 mm [27.6 in] body.
Breaker poles move the row just as fast. Five three-pole breakers take 270 mm instead of 90, the power row grows to 594 mm, and 20% spare then wants an 800 mm wide body.
Turn the rows into height
Give every equipment row 150 mm [5.9 in] of pitch, rail center to rail center: up to 125 mm of device and connector, then finger room and duct. Terminal rows live on 120 mm [4.7 in] - block, duct and the wire sweep down to the glands. Five rows stack to 3 x 150 + 2 x 120 = 690 mm [27.2 in], and an 800 mm body leaves about 725 mm of panel height, so the layout lands with 35 mm in hand.
Order the rows top to bottom - power, controller, I/O, then terminals - so the bottom glands meet the terminals first and the power drops stay short. Fill horizontal duct to 50% of its cross-section at most; that is the fill limit our backplate and DIN rail layout guide works from under NFPA 79's percentage-fill rule, and round cables never pack tighter. Cut each rail about 20 mm short of the duct ends and fasten it through the panel at the intervals DIN rail fastener spacing standards set out, so a full row never bows the rail. For the finger space above terminal rows, the numbers are in terminal block row spacing and finger duct clearance.
Set the depth from the deepest part
Depth is a one-line sum: panel setback, deepest device, then 100 mm [4 in] of clear space to the closed door. A 5 A supply with its connectors is about 130 mm [5.1 in] deep, so 25 + 130 + 100 = 255 mm [10 in] against the 280 mm [11 in] a 300 mm body gives you inside - 25 mm to spare. That 100 mm is working room for the wiring bulge, door hardware and your gloves. Spend it, and the door stops latching flat on its gasket.
If a display or a disconnect handle joins the door later, check its protrusion instead; a door HMI brings its bezel and its cable run. The same depth method for a full rail of devices is in minimum depth for DIN rail devices.
Keep spare you will actually use
Panel specifications commonly call for 20% spare, and 20 to 25% is the range most builders quote; sit at the top of it when the I/O count may grow. Spare is area on the panel, not air in the box. Reserve the vertical duct, the door clearance and the service room first, then count what is left, because space that looks empty at assembly is usually spoken for by cable paths once the wiring lands. Add module-level spare too - two empty slots per I/O head and one breaker position, as in the 348 mm row above - since growth arrives as modules rather than square millimeters.
Run the heat check before you order
Heat decides whether the box you sized is the box you can run. Sum the losses: at 90% efficiency, three supplies delivering 360 W lose about 10% of that, 36 W; the CPU adds about 12 W; twenty I/O modules add about 1.5 W each, 30 W. That totals 78 W - call it 80 W [273 BTU/h].
Stainless sheds about 3.7 W per square meter per kelvin, and painted steel manages 5.5. The surface of this box is 2 x (0.8 x 0.6 + 0.8 x 0.3 + 0.6 x 0.3) = 1.8 m2 [19.4 sq ft], so the rise is 80 / (3.7 x 1.8) = 12 K. In a 25 C [77 F] plant the inside sits near 37 C [99 F], under the 40 C [104 F] that PLCs, supplies and most electronics are rated for, with 3 K of margin. In a 35 C [95 F] plant the same box runs 47 C [117 F] and eats the rating.
At 35 C you cool the box rather than upsize it. To hold 40 C inside, the cooler moves 80 - (3.7 x 1.8 x 5) = 47 W, and with the 15% cooling reserve builders commonly specify, that is a 55 W unit at those conditions. Keep the seal with an air-to-air heat exchanger or an enclosure air conditioner; a filter fan only belongs where Type 12 air is good enough for the room. Size from the nameplate first and bank the part-load difference as margin. With several supplies stacked in one box the losses compound, as shown in nested enclosure heat buildup, and outdoors the sun loads the box before your equipment draws a watt - start from the outdoor enclosure guide.
The sizing steps in order
These seven steps give you the layout numbers. Heavy power wiring adds conductor bending space and enclosure fill limits on top, and the tables behind those are in the electrical enclosure sizing guide.
- List every device with its datasheet width and convert to modules; one breaker pole is one 18 mm module.
- Sort the devices into rows: power on top, then controller and I/O, terminals last so they meet the bottom glands.
- Take the longest row, add 20-25% spare, then add about 60 mm for walls, flange and one vertical duct; that is the body width.
- Multiply the rows by pitch - 150 mm per equipment row, 120 mm per terminal row - then add about 75 mm for the body height.
- Add the 25 mm setback, the deepest device and the 100 mm door clearance; that is the depth.
- Run the heat check and hold the inside at 40 C at your worst ambient, adding a cooler with its 15% reserve when the rise runs past the limit.
- Send material, rating and cutouts, and check the rail length and panel height on the returned drawing before you approve it.
Checks when the panel is built
- After two hours at real load, the inside air reads 40 C or less in a 25 C plant. Read it through the door window with an IR gun, or isolate the panel and prove zero voltage before opening the door - the one safety rule in this list.
- The door latches flat with every wire landed, so the 100 mm of clearance survived the wiring.
- Duct fill sits at or under 50%, with nothing pinched across a duct edge.
- The highest breaker handle lands at or under 2.0 m [6 ft 7 in] above the floor, where NEC 240.24(A) caps the grip of the operating handle in its highest position.
Where the box hangs
NEC 110.26(A) sets the space in front of equipment you will service energized: at least 900 mm [3 ft] deep for 0-150 V to ground in the common condition, 6.5 ft [2 m] of height or the equipment height, and room for a 90-degree door swing. A 480 V feed is 277 V to ground and moves you into the deeper rows of that table - the enclosure mounting guide walks them. Hang the box with its top edge near 1.7 m [5.6 ft]: the breaker row lands around 1.5-1.6 m, under the handle cap, and the terminals land near waist height where you spend your day.
What to put on the order
With the four numbers in hand, the shopping question answers itself: any enclosure line sells a box this size, and what differs is material, rating and who cuts the holes. Ours is built to your width, height, depth and cutout list from one piece and delivered in 10 business days - counted from your order, or from your approval of the drawing for custom work - through the Industrial Monitor Direct checkout.
- Body: 800 x 600 x 300 mm [31.5 x 24 x 12 in], with 540 mm of rail and 725 mm of panel confirmed on the drawing.
- Material: 304 stainless for indoor washdown and food plants; 316L where salt air, brine or chlorides reach the box.
- Rating: NEMA 4X / IP66 by the manufacturer, not UL listed. A job that calls for a listed panel is built to UL 508A and marked with its enclosure type under NEC 409.110 - say which path the spec takes when you order, and the UL 50E listing guide explains the difference.
- Cutouts: glands in the bottom face only, sized to your cable list, with hole dimensions in the cutouts and glands guide; a window cutout in the door covers a later HMI.
Start at the custom enclosure page with these numbers, or run the stainless enclosure size finder - the stock wall-mount line runs to 60 x 36 x 16 in outside - and the enclosure selector filters by module count and door clearance.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
How much spare space should a PLC enclosure have?
Plan 20% spare on your longest row and 25% when more I/O is likely, plus two empty module slots per I/O head and one breaker position. Count the spare only after you reserve cable duct, service access and the 100 mm [4 in] of door clearance; space that looks empty at assembly is usually already spoken for by cable paths.
What size enclosure does a compact PLC with two remote I/O heads need?
With three 5 A supplies, 20 I/O modules, five breakers and 96 terminals, the arithmetic lands on 800 x 600 x 300 mm [31.5 x 24 x 12 in]: five rows, longest row 414 mm plus 20% spare, and 690 mm of stacked rows against about 725 mm of panel. Growing I/O counts push the width before they push the height.
How hot can a PLC enclosure run?
Hold the inside air at 40 C [104 F] or less for typical PLC and power supply ratings unless the datasheet allows more. An 80 W load in this 800 x 600 x 300 mm box gives a 12 K rise: about 37 C at 25 C ambient and 47 C at 35 C. At the hotter ambient fit a cooler of about 55 W at those conditions, chosen with its 15% reserve.
Do I need a UL listed enclosure for a PLC panel?
Only when the specification or the inspector calls for listed equipment. A listed industrial control panel is built to UL 508A and marked with its enclosure type under NEC 409.110. Our enclosures are rated NEMA 4X / IP66 by the manufacturer and are not UL listed, so say which path the job takes when you order.