Short answer: the magnetic trip on a panel breaker is a band, not a line, and you read both edges of it. A motor-circuit breaker set to 14 A picks up instantaneously somewhere between 8x and 13x that setting — 112 A on the low edge, 182 A on the high. A type C miniature breaker does it between 5x and 10x its rating. Starting current stays under the lower edge, and the smallest fault at the load end clears above the upper edge. Here is how you pull the characteristic for the exact device bolted inside your enclosure, read its multiplier axis, and place inrush, fault current and the upstream breaker on it. The bands quoted here are documented typical values; the sheet for your order number wins where it differs.
What does a magnetic trip curve show?
It shows how fast the breaker operates at high current: a near-vertical band on the time-current characteristic, where the mechanism unlatches within a few milliseconds of current crossing a fixed multiple of the rating. The rest of the characteristic is the overload region, a slope where trip time falls as current rises, roughly on an I²t basis.
The instantaneous part draws as a band because production tolerance, temperature and supply frequency each shift the pickup a little; the nominal line on the datasheet is only the middle of that spread, so you work from the two edges. Many sheets label this region the average unlatching time — current keeps flowing until the arc clears after the mechanism lets go, so a few milliseconds of arc time get added whenever two devices are compared. An electronic release produces the same instantaneous shape with no magnetic parts; ask for the instantaneous characteristic either way. If you are still choosing the device itself, fuses or breakers inside a control panel enclosure covers that step.
How do I get the trip curve for the breaker in my panel?
You pull it from the manufacturer's documentation for the full order number on the nameplate, plus the installed release and its dial positions, because two breakers sharing a family prefix can differ by 2x or more in rating. Photograph the nameplate with the panel locked out, or hand the job to a qualified person with the arc-flash gear the task calls for. Then match what you recorded against the document and file the two together.
| Record from the nameplate | Why it moves the curve |
|---|---|
| Full order number, every character | the prefix repeats across ratings; the suffix carries the release |
| Release type: thermal-magnetic, magnetic-only, electronic | the instantaneous function is drawn per technology |
| Rated current and current setting | the multiplier axis is referenced to these |
| Positions of the adjustment dials | the plotted band follows what you actually dialed in |
| Curve document title, revision, page | keeps the study repeatable at the next audit |
A catalog table quoting one pickup threshold serves selection; the study itself needs the curve, because the tolerance edges and the operating times live only there. Where a family-level graph covers several variants, its coverage line has to name yours. If the mapping stays unclear, send the maker's support channel the order number, the nameplate photo and the settings, and ask for the matching characteristic.
How do I read a current axis marked in multiples?
Multiply the axis value by the reference current the document states: I = x × Iref, so a curve normalized to a 30 A setting puts its 8x gridline at 8 × 30 A = 240 A. The reference is usually the breaker's rated current, written In, or the release's current setting; the sheet defines which, and that definition is part of the curve. Both axes are logarithmic, so equal distances mean equal ratios — halfway between 100 A and 200 A sits near 141 A, which is why you read the decade lines instead of splitting the gap by eye.
Two conversions prevent most of the errors. Curve sheets are drawn in symmetrical RMS amperes, while your scope captures peaks, so divide a measured peak by 1.41 before plotting it, and expect a fully offset first half-cycle to nearly double that peak again. On the time axis, read whether the sheet plots release time or total clearing time; the two differ by the arc duration, and the selectivity math in the last section cares about that difference.
Where does the magnetic band sit on common panel breakers?
On miniature breakers the letter sets it — type B spans 3x to 5x In, type C 5x to 10x In, type D 10x to 20x In — and motor-circuit protectors give you an adjustable window of 800% to 1300% of motor full-load current. Those letter bands come from IEC 60898-1; breakers built to UL 489 and IEC 60947-2 publish characteristic sheets with no letters attached, and the reading method above applies to them unchanged. Band edges are type-test results at the reference temperature and frequency the sheet states, so note those conditions when your panel runs hot.
| Device in the panel | Instantaneous band | Basis |
|---|---|---|
| Miniature breaker, type B | 3x to 5x In | IEC 60898-1 letter bands |
| Miniature breaker, type C | 5x to 10x In | IEC 60898-1 letter bands |
| Miniature breaker, type D | 10x to 20x In | IEC 60898-1 letter bands |
| Motor-circuit protector, instantaneous-only | adjustable, 800% to 1300% of motor FLC | a manufacturer digest on instantaneous-trip breakers |
| Electronic trip unit, overload pickup | 1.075x the selected rating | trip-unit documentation figure |
| Molded-case breaker, fixed magnetic | one band per frame and rating | the maker's characteristic sheet |
The NEC's motor branch-circuit rules set their own ceiling on how high an instantaneous setting may go on a motor circuit, so take the lower of the digest window and what the code permits for your motor.
How do I place motor starting current on the curve?
Take a 10 hp, 460 V three-phase motor at 14 A full-load current: locked-rotor current runs about 6x FLC, or 84 A symmetrical, and that point must sit left of the whole characteristic for the 2 s the load takes to accelerate. Set the motor-circuit breaker's current dial to 14 A. Its band then spans 8 × 14 A = 112 A on the low edge and 13 × 14 A = 182 A on the high edge.
The start check: 84 A against 112 A gives a margin of 112 ÷ 84 = 1.33, above the 1.25 floor you want between locked rotor and the low edge. One input moves it fast. Premium-efficiency motors can pull 8x FLC, which is 8 × 14 A = 112 A, exactly on the low edge; move the pickup to 1100%, or 11 × 14 A = 154 A, and the margin returns as 154 ÷ 112 = 1.38. A start is a time-and-current point, so glance at the overload slope as well — 2 s at 84 A has to clear the thermal region, not just the band. Two neighbouring checks have their own pages: instantaneous settings per pole in a motor panel and how many starts per hour a motor protection breaker tolerates.
How do I check that a distant fault still trips instantly?
Compare the smallest prospective fault current at the load end with the high edge of the band: in the example, 260 A against 182 A clears instantaneously, while 150 A would land inside the band and slide toward the overload slope. Treat the 260 A as the figure from your circuit's fault study, since it comes from conductor size and run length. Inside the band, operation is uncertain by definition — the breaker might unlatch fast or ride the thermal slope, and a slow clear at the far end of a long motor feed is how cables cook. Fix it on the impedance side: shorten the run, upsize the conductor, or parallel conductors until the minimum fault rises above the high edge.
Interrupting capacity is a different line on the datasheet, marked in kA at a voltage. With 22 kA available at that panel, a frame marked 10 kA at 480 V is the wrong device however well the band fits; step to the next standard class, 25 kA, then read its curve. What an underrated breaker does to the energy at the door is its own subject: arc flash with underrated feeder breakers in the panel.
How do I keep the upstream breaker closed on a downstream fault?
Grade the curves so the downstream device finishes first: hold its total clearing time left of the upstream unlatching curve at every current, with the arc margin of up to 10 ms counted in. In the example, feed the panel through a 63 A type C miniature breaker and its band sits at 5 × 63 A = 315 A to 10 × 63 A = 630 A. The 260 A motor-terminal fault sits below 315 A, so the feeder rides its overload slope at about 4.1x rating — a region measured in seconds — while the motor breaker finishes in under 20 ms. Selective, with room to spare.
Above 315 A the picture changes: both devices enter their instantaneous regions and time grading collapses, because unlatching happens in single-digit milliseconds either way. There you lean on the manufacturer's tested selectivity tables for that pair of frames, and on current limitation, which a curve overlay cannot show you. The mechanics of grading miniature against molded-case breakers across both regions are laid out in MCB and MCCB coordination: selectivity in overload and instantaneous regions.
What belongs in the panel file for every breaker setting?
File the curve document itself — title, revision and page — against each breaker's order number, together with the dial positions, the inrush figure and the minimum fault current you checked them against. In a panel listed to UL 508A those settings become part of the listing, so the record follows the panel for life; the UL 50E and NEMA 250 listing guide explains what that route covers.
The enclosure adds one more input the curve cannot absorb: heat. The magnetic band barely moves with temperature, but the overload slope derates as the interior warms, and a sealed box warms fast — why a hot panel trips a 2 A breaker works that arithmetic, and the enclosure heat calculator sizes the fix. When the added breaker rows outgrow the box, the enclosure selector filters candidates by inside height and DIN module count, and a custom backplate with your cutouts is delivered in 10 business days, counted from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Does a hotter panel change the magnetic trip point?
Only slightly. The magnetic band moves a few percent over tens of kelvin, while the thermal element does the real moving: a miniature breaker calibrated at 30 C can be down to about 90% of rated current by 50 C inside the enclosure. Size the enclosure cooling on the thermal side, and re-read the instantaneous band when your margin to the low edge is thin.
Can I use a curve from the same frame with a different order number?
Use the curve for the exact order number. Two breakers sharing a family prefix can differ by 2x or more in rated current and sit on different instantaneous bands. The frame only sets the interrupting rating; the release and its dial positions set the curve, so the coverage line on the curve sheet has to name your variant.
What is the difference between unlatching time and total clearing time?
Unlatching is the mechanism releasing; current keeps flowing until the arc extinguishes, and the plotted instantaneous curve is usually the average unlatching time. Total clearing adds the arc time, up to about 10 ms at 50 or 60 Hz. For selectivity, compare the downstream total clearing time against the upstream unlatching curve at the same current.
How much margin should sit between motor inrush and magnetic pickup?
Keep the band's lower edge at least 1.25 times the locked-rotor current. A 6x FLC design B start against an 8x lower edge gives 1.33 and holds. A premium-efficiency motor pulling 8x FLC lands right on the 8x edge, so move the pickup to 1100% and the margin returns to 1.38.
Does the trip curve tell me the breaker can interrupt the available fault current?
It does not; interrupting rating is a separate marked value in kA at a voltage. If the panel sees 22 kA available and the breaker is marked 10 kA, the curve is the wrong document. Pick the next standard class, 25 kA, then read its curve, and match the whole panel's short-circuit current rating to it.





