Short answer: a bare-board 2 hp [1.5 kW] VFD sheds about 60-90 W, so you size its sealed stainless box by wall area, not by horsepower. At a 25 C [77 F] shop ambient, a 40 x 32 x 16 in (H x W x D) [1016 x 813 x 406 mm] 304 wall-mount enclosure holds the drive about 10 K over outside air and keeps the board under its 40 C [104 F] rating. Bolt the board to the metal mounting panel with its thermal pad, bring the cables in through rated glands, and leave every hole and the door gasket as the factory finishes them. Our stainless wall-mount line runs from 6 x 4 x 4 in to 60 x 36 x 16 in, built to your sizes, your holes and your grade, delivered in 10 business days.
What you need
You can pull this together in an afternoon:
- The drive and its installation manual. The watts-loss table is the input every later step hangs on.
- A 304 or 316L stainless wall-mount enclosure with a removable mounting panel, in any size from 6 x 4 x 4 in to 60 x 36 x 16 in (H x W x D); the size finder for stainless wall-mount enclosures filters the line by size and grade.
- The board's mounting hardware from the manual's drawing: clamp screws, thermal pad or paste, standoffs where the drawing shows them.
- Two cable glands. A 2 hp, 230 V three-phase motor lead runs about 0.4 in [10 mm] outside diameter, which a 1/2 in NPT or M20 gland seals.
- Shielded motor cable and a ground lug for the panel's stud.
- A thermocouple probe or IR gun that reads past 60 C [140 F] for the checks at the end.
Send each gland-hole position and diameter with the order and the factory cuts them burr-free; the custom enclosure builder takes every hole from your drawing.
Find the watts before the box
Work from three sources, in this order. First, the drive manual's watts-loss table: drive makers publish losses per frame size, based on a 40 C [104 F] ambient. Second, the efficiency figure: losses are (1 - η) × rated output power, so a 96% efficient 1.5 kW drive sheds (1 - 0.96) × 1500 W = 60 W. Third, the estimate: heat-loss tables quote 2-6% of the drive's rating, and small board-style frames sit at the top of that band.
A 2 hp [1.5 kW] board drive with no manual in hand plans at the 4-6% upper half of the band. The sizing below uses the hot end, 90 W, so the box you pick is right from the first shift and gains margin on a winter morning. When the drive is truly undocumented, sizing and sealing a drive with no documentation runs the same steps from nameplate values.
Size the box from wall area
A sealed stainless wall sheds heat by convection and radiation together, and the wall-transfer value behind the sizing guides is k = 3.7 W/m²K for stainless. Interior rise over ambient is ΔT = Q ÷ (k × A), where A is the wall area that sheds heat: door, two sides, top and bottom. Leave the back out while the box hangs flat, and keep leaving it out even when the feet stand the box off the wall, so the calculation keeps margin.
Worked example, 2 hp drive at the hot-end load of 90 W, shop air at 25 C [77 F], drive rating 40 C [104 F]:
- Allowed rise: 40 - 25 = 15 K.
- Wall area that carries that load at 15 K: A = 90 ÷ (3.7 × 15) = 1.62 m².
- A 40 x 32 x 16 in box gives a door of 0.826 m², two sides of 2 × 0.413 = 0.826 m², and top plus bottom of 2 × 0.330 = 0.660 m², together 2.31 m².
- Rise: 90 ÷ (3.7 × 2.31) = 10.5 K, so interior air sits near 35.5 C, about 4.5 K under the rating.
The 24 x 20 x 10 in box that looks big enough gives 0.88 m², a rise of 27.7 K and an interior of 53 C, which is 13 K over the rating. That is the trip you meet in August. Pick from the table at your wall's hottest ambient:
| Box, H x W x D | Heat-shedding wall | Rise at the hot-end load | Interior at 25 C ambient | Interior at 35 C ambient |
|---|---|---|---|---|
| 16 x 12 x 8 in | 0.41 m² | 59 K | 84 C | 94 C |
| 24 x 20 x 10 in | 0.88 m² | 28 K | 53 C | 63 C |
| 40 x 32 x 16 in | 2.31 m² | 10.5 K | 35.5 C | 45.5 C |
| 60 x 36 x 16 in | 3.38 m² | 7.2 K | 32 C | 42 C |
A washdown corner that reaches 35 C [95 F] leaves only a 5 K rise to 40 C, and the area that carries the hot-end load at 5 K is 90 ÷ (3.7 × 5) = 4.86 m², more than the largest wall-mount box offers. Three ways out, each with numbers. Move the drive to a wall that stays near 25 C. Read the drive's rating table, because small chassis drives commonly carry a 50 C [122 F] maximum ambient with output derating between 40 and 50 C; with 50 C allowed, the 40 x 32 x 16 in box runs at 45.5 C and passes with margin. Or flange the power module through the rear wall onto the heatsink the manual shows, and size from that mounting style's watts-loss row; at a 30 W row the same box rises 30 ÷ (3.7 × 2.31) = 3.5 K. The article on sizing a non-ventilated stainless enclosure by heat dissipation works this same wall-area method for any load.
Install the board, step by step
- Set the panel first. Bolt the removable mounting panel in place and lay out rail and duct with the spacing in the backplate and DIN rail layout guide, keeping the board's air path clear.
- Fix the board metal-to-metal. Follow the manual's mounting pattern: thermal pad or paste over the full power-tab footprint, clamp screws to the manual's torque, standoffs only where the drawing shows them. Nylon standoffs alone put the module's heat into the board instead of the panel; when the panel cannot carry it, sizing a heat spreader or fins in a sealed enclosure gives the thermal path.
- Keep the manual's clearances. The installation drawing gives space above and below the board for convection and for terminal access; a 40 in tall box tempts you to shrink it, and the trip at full load is the penalty.
- Gland the entries, lowest hole first. Motor lead through the lower entry, supply through its own, every spare hole closed with a rated plug. Anything you bring through the wall needs the same rating as the box; what a panel keeps after cutouts and mounted devices explains how the assembly rating settles.
- Ground first, then dress the rest. Land the PE on the panel stud, keep signal wires 4 in [100 mm] from the motor leads or cross them at 90 degrees, and terminate the motor cable shield the way the manual's EMC section shows.
- Set the fixed 60 Hz reference and the motor data with the manual's commissioning tool while the box is still open, and wire the run command so a restored supply leaves the grinder standing until someone commands it.
- Before touching a board that has been powered, wait the manual's bus-discharge time and measure 0 V across the DC bus terminals; the capacitors hold a painful charge after the supply is off.
Checks that prove the sizing
Run the drive at working load for an hour with the door closed, then check:
- Air temperature 2 in [50 mm] above the board: 40 C [104 F] or less at the site's hottest ambient, or the value your rating table allows.
- Measured rise against the calculation. Within a few K is right; 5 K or more over the predicted rise means the watts figure was low, so re-read the manual's row.
- The drive's heatsink readout, if it has one, at least 10 K under its alarm level.
- Door gasket seated in its groove all round, with the latch compressing it evenly. A gasket proud at one corner is the leak the first hose-down finds.
- Every gland wrench-tight and every spare hole plugged.
Trips that arrive weeks later usually trace back to this heat load, and drive faults with the door closed works them in order.
Mistakes that cost the drive or the rating
- Sizing by nameplate. A 2 hp drive in a 16 x 12 x 8 in box runs an 84 C interior and trips on a mild day.
- Skipping the thermal pad. Without metal contact the power tab runs hot even when the air feels cool.
- Mounting the board on the door. The hinge swing works every terminal; the panel carries the board.
- Adding a drain or louver to a Type 4X / IP66 box. The lowest-rated part sets the assembly, so that fitting ends the rating; keep the box sealed and let the sizing carry the heat.
- Sizing at winter temperature. A box chosen in a 15 C [59 F] shop fails at a 35 C [95 F] corner in July.
- Cutting a keypad or display hole behind an unrated bezel. The assembly drops to the bezel's rating.
The box to order, by corner
A dry machine-shop wall at 25 C [77 F]: 40 x 32 x 16 in, 304 stainless, board on the panel, interior at 35.5 C with the drive at the worked load. A washdown corner that reaches 35 C [95 F]: the same size in 316L, with your path picked from the three above. Salt air or brine: 316L, and keep chlorides off a hot surface, because chloride deposits start stress-corrosion cracking in both grades above about 60 C [140 F], while 316L resists the pitting that starts on 304 even at room temperature.
Type 4X means hose-directed washdown water plus corrosion resistance, and the paired IP66 is dust-tight plus powerful jets, tested with a 12.5 mm nozzle at 100 L/min. Every box in the line is rated NEMA 4X / IP66 by the manufacturer; not UL listed. Order with your sizes, grade and gland holes on the drawing, and the 10-business-day clock starts at your approval of it.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 24 × 20 × 10 in | 304 stainless | 24 x 20 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a bare-board VFD run with no enclosure at all?
On a dry bench for a test run, yes; the board carries no rating of its own, so dust, rinse water and grindings reach its terminals and DC bus capacitors directly. On a plant wall it needs a sealed box: our 304 and 316L wall-mount enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and sized so the 4-6% loss of a 2 hp unit keeps the interior at or under 40 C.
Does a board drive run cooler than a packaged drive of the same rating?
The power stage loses the same share either way: drive heat-loss tables quote 2-6% of rating at a 40 C ambient, so a 2 hp unit sheds the same watts packaged or bare. What changes is where the heat lands. If the manual's mounting style clamps the power module to a heatsink through the rear wall, most of the module's heat leaves through the outside fins, and you size the box from that mounting style's watts-loss row instead.
What happens when the air inside passes the drive's rating?
Nothing at first, then trips: rating tables derate output above 40 C [104 F], and at the table's maximum the drive alarms on heatsink temperature and cuts output. Repeated hot trips age the DC bus capacitors, which is the failure that shows up a year later. Size the box so interior air stays at or under 40 C [104 F] at the site's hottest ambient, or use the 50 C [122 F] row only if your drive's rating table prints one.
304 or 316L for a grinder that gets washed down?
304 stainless for fresh-water washdown; 316L where brine, chlorinated sanitizer or salt air reaches the box. Watch heat and chlorides together: above about 60 C [140 F] surface temperature, chloride deposits start stress-corrosion cracking in both grades, and 304 can pit under deposits even at room temperature. A hot, salty corner is the case that pays for 316L; a plain machine shop washdown is not.