Short answer: bond any fence section a conductor above 24 VDC can touch, and bond any fence that supports conduit, cable tray or a bonded machine frame. A painted bolted joint is not a bond: strip every lug contact to bare metal, jumper 10 mm² (8 AWG) copper panel to panel, home-run one return to the control panel's PE bar, and accept 0.1 Ω measured four-wire at the farthest panel. A 24 VDC-only fence with no bonded neighbour is the one case where the bond is optional, and it still buys visible fault detection for the price of one jumper. The guard standards themselves do not settle it: ISO 14120 covers guard design and construction, and ANSI/RIA R15.06-2012 covers robot-cell safeguarding, so the machine electrical standards and the NEC do the deciding. The hardware is a morning's work per cell.
Which standard settles it
ISO 14120:2015 spells out the design, construction and selection of guards: materials, strength, fasteners and interlocks. It says nothing about whether the guard carries a protective bond, so treat it as a construction standard rather than an electrical one. ANSI/RIA R15.06-2012 is the industrial robot safety standard that OSHA's technical manual points to. It governs how the cell is safeguarded, not the fence's continuity to earth.
The bond lands where machine electrical work lands. Machine-building practice follows IEC 60204-1's protective bonding test: push 10 A through the bonding circuit and read the resistance, with 0.1 Ω as the acceptance figure. NFPA 79 covers the same ground for machines built to North American practice. On the supply side, NEC 250.96(A) requires metal parts intended to serve as equipment grounding conductors — raceways, cables, equipment, enclosures — to be bonded together so they can safely carry any fault current likely to be imposed on them. A fence that holds conduit or cable tray is exactly such a part.
The 24 VDC boundary is simpler than it looks. Circuits up to 30 V RMS AC or 60 V DC sit inside the NEC's low-energy Class 2 envelope, so a chafed control cable touching a fence is an equipment fault, not a shock hazard. That is why the 24 VDC-only fence stands outside the shock-bonding rule.
Sort every fence section into one of three cases
Walk the cell with the schematics and list, for each fence section, every conductor that touches it or runs along it, with its highest voltage. The finished sheet gives a voltage entry per section and leaves nothing marked unknown. Then apply the table.
| Fence section | Bond? | Basis |
|---|---|---|
| 24 VDC devices and cables only, no bonded structure in reach | Optional; add it for fault detection | Below the 30 V RMS / 60 V DC Class 2 line, so no shock bond is owed |
| Supports or touches conduit, cable tray or a bonded machine frame | Bond to the same PE system | NEC 250.96(A): metal parts serving as grounding conductors are bonded together |
| Mains conductors, devices or powered doors wired across it | Bond every metal part that wiring can reach | A fault to the guard is a live shock hazard |
The middle row is the one most cells miss. Cable tray and conduit hug the fence line because it is a straight, free support, and every clamp makes the fence part of the bonded structure. A fence-mounted push-button station or junction box is bonded through its own equipment grounding conductor at the entry connector, as in grounding conductor entry: connector and bond. The fence it bolts to follows the table, and the station's bond does not bond the fence.
What you need
- A four-wire (Kelvin) ohmmeter that resolves 1 mΩ; a 2-wire handheld adds tens to hundreds of milliohms of lead and clip resistance, more than the entire 0.1 Ω budget.
- Tinned copper braid: 10 mm² (8 AWG) for panel-to-panel jumpers, 16 mm² (6 AWG) for the home run.
- Closed-barrel copper lugs crimped with the tool matched to the lug, plus external-tooth star washers.
- A flap disc or wire brush to reach bare metal, and zinc-rich cold-galvanizing paint to re-coat each cleaned spot.
- Labels and a marker for the as-built drawing.
- For washdown or salt-air cells: 316L stainless braid, because bare copper on galvanized posts corrodes the zinc and loosens within a couple of seasons.
- A new fence-mounted operator station for a wet cell? Order it as a custom build: custom stainless enclosures with factory cutouts are delivered in 10 business days from drawing approval.
Bond the fence in nine steps
- Map the conductors. Walk the cell with the schematics, list each section's conductors and voltages, and mark every section BOND, OPTIONAL or CLEAR against the table above.
- Pick one return point: the ground bar inside the control panel, not the painted machine frame. The panel-side scheme is set out in the grounding and bonding guide, and the bar-versus-backplane choice in ground bar versus backplane bonding.
- Size the conductors from NEC Table 250.122, by the rating of the overcurrent device that could fault onto the fence: 12 AWG copper for a 20 A device, 8 AWG for 100 A. Hold every jumper at 10 mm² (8 AWG) or larger so the chain stays far under 0.1 Ω; bonding conductor sizing for accessible equipment works the same way.
- Strip every contact to bare metal. NEC 250.12 requires paint, lacquer and enamel off threads and contact surfaces at grounding connections unless the fitting is designed to bite through them. Lug on bare metal, star washer on top, re-coat afterwards; the same joint rules as enclosure grounding screw threads and lug fit apply.
- Jumper every joint, panel to panel and panel to post. A joint without a jumper does not exist electrically.
- Cross each gate and removable panel with flexible braid at least equal to the panel jumper, bolted through its own terminal so the gate cannot be refitted without it. A hinge pin through two painted castings reads ohms, not milliohms, which is why door bonding straps and continuity checks matter on enclosures too.
- Home-run one return to the PE bar, 16 mm² (6 AWG) minimum, as a single path. Parallel returns through the frame build loops, and loops inject noise into the analog and fieldbus cable running along the fence.
- Re-protect and label. Zinc-rich paint or grease on every cleaned spot, a numbered label at each bond point, and both recorded on the as-built drawing.
- Measure before you sign the job off, using the checks below.
Worked example: a 24 m painted fence chain
Take one six-panel run: 24 m (79 ft) from the PE bar to the farthest gate post, eight bolted joints, 10 mm² jumper wire throughout. Copper at 20 °C has a resistivity of 1.72×10⁻⁸ Ω·m, so 10 mm² wire runs 1.7 mΩ per metre (1.72×10⁻⁸ ÷ 10×10⁻⁶ m²). The wire contributes 24 m × 1.7 mΩ/m = 41 mΩ. Assume 2 mΩ per cleaned bolted joint as an illustrative figure — substitute a measurement from a scrap joint — for 8 × 2 = 16 mΩ. The chain reads about 57 mΩ against the 100 mΩ limit: a pass with 43 mΩ of margin. At 40 °C, copper resistance has risen 0.39 % per kelvin over 20 K, about 7.8 %, and the same chain reads 62 mΩ, still a pass.
Now leave one joint under its powder coat and measure it at 0.8 Ω. The chain becomes 41 + 16 − 2 + 800 = 855 mΩ, 8.6 times the limit, and the farthest-panel sweep finds it as a step of roughly 800 mΩ at that single joint. Substitute the run length, joint count and joint milliohms of the cell at hand; the arithmetic stays the same.
Checks when the job is done
- Continuity, farthest first. Four-wire from the farthest panel and from every gate to the PE bar: each reading below 0.1 Ω, stepping smoothly along the chain. A jump of tens of milliohms between neighbours marks the failed joint.
- Voltage, zero on both ranges. With the cell energized, measure AC and DC from each section to the PE bar: 0 V expected. A steady 24 V DC reading means a conductor is already touching or leaking onto that section, and it moves to the bonded row.
- Insulation on the fence runs. Lock out the cell and verify absence of voltage, then measure ohms from each conductor running along the fence to the fence metal: megaohms expected, and a kilohm reading marks a chafe or a cable clamped through its jacket.
- Interlocks and monitors. Re-energize, cycle every gate interlock, and confirm no earth-fault or supply-monitor indication during operation.
- Re-check once a year and after any panel swap; washdown cells shake joints loose faster, so halve the interval there.
Mistakes that quietly undo the bond
- Verdicts from a 2-wire meter. The leads alone read tens to hundreds of milliohms, so a bond verified on a handheld is a guess until it is measured four-wire.
- The fence as fault path. Conduit mounted on the fence keeps its own equipment grounding conductor; the fence is bonded support, and when a metal raceway can serve as the equipment grounding conductor explains the line between the two.
- Parallel returns. Two home runs to different structures set up loops around the cable route; one defined return keeps the noise off the analog and fieldbus wiring.
- Bare copper on galvanized posts in a wet cell. The zinc sacrifices itself around the lug and the joint loosens in a season or two; tinned copper or 316L braid holds.
- The through-paint bond, the joint NEC 250.12 exists for: when the four-wire reading exceeds 0.1 Ω, the joint is the problem and the wire is innocent.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Do fence panels that only carry 24 VDC cables need bonding?
For shock protection, no: 24 VDC sits inside the NEC Class 2 envelope of 30 V RMS AC or 60 V DC, so no bond is owed on shock grounds. Add one anyway when the run supports conduit or tray or a bonded frame sits within reach; a single 10 mm² jumper per section turns a hidden chafe into a visible fuse trip and costs an afternoon.
What resistance should a guarding bond read?
0.1 Ω or less, measured four-wire at the 10 A test level, the acceptance figure machine builders take from IEC 60204-1's protective bonding test. Log every panel: cleaned joints add 2-5 mΩ each, so a step of 50 mΩ or more between neighbours points at the failed bolt before you even strip it.
Can the fence itself carry fault current instead of a dedicated bond?
Treat it as bonded support, never as the conductor. Bolted joints through coating are not an effective ground-fault current path as NEC 250.4(A)(5) defines it, so size a dedicated copper jumper from NEC Table 250.122: 8 AWG for a 100 A overcurrent device, 12 AWG for 20 A, and let the fence carry only faults onto itself.
Do copper jumpers last on galvanized fence posts?
Not in wet or washdown cells: the zinc around a bare copper lug corrodes away and the joint loosens within a couple of seasons. Use tinned copper or 316L stainless braid at those points, and re-test continuity once a year; a 316L braid on a stainless post holds its milliohm reading through salt air.