Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Fan filter enclosure cooling for a PLC: size it right

Size the fan-filter from heat load: airflow in m³/h ≈ 3 × watts ÷ rise in kelvin, so a 60 W example panel holding a 10 K rise needs 18 m³/h [10.6 CFM], filtered, blown inward at positive pressure, inlet low and exhaust high. In washdown, conductive dust or corrosive air, seal the box instead and cool it with a heat exchanger or air conditioner.

NEMA4 Enclosure engineering team · Published November 23, 2026 · 9 min read

Size the filter fan from the heat the cabinet loses, never from the free-air figure on the carton. A 60 W PLC panel holding a 10 K [18 °F] rise over 30 °C [86 °F] shop air needs 3 × 60 / 10 = 18 m³/h [10.6 CFM] of filtered air. Blow that air inward so the enclosure runs at positive pressure. If the site washes the box down, grinds metal nearby or carries corrosive vapour, fit no ventilation: seal the enclosure and cool it with a heat exchanger or air conditioner. The arithmetic is one line; the rest is placement, gaskets and a thermostat. The worked panel below assumes 60 W of dissipation, a 30 °C [86 °F] shop peak and modules rated to 40 °C [104 °F] — replace each with your own datasheet figures.

How much airflow does a PLC enclosure need?

Budget airflow in m³/h ≈ 3 × watts ÷ rise in kelvin. The worked panel's 60 W against a 10 K [18 °F] rise therefore needs 3 × 60 / 10 = 18 m³/h [10.6 CFM] of filtered air through the mat.

The 3.0 comes from a heat balance on the air stream: watts = 1.2 kg/m³ × 1005 J/(kg·K) × airflow × rise. Air near room temperature runs about 1.2 kg/m³ with cp = 1005 J/(kg·K), and 3600 s per hour ÷ (1.2 × 1005) = 2.99, rounded to 3.0. In imperial units the same balance reads CFM ≈ 3.16 × watts ÷ ΔT in °F. A fan maker's sizing example lands on the same number: 400 W held at a 20 °F rise takes 3.16 × 400 / 20 ≈ 63 CFM.

The load scales the answer one to one: 120 W doubles it to 36 m³/h [21.2 CFM]. The rise budget scales it inversely: the same 60 W at a 5 K budget needs 36 m³/h, and at a 20 K budget only 9 m³/h [5.3 CFM]. Set the budget as the module datasheet's ambient limit minus the shop's hottest afternoon. Most electronics datasheets publish 40 °C [104 °F]; a 30 °C peak leaves the 10 K used here. Air exchange only ever pulls the box toward shop temperature. When peak ambient climbs near the limit, no fan fixes it — that becomes the sealed-cooler decision later in this article.

Which heat loads do you add up first?

Add the stated power dissipation of every device in the box, not nameplate input power. In the example a compact PLC at 15 W, two expansion modules adding 10 W, a 24 V supply at 25 W and a small HMI at 10 W total the panel's 60 W.

Device in the worked panel Example dissipation Where your number comes from
Compact PLC CPU 15 W datasheet power loss at your scan and load
Two expansion modules 10 W datasheet power loss, added
24 V power supply 25 W datasheet loss at your actual load point
Small HMI 10 W datasheet power consumption
Total 60 W feeds the airflow line above

Each figure here is an example assumption; read yours from the power-loss column of each datasheet. The supply is the usual trap. A 90 % efficient unit delivering 250 W dissipates about 28 W, but the same unit at 100 W out dissipates roughly 11 W, so size at the load you actually run. Energized relay and contactor coils add a few watts each. On a sunlit wall, solar gain joins the sum and can rival a PLC all by itself. The full sizing method, wall losses and sealed boxes included, sits in the enclosure sizing guide; this article works only the fan branch.

How do you pick the filter fan model?

Select on the fan's pressure-flow curve at the resistance of the filter mat, grille and screen combined. The free-air rating on the carton applies at zero resistance and overstates the airflow you will get.

Free air means no back-pressure. Behind a loaded mat, a grille and an insect screen the operating point slides down the curve, so find the model that still delivers 18 m³/h [10.6 CFM] at that point. When the point lands in the steep part of the curve, step up one size so a mat half through its service life still meets the budget. Run the fan on a thermostat that closes at 35 °C [95 °F] and releases at 30 °C [86 °F]; the 5 K gap keeps it from hunting on mild days.

Mount the fan so it pushes shop air in. Enclosure fans are brushless DC or EC types: swapping the supply wires does not reverse one and can damage it — turn the fan round instead. A matched exhaust fan is money wasted, because fans in series move the same air as one; their flows never add.

Where do the fan filter and exhaust openings go?

Put the filtered inlet low on one side face with the fan blowing inward, and the screened exhaust high on the opposite face. Air then enters cool at the bottom and leaves at the top, along the convection path the modules want anyway.

Fit it in this order:

  1. Order both cutouts with the enclosure: the filter-fan cutout low on one side, the exhaust cutout high on the opposite side. Factory-cut openings arrive deburred and matched to their gasketed frames; the cutout and gland guide covers sizes and placement.
  2. Mount the filter fan on its frame with the gasket seated all round, fan pushing inward.
  3. Fit the exhaust grille with its insect screen high on the opposite face. Screen it — insects walk in through an idle exhaust the moment the fan stops.
  4. Keep about 2 in [50 mm] clear above and below the DIN rail unless the module manual asks for more; the backplate layout guide shows the spacing. Wire duct, cable looms or a document pocket in that band strangles the convection channel.
  5. Mount the 24 V supply and any transformer low on the exhaust side, and the PLC mid-height toward the inlet, out of the hot plume rising off the supply.
  6. Gland every other cable entry. One open knockout bypasses the filter and equalizes the box you just paid to pressurize.
  7. Wire the fan through the thermostat, 35 °C [95 °F] on and 30 °C [86 °F] off. Isolate the panel and check for absence of voltage before you open it.
  8. Write the filter mat's fit date on the inside of the door, so service has a starting point.

Does positive pressure keep dust and insects out?

Positive pressure pushes leakage out through door gaps and glands while the fan runs. That stops unfiltered air being sucked in, but it is leak-direction control: it does not make the box dustproof, and it ends when the fan stops.

The mat does the filtering: every cubic metre that enters passes through it, and insects meet the mesh before the mat. Screen the exhaust too, because that opening breathes backwards each time the fan shuts off. When the fan stops on a cool night, pressure simply equalizes through the mat, which still filters what passes. The openings cost you the sealed rating, and that is worth saying plainly: our 304 and 316L boxes come rated NEMA 4X / IP66 by the manufacturer; not UL listed. A filter-fan cutout turns the sealed box into a ventilated one, and the finished assembly then protects only as well as its lowest-rated opening — the logic the NEMA types guide explains for every type. The grounding and bonding guide covers what a cutout changes for the box's earth path.

When should you seal the box instead?

Skip air exchange when the site washes the box down, carries conductive dust or holds corrosive vapour. A sealed stainless shell sheds about 21 W at a 10 K rise, and a heat exchanger or air conditioner covers the rest.

The shell number comes from P = k × A × ΔT with k = 3.7 W/m²K for stainless. Take a 20 × 16 × 8 in [508 × 406 × 203 mm] wall-mount box — an example size, since you set your own dimensions. Faces: 2 × 0.508 × 0.406 = 0.413 m². Sides: 2 × 0.406 × 0.203 = 0.165 m². Top and bottom: 2 × 0.508 × 0.203 = 0.206 m². That is 0.784 m², about 0.58 m² once the back face sits against the wall.

At the 10 K rise the shell sheds 3.7 × 0.58 × 10 ≈ 21 W, leaving 60 − 21 = 39 W for the cooler. Heat exchangers are rated in W/K, so 39 W ÷ 10 K = 3.9 W/K is the floor. A compact 8 W/K unit moves 80 W at 10 K with headroom for a warm snap.

Choose by site and ambient:

  • Washdown, hose-down or corrosive air: sealed 316L shell, heat exchanger on its gasket, cooler made for sealed enclosures so the shell stays closed. See the 4X and IP66 guide for what the rating covers.
  • Conductive dust: sealed, and the exchanger keeps the dust outside where it belongs.
  • Peak ambient at or near the 40 °C [104 °F] limit: an air conditioner, because an exchanger can only pull the box toward ambient.
  • Uncertain between devices: the outdoor enclosures guide walks the crossover in watts and ambient for exposed sites.

How do you check that the cooling works?

Check the finished panel with the door closed at steady load. Air near the top of the cabinet should sit within a couple of kelvin of the planned 10 K rise. An anemometer at the exhaust should read about 0.5 m/s [98 ft/min] for the 18 m³/h design.

Give the panel 30-60 minutes at working load before trusting the thermometer; the mounting plate and wire duct take that long to settle. The velocity figure is arithmetic, not a guess. 18 m³/h is 0.005 m³/s, and through a 100 × 100 mm [4 × 4 in] exhaust grille — 0.01 m² — that is 0.5 m/s. Scale yours the same way: flow in m³/s divided by grille area in m².

A rise of 15 K instead of 10 K means flow has fallen to about 12 m³/h, because rise runs inversely against flow at a fixed load. Clean or swap the filter mat first, then look for a blocked exhaust grille or a second fan pulling against the inlet. Put the mat on a service schedule and watch the filter for clogging before heat builds. Dusty shops fill a mat in weeks; clean shops run a season.

What should you put on the order?

Order the box with both ventilation cutouts cut at the factory — the filter-fan inlet low, the screened exhaust high. Add gasketed frames, a thermostat and glands for every cable entry; the enclosure selector carries the sizes to a quote.

Site Cooling choice On the order
Clean indoor shop, peak at or under 30 °C [86 °F] Filter fan in, screened exhaust out, thermostat Filter-fan cutout, exhaust cutout, gasketed frames, thermostat, glands
Dusty but dry, service possible Same, larger mat, tighter schedule The above plus spare filter mats
Washdown, corrosive vapour, conductive dust Sealed shell, no ventilation openings 316L shell, heat exchanger on its gasket, glands
Peak ambient near the 40 °C [104 °F] limit Sealed shell plus air conditioner AC-sized cutout and gasketed frame

Pick the material and size in the enclosure selector, then send the cutout list with the order. We build every box from 304 or 316L in the width, height and depth you set, cut every opening you list, and deliver in 10 business days anywhere in the world — counted from your order, or from your approval of the drawing when the cutouts are custom.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
30 × 24 × 10 in304 stainless30 x 24 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

How do I scale the rule to a different heat load?

Airflow in m³/h ≈ 3 × watts ÷ rise in kelvin. A 30 W panel at a 10 K budget needs 3 × 30 / 10 = 9 m³/h [5.3 CFM]; a 100 W load with a 15 K budget needs 20 m³/h [11.8 CFM]. Keep the rise as a design budget: module ambient limit minus the shop's hottest afternoon, and replace the example watts with each device's datasheet power-loss figure.

At what temperature should the fan thermostat switch?

Close the fan contact at 35 °C [95 °F] and release it at 30 °C [86 °F] — 5 K of hysteresis stops the fan hunting. The pair assumes a 30 °C shop peak against a 40 °C module limit; on a hotter site, move both settings up by the same margin and keep the release point well under the limit.

Can a fan-cooled enclosure survive washdown?

No. Any filter opening ends the sealed rating, and hose water drives past the mat; the assembly then protects only as well as its lowest-rated opening. Washdown and corrosive sites get a sealed 316L box — ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed — with a heat exchanger or air conditioner on a gasketed cutout. At the worked 60 W load, the shell sheds about 21 W and an 8 W/K exchanger covers the 39 W shortfall with headroom.

The panel runs hotter than the calculation — where did the airflow go?

A rise of 15 K instead of the planned 10 K means flow has fallen to about 12 m³/h — two thirds of the 18 m³/h design, because rise scales inversely with flow at a fixed load. Clean or replace the filter mat first, then check the exhaust grille for blockage and make sure no second fan is pulling air out against the filtered inlet.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 20 × 16 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job

Keep reading

More on outdoor, heat and moisture

All articles

Buying guides

The guides behind this answer

All guides