Email us

Este artículo está en inglés. Ver el sitio en español

Cet article est en anglais. Voir le site en français

Dieser Artikel ist auf Englisch. Website auf Deutsch ansehen

Este artigo está em inglês. Ver o site em português

本文为英文。 查看中文网站

Ex s G5 limit switch in a battery room: keep or replace?

Keep a potted limit switch marked Ex s G5 on a battery-room fire damper only when its certificate — for example PTB-NO.III B/E 20478 — names a group that covers hydrogen (IIC), gives a temperature class read from the document (G5 normally maps to T5, 100 °C, not T6 at 85 °C), and carries conditions matching the room's zone. The marking and the maintenance-database text prove none of that; if the certificate cannot be produced, replace the switch.

NEMA4 Enclosure engineering team · Published November 25, 2026 · 6 min read

Short answer: keep the switch only when its certificate passes three checks — a gas group that covers hydrogen (group IIC), a temperature class read from the certificate itself, and conditions for use that match the zone the room's classification carries. G5 normally maps to T5 at the 100 °C level, not to the T6 that guesswork quotes. A potted switch that passes all three needs no enclosure around it: the certified device is the protection. The marking on the switch and the approval line in the maintenance database prove none of the three on their own; the certificate does. Where the paper cannot be produced, or its group entry stays silent on hydrogen, the switch comes out and a certified modern type goes in.

What Ex s and G5 mark, and what they leave out

Ex s is the pre-ATEX designation for special protection. It covered constructions protected by a means outside the standard types of that era, which is why the marking names no protection mechanism. A potted contact chamber was a common route, and its direct descendant today is encapsulation, type of protection m under IEC 60079-18. The hexagon Ex mark belongs to the ATEX system; a legacy Ex s switch carries only the old word marking, so the label tells you which approval system issued the device, not how it is built.

G5 is the old German temperature class. The German G1 to G5 series is tabulated against ignition-temperature ranges, and the tables place G5 at the 100 °C level — T5. The T6 figure, 85 °C, gets quoted for G5 as a guess. The class printed on the certificate is the figure an inspection is matched against, so read it there.

The maintenance record also lists IP 66 to DIN 40050, the old German ingress standard that grew into IEC 60529. A 6 as the first digit is dust-tight; a 6 as the second is protection against powerful jets, as the IP rating chart sets out digit by digit. That rating is about washdown water and salt air, and it says nothing about ignition. The certificate, not the ingress line, decides this case.

Why the gas group decides, not the temperature

Battery rooms earn their classification from the batteries. Vented cells release hydrogen on every charge, and even valve-regulated AGM and gel cells — whose sealed label describes the cell, never the room — can vent hydrogen on overcharge. The dossier for the room therefore names hydrogen whatever the chemistry on the rack.

Hydrogen sits in gas group IIC, and that is the check that decides the case. Equipment whose certificate covers only the lower groups fails in a hydrogen atmosphere whatever its temperature class says. Certificates of that era may write the group in the notation of their time rather than IIC, so read the group entry and match it to the gas the dossier names.

Temperature rarely binds. A damper-position signal through a closed contact dissipates almost nothing, so the T5 ceiling and the T6 ceiling both clear a battery room with room to spare. The picture changes when the contacts carry a continuous load such as a heater, because the switch body then warms and the class matters. The class still comes off the certificate rather than off a conversion.

The zone binds as well. The dossier assigns the room a zone — 0 where a flammable atmosphere is present continuously, 1 where it is likely in normal operation, 2 where it is unlikely or brief. The certificate's conditions must permit that zone; an approval silent on it, or excluding it, fails even when group and class fit.

Check What passes Where you read it
Gas group Coverage of hydrogen — IIC today, in the notation of the certificate's era Group entry on the certificate
Temperature class The certificate's figure; G5 maps to the T5 level in the old German tables Temperature class entry
Zone Conditions that permit the zone the dossier assigns Conditions for use on the certificate
Electrical load Circuit voltage and current inside the certified contact rating Certificate technical data
Physical condition Potting, gland, actuator and cable undamaged Inspection of the installed switch

Worked example: five checks on one switch

A fire damper in a battery room carries a potted limit switch marked Ex s G5. The maintenance record reads: explosion category Ex s G5; approvals PTB-NO.III B/E 20478; protection category IP 66 to DIN 40050; technical data 250 V AC. Assume the contacts make a resistive 230 V AC signal at 0.1 A — illustrative values, so measure the installed circuit before comparing. That is 230 × 0.1 = 23 VA switched inside the classified room, within the 250 V AC on the record with 20 V of headroom. The same damper position can instead reach the panel as a 24 V DC signal loop through a certified isolator at 20 mA: 24 × 0.02 = 0.48 W at the contacts, roughly 48 times less energy, and the arrangement that takes the arcing question off the table.

Then run the five checks. The record supplies none of them. It names the document to retrieve — the PTB file number — and the group, class, zone conditions and contact limits all come from that document. The fifth check, physical condition, comes from the switch on the damper.

How to document the switch for continued use

A day of paperwork keeps a certified switch in service, and the same day condemns one that cannot be documented. Work the list in order:

  1. Photograph the nameplate and record the type and marking exactly as printed.
  2. Request the certificate behind the PTB file number through the manufacturer's official channels or the certification body's archive service.
  3. Read off the certificate the explosion group, the temperature class, the permitted ambient range and the conditions for use.
  4. Pull the room's hazardous-area classification dossier: gas, group, temperature demand and zone.
  5. Compare certificate against dossier line by line: group covers hydrogen, class fits, ambient covers the room, conditions match the zone.
  6. Measure the circuit the switch actually makes — voltage, current, load type — and hold it inside the certified contact rating.
  7. Inspect the installed switch with the circuit isolated and absence of voltage confirmed at the terminals: potting free of cracks, cable gland sealed and suited to the entry, actuator free, terminals tight, no discoloration.
  8. File the outcome in the equipment register with the certificate attached, so the maintenance record points to a document rather than a text string.

Keep it or replace it

Keep the switch when every line passes: certificate produced, group covers hydrogen, class fits the dossier, conditions match the room's zone, circuit inside the certified rating, and the inspection finds nothing. An undamaged certified potted switch then needs nothing added around it; an ordinary box bolted over it adds an uncertified boundary, not protection.

Replace it when any line fails. The archive produces no certificate: replace. The group entry skips hydrogen: replace, whatever the temperature class says. The potting is cracked, the gland damaged or the cable sheath degraded: replace, because those faults turn a certified device into an uncertified one in a hydrogen atmosphere.

When you replace, specify a switch certified under the current scheme for group IIC and the room's zone; encapsulated designs are the direct descendants of Ex s potting. Order the certified cable entry with it, because a new certified switch behind an uncertified gland loses the protection at the first millimetre outside the potting. The difference between a gland that seals water and one that seals gas is set out in watertight vs gas tight cable glands: what the ratings prove.

The enclosure side of a battery-room loop

If the loop needs a junction box or a terminal compartment inside the room, that box carries its own Ex certificate for the same zone; what rating a Class I Division 1 junction box needs works that decision for a terminals-only box. A stainless NEMA 4X enclosure, however well it hoses down, is ingress hardware: our washdown enclosures and stainless junction boxes are rated NEMA 4X / IP66 by the manufacturer; not UL listed, and none of them is certified equipment for a classified area (washdown enclosures, stainless junction boxes).

The same line separates ratings from certificates elsewhere on a panel. What a NEMA 4 rating covers in a Class I Division 2 area approaches the split from the switch side, and UL 50E vs NEMA 250: listed or manufacturer-rated covers the paperwork side. US specifications meet the wall in different letters: hydrogen is Group B in the NEC gas-group scheme, the counterpart of IIC, and the consequences for motors in hydrogen areas are worked through in specifying Group B motors for Class I Div 1 hydrogen areas.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in304 stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
30 × 24 × 10 in304 stainless30 x 24 x 10 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Does G5 mean T6 on an Ex s switch?

The old German G1 to G5 series is tabulated against ignition-temperature ranges, and G5 sits at the 100 °C level — T5, not T6 at 85 °C. The T6 reading circulates as a guess.

Does 20 fault-free years keep an Ex s G5 switch in a battery room?

Service history adds nothing to the file. Age leaves the potting alone — encapsulation has no breathing path and no gasket to harden — but it attacks the cable gland, the sheath and the actuator. The switch stays on the certificate and today's inspection: group covering hydrogen, class and zone matching the dossier, terminals and potting undamaged.

Is the 250 V AC line in the maintenance record the certified limit?

It is the catalogue line, and the certificate governs in a classified area; some approvals restrict the contact load or add conditions beyond the plain rating. Measure the installed circuit — in the worked example, 230 V AC resistive at 0.1 A, which is 23 VA — and hold it inside whatever the certificate's technical data states.

What replaces an Ex s G5 limit switch?

A switch certified under the current ATEX or IECEx scheme for gas group IIC and the zone the room's dossier assigns. If the signal loop runs through an isolator or barrier, the certified output parameters on the barrier must suit the certified input parameters of the new switch. Any junction box added in the room carries its own certificate for the same zone.

Does a lost certificate end the discussion?

It does unless the document comes back. The PTB file number in the record is what the manufacturer's official channels or the certification body's archive service need; the marking carries the protection letter and the temperature letter but no group entry and no conditions for use. Nothing retrieved, nothing kept: the switch comes out.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 16 × 12 × 8 inRequest a custom quote

Check the heat load in the calculator · Outdoor enclosures: sizes for this job

Keep reading

Related engineering answers

All articles

Buying guides

The guides behind this answer

All guides