Gc is the Equipment Protection Level for gas atmospheres, and the small c is the lowest of the three levels: Zone 2. A panel PC nameplate reading Ex II 3G Ex nA IIC T5 Gc carries the whole approval in that string — the industry group, the zone, the protection technique, the gas subgroup, the 100 °C surface limit and the permitted area. Decode it element by element and the installation questions answer themselves. The power supply is where panel builders trip: the certificate and its installation instructions decide, not the marking on its own. A supply sitting in the unclassified room needs no Ex rating at all. The same supply bolted inside the Zone 2 cabinet needs its own approval, and nothing the panel PC carries transfers to it.
Read the marking element by element
When a nameplate gets typed into an e-mail, the Roman numeral II often arrives as two pipes, and the subgroup IIC as a pipe with a C. Read both off the actual nameplate, because every character decodes into one check you make against the plant.
| Marking element | What it says | What you check at the plant |
|---|---|---|
| Ex | Built to the IEC 60079 series | The Ex hexagon mark is on the nameplate |
| II | Equipment group II: gas areas outside firedamp mining | Any surface plant is group II |
| 3G | ATEX category 3, gas | The EU directive's Zone 2 category |
| Ex nA | Type of protection: non-sparking | No ignition-capable arcs, sparks or hot surfaces in normal operation |
| IIC | Gas subgroup, the most easily ignited | Covers IIA and IIB gases as well; the area gas group must be IIC or lower |
| T5 | Temperature class | Maximum surface temperature of 100 °C |
| Gc | Equipment Protection Level, gas, level c — the G is gas; dust uses D | Zone 2 areas only |
Two characters repeat each other on purpose. 3G is the category written for the EU ATEX directive; Gc is the EPL written for the IEC marking system that international projects follow. Both say Zone 2 for gas, so the certificate carries both. Ex nA is the older label for non-sparking construction: equipment that produces no ignition-capable arcs, sparks or hot surfaces in normal operation. Current editions of IEC 60079-7 certify the same design as Ex ec, and a certificate issued with nA stays valid for the unit it names.
Where Gc lets the panel PC run
Zones grade how often the explosive atmosphere shows up, and the EPL on the marking has to match the zone you install into.
| Zone | Explosive gas atmosphere | EPL the equipment needs |
|---|---|---|
| Zone 0 | Present continuously, frequently or for long periods | Ga |
| Zone 1 | Likely to occur occasionally in normal operation | Gb |
| Zone 2 | Not likely in normal operation; if it occurs, only briefly | Gc |
A Gc panel PC is a Zone 2 machine and nothing more. It stays out of Zone 1 walls and Zone 0 vessel interiors, whatever its housing and IP seal suggest. The three levels also differ in what they survive, which is the part installers miss: Gc assesses normal operation only, Gb holds protection through a rare fault, and Ga even through two independent faults. A Zone 1 specification asking for Gb therefore rejects an honest Gc nameplate.
North American drawings say Class I Division 2 where IEC documents say Zone 2; the areas broadly line up, but the marking systems differ. What a NEMA 4 HMI actually covers in a Class I Div 2 area walks that side, and the NEMA 4X junction box question in a Class I Division 2 area gets the same answer there as here: the environmental rating and the area approval are separate properties.
The temperature class and the ambient range
Every marking ends in a temperature class, and it is the check that quietly kills more installations than the zone does. The classes run from T1 to T6 under IEC 60079-0:
| Temperature class | Maximum surface temperature |
|---|---|
| T1 | 450 °C |
| T2 | 300 °C |
| T3 | 200 °C |
| T4 | 135 °C |
| T5 | 100 °C |
| T6 | 85 °C |
A T5 panel PC keeps every external surface at or below 100 °C under the certified conditions, and the area gas needs an ignition temperature above that. Hydrogen ignites at about 560 °C, so the T5 unit covers it with 460 °C of margin. Carbon disulfide ignites at about 90 °C and is a T6 gas; a 100 °C surface sits 10 °C too hot for it, so the panel PC that suits a hydrogen room fails a carbon disulfide room although the IIC gas group fits both.
The marking also assumes an ambient temperature range. The IEC 60079-0 default is -20 °C to +40 °C unless the certificate prints wider figures, and the range applies to the air where the equipment actually sits. In a closed outdoor cabinet in summer sun, the standard panel-cooling rule of thumb puts the inside air 15-20 °C above the outside shade temperature, which breaks a certified ambient without anyone touching a wire.
What the certificate covers, and what it leaves out
The certificate names one product in one configuration: the housing, the electrical build and the accessories in its schedule. Set the nameplate beside that schedule first, because a family resemblance is not a match. The assessment then stops at the PC's own terminals. It says nothing about the supply feeding the PC, the cable entering it or the box you mount it in. Drill extra holes in the PC's own case, or fit a connector the schedule does not list, and the marking no longer describes the hardware in your hand. Those parts fall to the installation instructions, which is why the supply question below is a table rather than a sentence.
The power supply: three cases and one decision
The classic question: does every piece of equipment in the installation need the same certificate? The answer sits in two facts — where the supply physically sits, and what the certificate and instructions say about it.
| Where the supply sits | What it needs | What you check |
|---|---|---|
| Named in the certificate or instructions | That supply, as documented | Replacements come from the maker's approved list |
| Outside the classified area (control room, MCC) | No Ex rating; an ordinary industrial supply meeting the PC's documented input voltage, current and grounding | Voltage at the PC terminals stays inside the documented range once cable drop is counted; entry and terminations per the instructions |
| Inside Zone 2, in the same cabinet | Its own Ex marking at Gc or better, or membership in the certified assembly | Its own nameplate, certificate and temperature class |
A 24 V DC DIN-rail supply in the unclassified MCC room is the normal answer and needs no Ex marking. The same supply bolted to the subpanel inside the Zone 2 cabinet is an unassessed device in a classified area. The panel PC's approval does not reach it, and wrapping it in an enclosure changes nothing, because a steel box is not an approval. Isolate and prove dead at the terminals before you wire either way.
The route that lets ordinary equipment run inside the classified area is pressurization. The purge holds clean air in the panel and interlocks the supply so nothing energizes before the purge cycle completes; the North American scheme for a Zone 2 panel is a Type Z purge. Buying Ex-rated gear instead of running a purge is the other road, and the control cabinet without purge covers that route.
Worked example: hydrogen dosing room
Assume a room in an electrolyser building classified Zone 2 for hydrogen, indoors, with summer air reaching 35 °C. The panel PC nameplate reads Ex II 3G Ex nA IIC T5 Gc, and the certificate prints the default ambient of -20 °C to +40 °C. The plant feeds it from a 24 V DC DIN-rail supply in the unclassified MCC room across the corridor. Run the five checks:
- Zone. Gc and 3G both point to Zone 2, and the room is Zone 2. Pass.
- Gas group. Hydrogen is IIC, and an IIC marking covers IIC, IIB and IIA. Pass.
- Surface temperature. T5 sets the limit at 100 °C; hydrogen ignites at about 560 °C, leaving a margin of 560 - 100 = 460 °C. Pass.
- Ambient. The 35 °C room sits under the +40 °C certificate limit with 40 - 35 = 5 °C of margin. Pass, but a heated auxiliary box would eat the difference.
- Supply. It sits outside the classified area, so it needs no Ex rating; the 24 V DC output and the cable entry follow the PC's instructions.
Decision: install the panel PC as delivered, feed it from the MCC room, and keep every heat source out of the 5 °C margin.
Where the enclosure fits
The Ex approval rides on the panel PC, not on the box around it. Our housings answer washdown water and weather, not ignition sources. The washdown wall-mount boxes are manufacturer-rated NEMA 4X-type/IP66, not UL listed; the HMI housings carry an IP65-type front seal with the display installed, manufacturer rated — for example the stainless housing for a 15 in panel PC. None of that is Ex certification, and we do not build hazardous-location enclosures. The two ratings are bought separately because they are tested separately: how the NEMA enclosure types are defined is a different series of tests from the IEC 60079 ignition work.
If the PC's certificate instructions allow an external housing, two conditions decide it: the box keeps the PC inside its certified ambient, and the cable entries keep the sealing the instructions call for. When the instructions are silent on external housings, mount the PC as delivered, because its own case is part of the assessed build. A rating that lives by its printed conditions behaves like indoor use only on a NEMA 4X rated HMI: the letters describe a tested scope, and the scope has edges.
Where the classified room also gets hosed down, washdown enclosures and HMI housings cover the water side. The cutouts for the certified connectors are set in the drawing, and custom enclosures are delivered in 10 business days from your approval of the drawing.
What to specify, case by case
| The installation you have | The decision |
|---|---|
| Zone 2 area, gas group IIC or lower, ignition temperature above 100 °C | The Ex II 3G Ex nA IIC T5 Gc panel PC installs as certified, supply in the unclassified area |
| Zone 2 area with a T6 gas such as carbon disulfide, ignition about 90 °C | The PC misses the temperature check by 10 °C; specify a T6-rated unit |
| Zone 1 or Zone 0 location | Gc is outside its scope; specify Gb or Ga equipment, or a purged panel |
| Supply outside the classified area | Any supply meeting the PC's documented input; no Ex rating on it |
| Supply inside the Zone 2 cabinet | Its own Gc-or-better marking, or it lives in the certified assembly or a purge |
| Washdown and Zone 2 on the same job | Environmental housing and Ex device are separate purchases; the certificate's conditions rule the combination |
Order the certified panel PC with the supply its instructions name, keep the unclassified supply outside the room, and set the nameplate beside the certificate before the first terminal lands. When the display needs a washdown housing around it, send the outline and connector positions and the cutouts get set in the drawing; the Ex approval stays with the PC and the washdown rating stays with the box.
Enclosures in this article
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 15" HMI enclosure | 304 stainless | 12.91 x 16.06 x 3.88 in | IP65-type front seal with the display installed, manufacturer rated; not UL listed |
Questions
What EPL covers dust instead of gas?
Dust has its own scale: Da for Zone 20, where combustible dust is present continuously, frequently or for long periods; Db for Zone 21, likely occasionally in normal operation; Dc for Zone 22, not likely and only for short periods. A panel PC marked Gc is gas equipment only. In a dust area, the marking needs the matching D level as well.
Does an IIC marking cover a propane area?
Yes. The gas groups run IIA for propane, IIB for ethylene and IIC for acetylene and hydrogen, in rising ease of ignition. Equipment marked IIC covers all three groups; IIB covers IIB and IIA; an IIA marking covers IIA only. Read the gas group from the area classification, then keep the marking at or above it.
Can the power supply sit inside a purged cabinet?
Yes, and that is the standard way to run ordinary equipment in a classified area. The purge holds clean air or inert gas in the enclosure and interlocks the power, so the panel cannot energize before the purge cycle completes. With a valid purge system in place, the PC and its supply need no Ex marking of their own; the purge approval becomes the one that matters.
What ambient range does an Ex marking assume?
The IEC 60079-0 default is -20 °C to +40 °C unless the certificate prints a wider range. Outdoor-certified units are often extended to +50 °C or +60 °C, and the exact figures sit on the certificate, not the nameplate alone. Compare the printed upper limit with the warmest air at the mounting point; inside a closed cabinet in the sun that air can run 15-20 °C above the outside shade temperature.





