Divider between 24 VAC control and 120/240 V in an SSR enclosure

A grounded metal barrier is required when the 24 VAC control side is a Class 2 limited-energy circuit: a listed Class 2 source of 100 VA or less. Class 1 control wiring needs only spacing. Size the SSR compartment for about 1.2 W per ampere of load: a 3 kW, 240 V heater adds 15 W, a 7.6 K rise in a 16 x 12 x 8 in stainless box; at 35 C ambient, step up a size to hold the interior near 40 C.

NEMA4 Enclosure engineering team · Published November 24, 2026 · 8 min read

Short answer: yes — when the control side of a solid-state relay is a Class 2 circuit at 24 VAC, the NEC wants it separated from the 120/240 V line side by a metal barrier or a divided compartment. A listed Class 2 transformer of 100 VA or less makes it Class 2. Feed the control side as Class 1 from a larger source and the barrier becomes the cheapest fault protection you can bolt in. It keeps a failed line-side terminal off the thermostat and pilot wiring. This article gives the decision rule, the divider build for a 16 x 12 x 8 in [406 x 305 x 203 mm] stainless box, the wiring order, the SSR heat load and the checks that close the job.

Is a divider required between 24 VAC control and 120/240 V line wiring?

Yes when the control side is Class 2. It usually is, because a listed Class 2 transformer puts everything downstream under a 100 VA and 8 A ceiling on the source, at 30 V AC or less.

The NEC's Class 2 rules bar limited-energy conductors from sharing a raceway, duct or compartment with power conductors. A metal barrier between the two lifts that bar. A junction box holding an SSR is one compartment until you bolt the plate in, so the plate is what completes the separation.

Feed the control side as Class 1 — a 250 VA control transformer with fused secondary, for instance. Then the barrier becomes the practical choice rather than a code demand. Keep 2 in [50 mm] between control runs and line conductors and cross them at right angles. That spacing is panel practice for keeping switching noise out of low-voltage wiring. The plate still earns its bolts in a Class 1 box: a shorted relay or a burnt line terminal puts full line voltage across wiring sized for 24 V.

One rule covers both layouts. Conductors of different voltage systems sharing an enclosure all carry insulation rated for the highest voltage present, and 600 V building wire covers a 240 V line side with room to spare. The mixed-voltage cabinet has its own write-up in 120 V and 220 V AC in the same control cabinet. Sharing a raceway is where most divider questions really land. Running low-voltage and high-voltage conductors in the same conduit sets out why the two belong apart.

What makes the control side Class 2?

The source decides the class, not the wire. A control transformer listed and marked Class 2, delivering 100 VA or less at 24 VAC with no output above 8 A, makes everything downstream of its secondary Class 2 wiring.

HVAC-style transformers of 40, 50, 75 and 100 VA at that voltage are the usual Class 2 sources, and the manufacturer marks the limit on the body. Pick a 250 VA transformer instead and protect it as its instructions ask, and your control wiring is Class 1. It is still low voltage, but outside the limited-energy ceiling, so spacing practice takes the place of the barrier. The SSR input belongs on the control side either way: a 24 VAC input typically draws 10 to 25 mA, under 1 W, and it sits behind the plate with the transformer secondary. Mark where Class 2 begins, at the transformer's secondary terminals, so the next hand in your box keeps each circuit on its own side.

How do you build the barrier between the two compartments?

Bolt a metal plate across the full section of the box and bond it to the enclosure ground. For a 16 x 12 x 8 in [406 x 305 x 203 mm] 304 stainless body, a 2 mm [0.08 in] plate on 4 in [100 mm] screw centers is a working example.

The plate splits the box into a line compartment and a control compartment while both stay inside the one gasketed envelope, so the assembly keeps its water rating. Order the depth so each side keeps about 3 in [75 mm] of working room behind the plate. In the 8 in example, the line half holds a wall-mounted SSR and its terminals; the control half holds the transformer secondary, the input pair and a small terminal strip.

When a plate fights your layout, two alternatives work: two smaller enclosures joined by a conduit nipple, or one deeper custom body that takes the plate as a bolt-in rather than a field cut.

Place each compartment's wall openings before anything is cut. The cutout designer lays out glands and operators per face and sends the layout with the quote. Custom stainless enclosures with factory cutouts compares a standard body with new openings against a fully custom one. The custom builder takes your material, width, height and depth from one piece, delivered in 10 business days from your approval of the drawing. A line-side gland that pierces into the control compartment undoes the division: each entry opens into its own compartment only.

How do you wire and ground each side?

Wire the line compartment first, land every conductor on insulation rated for the highest voltage in the box, and bond the plate to the ground bus before any Class 2 pair comes near it.

  1. Mount the SSR base to the backplate or side wall with thermal compound; the metal is the heatsink, and a dry or loose base is the top reason an SSR runs hot.
  2. Land the 120/240 V line and heater-load conductors in the line compartment, with their bends clear of the terminal zones.
  3. Bond the plate to the ground bus with an equipment grounding conductor sized from NEC Table 250.122 by the overcurrent device ahead of the circuit — 12 AWG copper covers a 20 A device. Stainless bodies ship bare, so the lug lands on clean metal; on a painted body, NEC 250.12 requires paint removed from threads and contact surfaces at bonding connections. The grounding and bonding guide covers bus and conductor layout, and armored cable or shields earn their own gland earthing, as why cable gland earthing is required explains.
  4. Run the Class 2 pairs inside the control compartment only, from the transformer secondary through the plate's grommeted pass-through to the SSR input; the two circuits never share a wiring duct.
  5. Fit each compartment's glands at its own openings and cap every spare one; a single open gland sits the assembly below its NEMA 4X / IP66 rating, because the weakest part sets the rating.
  6. Close the door on an even gasket line and pull the screws down in a cross pattern; a pinched corner gasket is where washdown water gets in.

How much heat does the SSR put into the box?

A solid-state relay wastes about 1 to 1.2 W per ampere switched — the SSR datasheet rule of thumb. A 3 kW, 240 V heater load therefore puts roughly 15 W into the box, about an 8 K rise in a 16 x 12 x 8 in stainless enclosure.

Worked example, for a 3 kW resistive heater at 240 V single phase:

  • Load current: I = 3,000 W ÷ 240 V = 12.5 A.
  • SSR loss: 12.5 A × 1.2 W/A = 15 W, and the 24 VAC input adds under 1 W.
  • Box surface: the 16 x 12 x 8 in [406 x 305 x 203 mm] body presents about 0.537 m².
  • Rise at the stainless wall value of 3.7 W/m²K: 15 W ÷ (3.7 W/m²K × 0.537 m²) = 7.6 K.
  • Interior air: about 33 C at a 25 C ambient, about 43 C at 35 C.

Decide on the numbers. Size the SSR at twice the load or better, 25 A for this 12.5 A heater — the doubled margin SSR application guides ask for heater loads. Load current moves the rise linearly, box area moves it inversely, and the 1.0 W/A lower figure trims the loss about 20%. At a 35 C ambient, order the 20 x 16 x 8 in [508 x 406 x 203 mm] body instead: 0.784 m² gives 15 W ÷ (3.7 W/m²K × 0.784 m²) = 5.2 K, which holds your interior near 40 C (104 F). The SSR datasheet's derating curve above 40 C sets the final margin, and how to size an electrical enclosure walks the full heat and space calculation.

Where can the SSR sit when the heater is in a Class I Division 1 area?

Keep the switching outside the classified boundary. In Division 1, every enclosure and device inside the line must carry the Division 1 certificate. A general-purpose stainless box — rated NEMA 4X / IP66 by the manufacturer; not UL listed — is not that equipment.

In US workplaces, OSHA 29 CFR 1910.303(a) requires electrical equipment to be approved, and 1910.399 defines acceptable as equipment accepted, certified, listed or labeled by a nationally recognized testing laboratory. Division 1 zones take explosion-proof apparatus certified for Division 1, and those hazardous-location enclosures are not something we build. Put the SSR enclosure outside the boundary and run conduit in, and any 304 or 316L stainless body serves the duty.

Division 2 relaxes one step. The NEC allows apparatus that makes no arcing contacts in normal operation to sit in a general-purpose enclosure, and a solid-state relay switches with no contacts at all; that is why relay panels cluster just outside zone edges. The allowance attaches to the installed assembly, so your inspector signs the layout — bring the SSR datasheet showing the contactless output. A NEMA 4X rating answers water and corrosion, and Division 1 certification answers ignition; order each by name.

What do you check before you close the door?

Check four numbers with the door open and one after the first half hour at full load, and the layout holds both its rating and its separation.

  • Secondary voltage at the SSR input: 26 to 28 VAC off load, since a Class 2 secondary runs high unloaded, staying near 24 VAC while the relay conducts.
  • Load current: 12.5 A in the example, against an SSR rated 25 A or more.
  • Bond: plate to ground bus reads under 0.1 Ω with your meter leads zeroed.
  • Entries: every gland made up and every spare opening capped, because one open hole and the assembly is no longer a NEMA 4X / IP66 box.
  • Heat: after 30 minutes at full load, interior air sits near the calculated 33 C at a 25 C ambient; a reading far above it points to a dry SSR base.
  • Separation: the only conductor crossing the plate is the secondary pair through its grommet, and no duct carries both circuits.

Three mistakes cost people this job. One gland or one duct carrying both circuits ends the separation the plate provides. A fan-filter or open vent added for cooling drops the assembly below Type 4X, so take the heat out with a bigger body instead. A bonding lug left off the plate leaves the barrier floating and the fault path broken.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
20 × 16 × 8 in304 stainless20 x 16 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Does the Class 2 barrier rule cover wiring duct inside the enclosure?

Yes. The NEC's Class 2 separation rule covers raceways and ducts as well as compartments, so the limited-energy pairs get their own duct run on the control side. Duct makers cap fill at 50% of the duct's interior cross-section, citing NFPA 79 section 13.5.2; the other 50% is the air space between round cables.

What changes if the low-voltage control circuit is intrinsically safe?

Intrinsic safety sets stricter separation than the Class 2 barrier: the NEC keeps intrinsically safe conductors apart from all other circuits, by spacing or by a grounded partition. An SSR control circuit is not intrinsically safe. IS describes circuits limited so a fault cannot release enough energy to ignite the atmosphere. A 24 VAC supply of up to 100 VA sits far above those energy levels.

Can one enclosure carry several SSRs behind one barrier?

Yes — add the heat before you size the box. Three SSRs each switching a 12.5 A heater dissipate 3 × 15 W = 45 W; in a 20 x 16 x 8 in body that is 45 ÷ (3.7 × 0.784) = 15.5 K, about 41 C inside at a 25 C ambient. At 35 C ambient, move up a body size.

Which side of the barrier does the control transformer sit on?

The line compartment. The transformer's primary is 120/240 V, and Class 2 begins at its listed secondary terminals. The primary and its fuse stay on the line side while the 24 VAC secondary pair passes through a grommeted hole in the plate. Leave the terminal covers on and land nothing else in that opening.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Build it from 16 × 12 × 8 inRequest a custom quote

NEMA 4X enclosures: sizes for this job

Keep reading

More on layout and installation

All articles

Buying guides

The guides behind this answer

All guides