Short answer: DIN EN 60715, the standard behind TH35 rail, fixes the geometry — 35 mm [1.38 in] wide, hat 7.5 mm or 15 mm deep — and sets no force limits. The snap-on push and the pull-off retention live in the mechanical data of the housing datasheet, one set of numbers per housing. This article works the arithmetic with two labelled assumptions, 40 N to snap on and 50 N of pull-off retention, so you can see the method; swap in your datasheet's printed values before you freeze a design. With those assumptions and a 3x vibration allowance, one snap-on foot carries about 1.7 kg [3.7 lb], and heavier gear goes on a screw-mounted adapter.
What does DIN EN 60715 cover for a TH35 rail?
It covers dimensions and compatibility, full stop: the top-hat profile with its two hat depths, slotted fixing holes, and the tolerances that let any compliant housing snap onto any compliant rail.
IEC 60715, published in Europe as DIN EN 60715, covers the dimensional and functional side of mounting switchgear, controlgear and accessories on rails, and its appendix prints the dimensions and manufacturing tolerances of the steel rails that meet it. You will also meet the profile under its old number, EN 50022 — same top-hat, same foot. Device widths on the rail are counted in modules of 18 mm [0.71 in], so a row of 32 modules runs 32 × 18 mm = 576 mm [22.7 in].
| Rail per DIN EN 60715 | Profile | Where you meet it |
|---|---|---|
| TH35-7.5 | 35 mm wide, 7.5 mm hat depth | Terminal rows, relays, small electronics |
| TH35-15 | Same width, 15 mm hat depth | Same foot, stiffer over long spans |
| TS32 | 32 mm C-profile | Older panels, some switchgear |
| TS15 | 15 mm width class, 5.5 mm deep | Light-duty, low-profile assemblies |
Feet marked TH35 fit both hat depths: the lips the foot grips are identical, and the deeper hat simply stiffens a long span and stands the row a little prouder of the plate. What the standard leaves to the housing maker is the latch itself. Two housings can both be TH35-compliant and hold very different loads, because each spring foot is one maker's design in that maker's plastic or steel — which is why the force question always lands on the housing datasheet.
Where do the snap-on and pull-off numbers come from?
From the housing datasheet's mechanical data, stated in newtons for that one housing on a TH35 rail — the rail standard contributes nothing to the force numbers.
Open the mechanical data page of the housing in question — terminal block, relay, power supply — and look for two lines. One is a mounting or engagement force, which is what you apply to latch the foot. The other is a pull-off or retention force in newtons, which is what the latched foot holds against on a TH35 rail. Removal is a third and different action: you lever the foot open with a screwdriver, so a removal figure describes that deliberate unlatch, a load case apart from what the foot carries in service. When a sheet lists no force at all, one e-mail to the housing maker closes the gap before the build spec is written.
Wire-side retention is a number of its own, set by the clamp type. The choice between spring-clamp and screw clamp terminal blocks is worth making early, because it changes both the wire pull-out value and your wiring time.
How much force should snapping a housing on take?
A firm thumb push — about 20 to 40 N in this article's worked example — and an audible seat at the end; if you reach for a mallet, the profile, the finish or the orientation is wrong, not the housing.
A terminal housing or a small relay seats with one push and a click, and that band here is the example; your datasheet's mounting force is the real figure. When the housing fights you, measure before you force it:
- Profile. The standard width across, 7.5 or 15 mm deep — a TS32 or TS15 rail looks close and takes a different foot.
- Finish. Paint or heavy zinc on the lips and in the slots.
- Burr. The cut end of the rail needs a flat file pass before the first housing goes on.
- Orientation. Slotted back against the plate, lips facing out.
Forcing a foot over the wrong profile cracks it, and the crack finds you later as the housing lying in the bottom of the panel.
How much weight can one snap-on DIN foot hold?
About 1.7 kg [3.7 lb] per foot, using the assumed retention and a 3x vibration allowance; the rule is mass = retention ÷ (allowance × 9.81 m/s²), so a housing rated 20 N stops at 0.68 kg [1.5 lb].
Take a 0.75 kg [1.65 lb] DIN rail power supply on one snap foot, rail running vertically in the panel:
- Weight force along the rail: 0.75 kg × 9.81 m/s² = 7.4 N.
- Static margin: 50 N ÷ 7.4 N = 6.8.
- With the ×3 allowance: 7.4 N × 3 = 22 N, still under the assumed retention, so the foot keeps it.
- The same supply at 2.0 kg: 2.0 × 9.81 × 3 = 59 N, over the assumed value — that unit moves to a screw-mounted DIN rail adapter.
On a horizontal rail the weight pulls straight out of the rail, the exact direction the retention figure covers. On a vertical rail it shears down instead, and using the pull-off figure as the limit is the safe side, because it is the weakest number the latch is given.
Now the terminal row beside it: 24 terminals at 22 g each make 0.53 kg, or 5.2 N spread over 24 feet. Each foot sees 0.022 kg × 9.81 = 0.22 N of terminal weight, so terminals are never the pull-off risk; heavy single devices and cable tension are. Keep the bundle's tension off the feet — the gland and the duct carry it, and a service loop inside the box means the only force on a foot is the device itself. Duct and rail placement settles that before you cut anything.
The decision in one line: about 1.7 kg per foot at the assumed retention and ×3 shaken; above that, bolts hold the device.
How do I check a TH35 rail before loading it?
Measure three dimensions — the width across the back, 7.5 mm [0.30 in] or 15 mm [0.59 in] from the plate to the lips, slotted holes along the centre — and read any marking that says TH35, EN 60715 or the older EN 50022.
Ten seconds with calipers settles the profile: the full width across the back, the hat depth to the lips, long slotted holes along the centre of a galvanised steel section. Cut the row to your module count, file the cut end flat, and fix the rail to the plate with its slotted back down — mounting DIN rail on a backplate covers the spacing and the fixings. Match the box to the parts while you are at it: housing depth plus rail and wiring space sets the minimum enclosure depth, and the guide to enclosure depth for DIN rail devices gives you that number.
What changes when the panel moves or vibrates?
Only your vibration allowance: multiply each weight force by it and re-run the mass rule — the 0.75 kg supply at ×3 pulls 22 N against the assumed retention and stays on its foot, while a 2.0 kg unit pulls 59 N and moves to screws.
Say the allowance on the drawing and use one rule for every device: mass = retention ÷ (allowance × 9.81). A static wall panel works at 1, because the static margin already covers it; a machine-mounted cabinet is the ×3 case worked above; a pendant station that gets knocked in use deserves more. End anchors belong at both ends of every loaded row — they stop the row creeping along the rail when you lever off an end terminal, and they add nothing to pull-off, which pulls a housing off the rail rather than along it. Light boards are a case of their own: DIN rail mounting for single-board computers covers the carrier plates that keep a small board rigid on the rail.
What should the enclosure order say?
Four lines: the rail profile, the row lengths in modules, end anchors on loaded rows, and which devices go on screw-mounted adapters — that is everything a builder needs to populate the backplate to your layout.
In the enclosure builder you tick DIN rails as a fitted option and set your row positions. On the custom enclosures route you choose material, width, height, depth and every cutout, and the box is delivered in 10 business days from your approval of the drawing. Whatever box you choose — our stock stainless ones are rated NEMA 4X / IP66 by the manufacturer and not UL listed — the rail forces stay the housing datasheet's numbers, so keep both references on the same drawing.
| On the order | What to write | Worked-example value |
|---|---|---|
| Rail | Profile and hat depth | TH35-15 per DIN EN 60715 |
| Rows | Length in modules | 32 modules = 576 mm |
| End anchors | Which rows get them | Both ends of every loaded row |
| Heavy devices | How they mount | Screw-mounted adapter, not a snap foot |
| Forces | From the housing datasheet | Snap-on 40 N, retention 50 N |
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is EN 50022 the same rail as DIN EN 60715 TH35?
Yes — EN 50022 is the old number for the same profile, so a housing marked for either fits both. They describe the same 35 mm wide top-hat rail with a 7.5 mm or 15 mm deep hat, and neither document carries latch force values; those stay in the housing datasheet.
Can I hang a 1 kg power supply on a snap-on DIN rail foot?
Run the rule: mass limit = retention ÷ (vibration allowance × 9.81). At this article's assumed 50 N retention and a ×3 allowance the limit is 1.7 kg, so 1 kg passes at 29 N of effective load with room to spare; at 20 N retention the limit falls to 0.68 kg and the same supply needs a screw-mounted adapter.
Why is my terminal block so hard to push onto the DIN rail?
Most often the rail is the wrong profile: measure the width across the back and the depth to the lips before blaming the housing. Paint in the slots, a burr at the cut end, or a rail mounted with the lips against the plate give the same fight. A true TH35 foot seats with a thumb push, about 20 to 40 N in this article's example.
Do end brackets increase the pull-off force a rail can hold?
They stop sliding, and they add nothing to pull-off. End brackets block movement along the rail, which matters when you lever off an end terminal or when vibration walks a row sideways; pull-off pulls a housing off the rail and stays the datasheet figure. Fit them on loaded rows — a 32-module row is 576 mm of housings that otherwise creep.
What force value should a panel build spec state for DIN rail mounting?
Write the datasheet's own figures, per housing, next to the rail call-out — for example 'snap-on force 40 N max, pull-off retention as printed, TH35 per DIN EN 60715', replacing 40 N with the printed values. If a datasheet carries no force line, get the number from the housing maker before the spec is issued; the rail standard supplies none.