Short answer: make every rebar-to-conductor bond with an exothermic weld or a compression connector marked and listed for concrete encasement or direct burial. Test each joint while the rebar cage is still open. Tie wire and standard bolted clamps are not listed connections, and once the concrete is placed the joint is unreachable — you cannot inspect, repair or replace it without cutting concrete. Your drawing sets the conductor size, the bond count and the exit point; the method is yours to run. Bare the steel to bright metal, match the mold or die to the bar and conductor, photograph every joint, and take a milliohm reading — 25 ft [7.6 m] of 4 AWG copper should read about 6 mΩ — before you release the pour.
What the NEC asks of the rebar bond
"Bond the rebar to the grounding system" turns your foundation into a concrete-encased electrode. The NEC describes one as at least 20 ft [6 m] of bare or zinc-coated steel reinforcing bar, 1/2 in [13 mm] in diameter or larger, under at least 2 in [50 mm] of concrete. Most slabs and footings already carry that steel. Recent NEC editions add a clarification that decides your bond points: the stub you connect to must be electrically continuous with the electrode rebar, or securely connected to it. A bar that runs out over a form is not a bond point; use bars tied or welded into the continuous mat the structural drawings identify.
Two conductors meet at this foundation. The grounding electrode conductor runs from the rebar to the service disconnect, and the NEC sizes it from the largest service-entrance conductor. The earth does none of the fault work: NEC 250.4(A)(5) calls the fault path metallic, and the earth is not considered part of it. The rebar bond is an electrode connection, not a path through soil.
Weld or listed compression: pick the joint
| Criterion | Exothermic weld | Listed compression connector |
|---|---|---|
| Joint type | Copper-to-steel fusion, no mechanical interface | Crimped barrel with a matched die and tool |
| Listing to check | Connection system marked for the application | Connector marking lists concrete encasement or direct burial |
| Bar and mold prep | Bright, dry steel; a wet bar or mold gives a porous weld | Bright steel; tolerates a damp cage |
| Heat into the bar | Local heat; needs the structural engineer's written OK | None |
| Pass criteria | Full button, conductor encapsulated, no porosity | Die mark in position, conductor not slipped |
| Best when | Dry cage, experienced crew, engineer accepts heat | Wet weather, coated bars, heat refused |
Order the weld mold against your bar diameter and conductor size: a #5 bar, 5/8 in [16 mm], with 4 AWG cable takes its own mold, and the grounding-component catalog cross-references the pair. Default to the weld. It fuses copper to steel with nothing left to loosen, and it outlives the concrete. Switch to compression when your structural engineer refuses heat on the bar, when rain keeps the cage wet, or when your crew has little weld experience. The reaction runs above copper's melting point, 1,984 °F [1,085 °C], but only inside the button it casts — still hot enough that the engineer signs off first. The same weld-versus-bolted choice recurs wherever electrodes stay buried; the bolted versus exothermic ground electrode connections for test wells comparison walks it for ground test wells.
What you need on site
- The bonding conductor in the size and length the drawing shows — bare copper; the worked example below runs 4 AWG
- An exothermic kit: molds matched to your bar and conductor, cartridges, mold holder, igniter, slag brush and a flame for drying the mold
- Compression connectors listed for concrete encasement or direct burial, with the crimp tool and dies matched to those connectors
- A 4-wire micro-ohmmeter or low-resistance ohmmeter; a handheld meter resolves 0.1 Ω, 200 times too coarse for a 0.5 mΩ joint section
- A wire brush or flap disc to bare the bar, plus a stripping tool where bars are epoxy-coated
- Plastic chairs and tie wire for support alone, never as the electrical joint
- A camera, marker and cage sketch for the photo record
Make the bond, step by step
- Pull the bond data from the drawing: conductor size and length, number of bond points, and where the conductor exits the foundation inside the building footprint. Chase anything missing to the engineering firm in writing.
- Walk the cage and confirm the chosen bars are tied or welded into one continuous mat, per the structural drawings, before you treat them as one electrode.
- Get the structural engineer's written OK for exothermic heat on the bar, and file it with the job book.
- Check each connector or mold against its marking — listed for concrete encasement or direct burial — and against your bar diameter and conductor size at that point.
- Bare the steel: brush mill scale, rust and slurry back to bright metal, and strip epoxy clear past the joint area on coated bars.
- To weld, flame-dry the mold, clamp it over bar and conductor, load the cartridge and ignite. Look for a full button with the conductor encapsulated and no porosity; cut off and redo any suspect weld while you can still reach it.
- To crimp, seat the conductor fully in the barrel, close the matched die, and confirm the die mark sits in position with no conductor slippage; pull-check the conductor where the connector's procedure calls for one.
- Run the conductor to the exit on chairs, clear of the forms, and support it so placement and vibration cannot work the joints.
- Photograph every bond and mark its location on the cage sketch.
- Test each section with the numbers in the next section, redo any failure, then release the pour.
Test the joint while the cage is open
Work the numbers before the concrete moves. Say your drawing calls 4 AWG [21 mm²] bare copper run 25 ft [7.6 m] from the rebar stub-up to the ground bus. The NEC's conductor resistance table lists 4 AWG copper at 0.2485 Ω per 1,000 ft at 20 °C, so the run alone reads 25 × 0.2485 ÷ 1,000 = 0.0062 Ω, about 6 mΩ. A sound weld or crimp adds almost nothing you can measure, so 6 to 7 mΩ across the whole run is your pass line at room temperature.
Break the run into sections at your test points. A 2 ft [0.6 m] length of 4 AWG reads 0.2485 × 2 ÷ 1,000 = 0.50 mΩ. A practical bench rule: redo any section reading more than ten times its neighbour. A section at 5.5 mΩ beside a 0.5 mΩ section is eleven times the reading, so that joint comes off while the cage stands open.
After the pour and cure, measure from the stub-up to the ground bus and compare with the baseline. Copper resistance rises about 0.39 % per °C, so that 25 ft run reads about 7.5 mΩ at 75 °C; a post-pour reading that tracks the copper says the embedded joints held. Then test earth resistance at the completed electrode. The NEC's benchmark for a single grounding electrode is 25 Ω, and industrial specifications commonly tighten the target to 5 Ω. Record the readings with the bond photographs in the commissioning file.
Mistakes that bury a bad bond
- Counting tie wire as the bond. Tie wire holds the cage together, and its contact relaxes and corrodes inside concrete; it carries fault current only by accident.
- Welding wet or dirty steel. Moisture in the mold or on the bar makes porous buttons; flame-dry both, or crimp instead.
- The wrong mold or die. A mold sized for a #4 bar, 1/2 in [13 mm], over a #5 bar, 5/8 in [16 mm], casts a weak joint that still photographs well.
- Epoxy left in the joint path. Coating blocks metal-to-metal contact; strip it back before you weld or crimp.
- An exit nobody marked. Fix and protect the stub-up before the pour; a bond with no reachable conductor end cannot reach the ground bus.
- Releasing the pour early. The inspection happens once. After placement, the joint is permanent.
From the stub-up to the ground bus
The bond ends at the building's ground bus, and the landing matters as much as the weld. Land the grounding electrode conductor on the service enclosure with the right connector, as covered in how the grounding electrode conductor bonds to a service enclosure. Where the conductor enters any enclosure, fit a listed connector and keep the contact metal-to-metal; the details live in the connector and bond at a grounding conductor's enclosure entry. NEC 250.12 requires paint, lacquer and enamel to come off threads and contact surfaces at grounding connections, so brush the landing point back to bare metal. Feeders onward to panelboards carry their own EGC sized from the overcurrent device ahead of them, as in the sizing note above — the same logic behind the EGC you run from the service disconnect to a subpanel.
If a junction box is cast into the same concrete, its entry and cover need their own decisions: see what to specify when a junction box is embedded in concrete. The panels then live in enclosures that sit on this electrode, indoors or out; the outdoor stainless enclosures range covers the wall-mount and HMI cases. The whole chain, from enclosure bond to buried electrode, is laid out in the enclosure grounding and bonding guide.
Decision: exothermic weld every embedded bond by default — dry cage, continuous mat confirmed, engineer's written OK. Switch to compression connectors listed for concrete encasement where heat is refused or the cage is wet. Either way, the pour moves only after every joint passes its milliohm check.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a bolted clamp bond rebar instead of a weld or crimp?
Only when the clamp's own marking lists it for concrete encasement or direct burial. Standard above-ground clamps hold by screw pressure alone, and a cast-in joint cannot be re-torqued, so unmarked clamps stay out of the concrete. Keep bolted connections where they belong: at the accessible ground bus or a test well, where you can reach them with a wrench. Every joint you cast in gets a weld or a listed compression connector and its milliohm reading before the pour.
Does exothermic welding damage the reinforcing bar?
The reaction runs above copper's melting point, 1,984 °F [1,085 °C], but the heat stays inside the button it casts and a small length of bar around it. The structural engineer decides in writing whether that local heat suits the bar, and usually refuses it on lightly reinforced or fatigue-critical work. Where heat is refused, a listed compression connector makes the same bond cold with a crimp tool and matched die, and the bar never sees a flame.
What size conductor bonds the rebar to the grounding system?
The drawing sets it, and the NEC's grounding electrode conductor table backs the number: a building fed with 3/0 AWG copper entrance conductors takes a 4 AWG [21 mm²] copper electrode conductor to the rebar. Inside the building, feeder EGCs size from the overcurrent device ahead of them per NEC Table 250.122 — 8 AWG copper behind a 100 A breaker. If a size is missing from the drawing, get it from the engineering firm in writing before you cut conductor.
How do you test the bond after the concrete cures?
Compare the post-cure reading from the stub-up to the ground bus with your pre-pour baseline, temperature-corrected. The 25 ft of 4 AWG in the example moves from about 6 mΩ at 20 °C to about 7.5 mΩ at 75 °C, at roughly 0.39 % per °C. Then measure earth resistance at the completed electrode: 25 Ω is the NEC's benchmark, and industrial specifications commonly tighten the target to 5 Ω or less. Log both readings with the bond photographs.





