Pick the gland size from the bedding and overall cable diameters first, because those two run the two seals. Then hold the armour wires against the gland's printed armour window, typically 1.5-3.25 mm (0.06-0.13 in) on a 20 mm SWA gland, and read the exact window from the datasheet of the gland you buy. A wire 0.1 mm under the window leaves the clamp riding past the armour; a wire above it drives the clamp into the bedding. Either way the termination slips, and the armour earth path goes with it. The whole check is three caliper readings against three printed limits, five minutes on the drum before you cut a hole.
The three diameters the gland has to hold
An SWA gland holds the cable at three diameters, and each one does a different job. The outer seal grips the sheath at the overall diameter; that seal keeps water out of the box, and it must bite the sheath itself, as the cable gland clamping range article sets out. The armour clamp grips each steel wire on its own diameter, and that grip carries two duties at once. It gives strain relief against the pull load, and it forms the metal-to-metal clamp that bonds the wires to the gland body so the armour reaches panel earth, the path traced in the grounding and bonding guide. The bedding maximum is the largest under-armour core that still seats under the clamp cone. For the part names and the anatomy, start with the article on what a cable gland does for an enclosure.
The three readings also have to agree with one another. A single layer of round wires resting on the bedding adds about one wire diameter to the radius, so the over-armour diameter lands near bedding + 2 × wire diameter. The oversheath adds its own wall on top of that. A cable with 13.0 mm bedding and 2 mm wires should therefore read about 17.0 mm over the armour; an overall reading far from the prediction points to a slipped caliper, not a gland problem.
How to read the gland table
Every published SWA table gives each gland size three limits: a bedding maximum, an overall diameter range for the two seals, and an armour wire window. The entry thread decides the hole in the wall and how the gland seals to it; the cable windows decide the cable. That separation is why a thread adapter cannot rescue a cable that misses a window. Limits move between series, so take them from the datasheet of the gland you buy.
To show how the check runs, the table below carries illustrative values typical of a published metric SWA series; the numbers that decide your order come from your gland's own datasheet.
| Gland size | Bedding maximum | Overall range | Armour wire window |
|---|---|---|---|
| M16 | 11.0 mm | 12-18 mm | 1.0-2.0 mm |
| M20 | 14.5 mm | 17-24 mm | 1.5-3.25 mm |
| M25 | 21.0 mm | 22-30 mm | 2.5-4.0 mm |
| M32 | 26.0 mm | 28-36 mm | 3.0-5.0 mm |
The common miss is choosing the size on overall diameter alone: the seal fits and the armour clamp does not. The entry thread on these sizes is the metric fine pitch, M20 × 1.5 on the 20 mm line. Metric versus NPT thread at the wall is its own decision, covered in the gland thread comparison.
The worked check: 20 mm gland on a 20.2 mm cable
Take a 3-core 10 mm² 0.6/1 kV SWA/PVC cable on the drum. Calipers across the stripped-back bedding read 13.0 mm; a single armour wire reads 2.0 mm; the overall over the sheath reads 20.2 mm. Run the cross-check first: over-armour = 13.0 mm + (2 × the wire reading) = 17.0 mm, so the sheath wall works out at (20.2 mm − 17.0 mm) ÷ 2 = 1.6 mm per side, a believable PVC build for this size. The three readings agree, so the bedding figure is trustworthy.
Now the M20 line. Bedding 13.0 mm against a 14.5 mm maximum leaves 1.5 mm. Overall 20.2 mm sits inside the 17-24 mm range, 3.2 mm above the bottom and 3.8 mm below the top. The wires sit inside the 1.5-3.25 mm window, 0.5 mm above the floor and 1.25 mm under the ceiling. All three pass with margin, so the order is one M20 SWA gland, and the hole is a single M20 × 1.5 clearance on the bottom face. Lay it out with the cutout designer and the spacing guidance in the cutouts, glands and windows guide.
When the wires sit outside the window
Wires under the window floor are the usual miss on small cables. Put the same M20 gland onto a cable with 1.25 mm wires: the clamp cone closes past them and touches only the bedding, so the gland looks fitted while the first firm pull walks the armour out. The fix is a smaller gland, and the whole check reruns on its line. The same cable measured at 9.8 mm bedding, 14.7 mm overall and 1.25 mm wires fits the M16 row, whose window starts at 1.0 mm, with 0.25 mm of floor margin. Isolate the panel and prove it dead before stripping a fitted gland to re-terminate it.
Wires over the window ceiling fail the other way: the clamp ring bridges from wire to wire and the lock nut bottoms without gripping, and more torque just cuts the wires into the bedding. A cable reading 20.0 mm bedding, 3.5 mm wires and 29.8 mm overall misses the M20 twice, on bedding and on armour. The M25 row clears the wires at 3.5 mm against a 2.5-4.0 mm window but leaves only 0.2 mm at the top of its 22-30 mm overall range, too tight for a cable that varies with ovality and temperature. Take the M32 row instead: 20.0 mm bedding under a 26.0 mm maximum, 29.8 mm inside 28-36 mm, 3.5 mm wires with 0.5 mm of floor and 1.5 mm of ceiling margin.
When a wire lands within 0.1 mm of a window edge, treat the fit as a miss and change size; we work to at least 0.2 mm at each end of the armour window and 1 mm at each end of the overall range. The window applies per wire, not per bundle, and it applies the same to aluminium wire armour on single-core circuits, measured wire by wire the same way.
Why the printed windows are hard limits
IEC 62444, the standard that metric glands for steel and aluminium wire armour are built to, has the maker declare the maximum over-armour diameter the gland accepts. Its termination test runs on a 300 mm (about 12 in) length of cable at that declared maximum. The printed windows are the basis the gland was proven on, so a cable outside them sits outside the proof, whatever the torque wrench says.
On flameproof and increased-safety glands the windows are part of the certificate: the sealing ring and the armour chamber have fixed dimensions, and the certificate is built on those dimensions. That is where armour retention gets inspected as a routine; the Ex d gland armour-retention inspection page shows what to look for. On ordinary industrial glands the logic is the same with less paperwork: the ranges are what the maker stands behind.
What to put on the order
Send the three measured diameters with the gland line so the supplier's window check is arithmetic instead of guesswork. The box itself we build to your drawing and deliver in 10 business days from your approval of the drawing, so put the gland holes on that same drawing and request the quote through the custom stainless cutout page. The gland also has to keep the rating the box carries. A box rated NEMA 4X / IP66 by the manufacturer, not UL listed, holds that rating only when every gland fitted is rated to match, as the armoured cable gland rating article explains.
| Order line | What to write | The worked example |
|---|---|---|
| Cable | construction, core count, three caliper readings | 3-core 10 mm² 0.6/1 kV SWA/PVC: bedding 13.0 mm, wire 2 mm, overall 20.2 mm |
| Gland | smallest size whose three windows fit, with margin | M20 SWA gland, armour window 1.5-3.25 mm |
| Entry thread and hole | thread, pitch, count, face | M20 × 1.5, one hole, bottom face |
| Rating | gland rating matched to the box rating | IP66 gland, box NEMA 4X / IP66 |
| Layout | gland centres so the nuts clear | 30 mm centres between M20 entries |
The decision by case: a 3-core 10 mm² SWA/PVC at 13.0 / 2.0 / 20.2 mm takes one M20 SWA gland with an M20 × 1.5 hole. The same M20 on 1.25 mm wires is a termination that slips; order the M16 with its 1.0-2.0 mm window instead. A 29.8 mm cable with 3.5 mm wires overruns the M20 on bedding and armour both; order the M32 with its 3.0-5.0 mm window and its 28-36 mm overall range. When two sizes clear all three windows, take the one with the larger armour margins: the clamp is the part that holds the cable, and the outer seal rides on it.
After fitting, follow the SWA termination steps in order, then pull the sheath firmly by hand: the armour clamp must take the load with the outer seal staying put. The fitting sequence that keeps the rating is the one in the guide to installing a gland without losing the rating. A gland that passes the pull test but still weeps is losing water at the seal-to-sheath line, which is a clamping range question, not an armour one.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Do I measure the bedding diameter with the armour still on?
Strip the armour back a few centimetres at the drum end and caliper across the exposed bedding layer, taking two readings 90 degrees apart. Round cables run slightly oval, and a spread of 0.3-0.5 mm between readings is normal on a 13-20 mm cable; use the larger figure against the bedding maximum. Read the wire diameter the same way, across one wire, not across the bundle.
Does the number of armour wires change the gland range?
The printed window is per wire, not per bundle. Two wires of 2 mm side by side span 4 mm across, but an M20 window of 1.5-3.25 mm still applies, because the clamp cone grips each wire on its own diameter. Check a single wire against the window and let the bedding maximum handle the bundle's packing.
Can a reducing adapter rescue a gland whose armour range does not fit?
No, because the cable windows belong to the gland, not the hole. An M25 to M20 reducing adapter puts a fixed M20 gland into a bigger hole while keeping its 1.5-3.25 mm armour window and its bedding maximum, so the cable check stays exactly as you ran it. When the wires miss the window, change gland size, then re-check all three limits on the new line.
Is aluminium wire armour checked against the same window?
Against the same printed window. AWA replaces steel wires with aluminium ones on single-core AC circuits, and for a comparable cable the aluminium wires often run a few tenths of a millimetre larger. Caliper one wire and hold it against the window as usual; the clamp grips aluminium more softly, so we keep at least 0.2 mm of margin at each end of the window.
What does a wire just 0.1 mm outside the window actually do?
At 0.1 mm under the floor, a 1.4 mm wire against a 1.5 mm window start, the cone touches the wire with almost no interference, and a firm hand pull walks the armour out of the gland. At 0.1 mm over the ceiling the ring bridges and the lock nut bottoms without clamping. Treat the printed window as hard limits and step the gland size.