Short answer: power consumption is what your meter reads at the input, and heat dissipation is the part of that power which turns to heat inside the enclosure. The two are equal when everything the panel powers sits inside it: supply, PLC, relays and HMI on one backplate. They split when useful power leaves the box. A drive drawing 6.7 kW at 97 % efficiency keeps about 200 W inside and sends the rest down the motor cable. Split the input into useful output and losses, and the cooling decision becomes arithmetic you can put on the drawing.
Follow the watts across the enclosure wall
Your heat balance has one boundary: the enclosure wall. Every watt that enters as electricity either leaves again as useful power crossing that wall, or becomes heat the box must shed. If the inside temperature keeps climbing, the box is shedding less than the panel makes.
Useful power leaves through wires you can point at: a 24 V feed to a sensor or radio bolted outside, a drive's output to its motor, a transformer secondary feeding gear in the next cabinet. Everything else stays and heats the air.
| Device inside | Heat that stays in the box | Useful power that leaves |
|---|---|---|
| 24 V supply, load in the same box | all of it: output / efficiency | none |
| 24 V supply, load outside the box | about 10 % of input at 90 % efficiency | the 24 V output |
| VFD at 97 % efficiency | about 3 % of its input | motor power on the shielded cable |
| Dry-type transformer | about 1-3 % of its rating | the secondary power |
| PLC, HMI, relays, terminals | 100 % of what they draw | none |
A PLC card drawing 20 W has nowhere to send it: 20 W in, 20 W of heat on the plate. Contactors and terminal blocks add their I²R losses, small per pole and worth summing in a dense power panel.
Real power is what heats the box
Heat tracks real power in watts, and that is the number a wattmeter gives you. Voltage times current alone gives apparent power in VA. Real power is apparent power times the power factor (PF), the share actually doing work.
| Supply | Real power | Readings to take |
|---|---|---|
| DC | P = V x I | DC volts and amps |
| Single-phase AC | P = V x I x PF | RMS volts, RMS amps, PF |
| Three-phase, balanced | P = 1.732 x V x I x PF | line-to-line volts, line amps, PF |
Worked reading: 480 V line-to-line, 8.5 A per line, PF 0.95. P = 1.732 x 480 x 8.5 x 0.95 = 6,713 W, call it 6.7 kW. Volts times amps alone would read 7.1 kVA; on a load running at PF 0.7 the truth is 7.1 x 0.7 = 4.9 kW, so the shortcut overstates the heat-driving power by more than 40 %.
Drive input current is also distorted, so pick a meter that reports true watts there. For an unbalanced panel, take three single-phase readings and add them. Treat the 480 V check as energized work: rated meter and leads, and the arc-flash protection your site sets for the task.
From efficiency to watts inside
Two routes to the same loss, depending on which side you measured. From the output: losses = output watts x (1 / efficiency - 1). From the input: losses = input watts x (1 - efficiency). Use the efficiency at your actual load, off the datasheet curve.
A 240 W 24 V load on a 90 % efficient supply loses 240 x 0.111 = 26.7 W. A 95 % supply loses 240 x 0.0526 = 12.6 W, so five points of efficiency halve the heat. The maker's printed watts-loss figure beats both calculations when you have it; calculating the heat load from component losses and finding watts-loss when a datasheet prints none cover where to get the numbers.
A drive's loss fraction moves with load and carrier frequency. Conduction losses fall with the square of current, a quarter at half load, while the fixed switching losses sit there, so the loss percentage is worst at light load. Take the dissipation figure from the drive manual at your load; sizing a VFD enclosure: rating, size and cooling walks one drive end to end.
Dry-type transformer losses run about 1-3 % of the rating: 10 to 30 W on 1 kVA. The copper share falls with the square of current and the core share stays constant, which is why an unloaded transformer still warms its cabinet; transformer heat loss at partial load splits the two.
Read dissipation ratings with care. A semiconductor datasheet states power dissipation as a ceiling at a stated case temperature, usually 25 C, and how to read a MOSFET datasheet's current and power dissipation ratings shows how far that ceiling falls as the case heats. Your operating loss is lower; compute it from current and efficiency.
Worked example: 334 W in a 20 x 16 x 8 in stainless box
The panel: a 24 V supply at 120 W output and 90 % efficiency, 120 W of 24 V equipment on the same backplate, and a drive whose input meter reads 6.7 kW at 97 % efficiency.
- supply loss: 120 x (1 / 0.90 - 1) = 13 W
- control gear: 120 W, all of it stays
- drive loss: 6,713 x 0.03 = 201 W
- total: 13 + 120 + 201 = 334 W
The box: 20 x 16 x 8 in [508 x 406 x 203 mm] outside. Surface = 2 x (0.508 x 0.406 + 0.508 x 0.203 + 0.406 x 0.203) = 2 x (0.206 + 0.103 + 0.082) = 0.78 m². A stainless wall sheds about 3.7 W per square metre per kelvin, so this box rejects 3.7 x 0.78 = 2.9 W for every kelvin of rise. Steady rise: 334 / 2.9 = 115 K. At 35 C [95 F] ambient the inside settles near 150 C.
Drives and most industrial electronics are rated for 40 C [104 F] ambient unless their datasheet allows more. With 35 C outside, that is a 5 K budget. The box sheds 2.9 x 5 = 14 W passively, and the cooler must supply 334 - 14 = 320 W.
The decision: a heat exchanger or air conditioner in the 350-400 W class, or split the panel. Move the drive to its own cooled cabinet and this box still holds 133 W. That 133 W passively would need 133 / (3.7 x 5) = 7.2 m² of stainless, so order about 120 W of cooling instead (133 - 14 = 119 W). An internal fan evens hot spots but moves nothing through the wall; where internal fans leave the heat shows why. For the full sizing method from a finished heat load, the enclosure heat calculation guide carries it, and the enclosure heat calculator runs your numbers.
What to write on the drawing
- The heat budget, one line per device: 13 W supply + 120 W control + 201 W drive = 334 W total.
- The internal target and your ambient: 40 C inside at 35 C outside gave the 5 K budget that sized the cooler.
- The material factor: 3.7 W/m²K for stainless, 5.5 for painted steel, 3.5 for plastic; at one size, stainless passively sheds about two-thirds of painted steel.
- The cooling class with its watts: passive only while k x A x temperature rise covers the load, which is 14 W in the example box at a 5 K rise.
- The cooler's cutout pattern and the depth it needs behind the door.
Grade changes nothing in the heat math: 304 and 316L carry the same 3.7 W/m²K, because the surfaces and the air dominate a thin wall. Pick the grade for the environment and the size for the gear; the enclosure selector sets the inside dimensions, and a box that fits everything can still cook it, so keep the heat route on the same drawing. Our stainless boxes are rated NEMA 4X / IP66 by the manufacturer and not UL listed, and a custom box is delivered in 10 business days, counted from your approval of the drawing.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Are power consumption and heat dissipation ever the same number?
Yes, when every watt stays inside the box. A sealed panel whose supply, PLC, relays and HMI share one backplate dissipates exactly what the input meter reads, because no useful power crosses the wall. Add a drive feeding an outside motor and only its losses stay: about 3 % of input at 97 % efficiency, roughly 200 W on a 6.7 kW draw.
How much heat does a 24 V power supply add to an enclosure?
Its own loss is output watts x (1 / efficiency - 1): a 120 W output supply at 90 % efficiency loses 13 W, and a 95 % unit about 6 W. When the 24 V load lives in the same box, add the full output, so the first case puts 133 W into the air. Five efficiency points roughly halve the supply's share of the heat.
Why does multiplying volts by amps overstate my panel's heat?
Volts times amps gives apparent power in VA; heat comes from real power, which is VA times power factor. A balanced three-phase reading of 480 V and 8.5 A is 7.1 kVA - worth 6.7 kW at PF 0.95 but only 4.9 kW at PF 0.7. Use a meter that displays true watts, above all on distorted drive input current.
How hot will 334 W get a 20 x 16 x 8 in stainless box?
That box has 0.78 m2 of surface and sheds 2.9 W per kelvin through a stainless wall at 3.7 W/m2K, so 334 W lifts it 115 K, to roughly 150 C inside at 35 C ambient. Holding 40 C inside leaves a 5 K budget and about 14 W passive, so plan on around 320 W of cooling.
Does a drive's heat output track its load?
Only partly, and the loss percentage is worst at light load: the current-dependent conduction share shrinks with the square of the load current while the fixed switching losses remain, and raising the carrier frequency raises the switching share. The drive manual's dissipation table at your actual load beats any rule of thumb.





