Yes — with one condition: heat picks the box, not the weather. A stainless box rated NEMA 4X / IP66 by the manufacturer takes rain, hose spray and sun in stride. The sizing question is thermal: a sealed 24 x 20 x 8 in [610 x 508 x 203 mm] stainless box — the case worked below — sheds about 14 W at 35 C ambient while holding the interior 5 K warmer. A 48 A, 11.5 kW wall unit pushes current through it all night, so read the dissipation figure out of the charger's installation manual and run the arithmetic below. The box size follows. Charge with the door open when you are standing there; the sealed case that matters is unattended, full-current charging.
What the wall throws at the box
Four things hit an enclosure on an outside wall: rain, pressurized spray, sun and salt. Rain alone is a Type 3R job. Spray with pressure behind it — a hose rinsing the wall, a sprinkler head, a pressure washer — puts you in Type 4X / IP66 territory. That code means dust-tight plus powerful jets, a 12.5 mm nozzle at 100 L/min, and no immersion claim.
Salt picks the grade: 304 inland, 316L within sight of the water or where winter road salt lands on the wall. Molybdenum in 316L lifts pitting and crevice resistance, and that difference — not a heavier wall, not a higher temperature limit — is what the coast buys you. Coastal means 316L, not a thicker 304 box.
The sun is the largest single heat load an outdoor box sees. The solar heat load on an outdoor enclosure walks that number, and a shade hood beats an air conditioner on cost.
The rating the box needs
When the only weatherproofing on a label is the word itself, there is no test behind it. Buy the marking, not the adjective. A Type 3R box sheds rain and breathes: drainage openings of 3 mm to 6 mm [1/8 to 1/4 in], which NEC 314.15 permits in boxes listed for damp or wet locations. The Type 3R vs Type 4 comparison covers the trade. A Type 4X box has no openings and passes the hose test plus another 200 hours of salt spray judged against a 304 stainless specimen (Table 5-1D). What 4X adds over Type 4 is corrosion resistance; the fundamentals sit in the NEMA 4 vs 4X vs IP66 guide.
In US installations, NEC 110.28 is direct: the enclosure carries its type from Table 110.28, and an ip marking alone will not fill that line. Order both markings when the spec serves US and international readers. Our boxes are rated NEMA 4X / IP66 by the manufacturer and are not UL listed; a UL listed enclosure has been evaluated by UL to UL 50E, which is a different product and a different purchase. NEMA itself tests nothing — the maker rates the box against the type's tests. The charging unit, meanwhile, is listed equipment with its own outdoor marking on the label. Your box adds the lock, the hose resistance and the steel between the cable and bolt cutters.
| Condition on your wall | Order | What it buys |
|---|---|---|
| Under an eave, rain only, unit outdoor-rated | Type 3R box | Drains and free convective cooling |
| Hose, sprinkler or pressure spray | Type 4X / IP66 | No openings, hose-tested |
| Salt air or road-salt spray | Type 4X in 316L | Pitting resistance for chloride |
| Overnight 48 A charging, sealed door | 4X, then the heat check | Every watt leaves through the steel |
How much heat a wall unit makes
A Level 2 wall unit is a switch, not a converter: the car does the power conversion, and the box only carries the current. Losses follow the square of that current. Every milliohm in the path — a contactor pole, a lug, a breaker terminal — dissipates 48² x 0.001 = 2.3 W at full output, and 32² x 0.001 = 1.0 W on a 32 A, 7.7 kW circuit.
Add the contactor coil, the relays and the electronics, and the total lands between tens of watts and, if the manual quotes only an efficiency, 2% of the pass-through power. The installation manual governs: use its dissipation in W where it prints one. Where it gives an efficiency, losses = output x (1 − efficiency). The worked example below assumes 230 W, a deliberately conservative 2% of 11.5 kW — swap in the real figure before anything is ordered. The method for summing losses from every part in the box is in how to calculate enclosure heat load from component losses.
Sizing a sealed 24 x 20 x 8 in box for a 48 A charger at 35 C ambient
The inputs, each with its source:
- Charger: 11.5 kW output at 48 A on a 240 V circuit — the class of wall unit this question is about.
- Dissipation: 230 W, an assumption of 2% of output; the charger's installation manual holds the real number.
- Ambient: 35 C; interior target 40 C, the default this site uses for drives and electronics unless the unit's own listing allows 50 C.
- Box: 24 x 20 x 8 in [610 x 508 x 203 mm] stainless, wall-mounted.
- Wall coefficient: 3.7 W/m²K for stainless, the overall value with both air films included.
The rule in words: a sealed box loses heat only through its surface, and temperature rise = heat ÷ (k x exposed surface). The face against the wall does no work, so subtract it.
The arithmetic:
- Exposed area: door 0.610 x 0.508 = 0.310 m²; top and bottom 2 x (0.610 x 0.203) = 0.248 m²; sides 2 x (0.508 x 0.203) = 0.206 m²; total 0.764 m².
- Heat path: 3.7 W/m²K x 0.764 m² = 2.83 W/K.
- At the assumed 230 W: rise = 230 ÷ 2.83 = 81 K, interior 35 + 81 = 116 C. The contactor and the breaker derate out of that range long before you reach it.
- What the box can really shed: 2.83 W/K x 5 K = 14 W at the 40 C target; 2.83 x 15 K = 42 W if the unit is listed for 50 C ambient.
- What 230 W would need: 230 ÷ (3.7 x 5) = 12.4 m² of surface — a wall box about 1.6 m [5.2 ft] on a side.
The decision, then:
- Manual says 14 W or less: this box works sealed at 35 C ambient. Done.
- Manual says 15 to 42 W and the unit carries a 50 C ambient listing: still fine. Against a 40 C limit, step up the size — capacity scales linearly with surface, so twice the steel sheds twice the watts.
- Above 42 W: cool it sealed or vent it on purpose. A closed-loop heat exchanger or a 4X-rated air conditioner keeps the rating. A fan-filter or louver, usually about IP54, drops the assembly to its own rating, and a drain turns the design into Type 3R. A vent's own rating sets the assembly's rating, as the breather vent article covers. Drive enclosures get picked the same way — by heat, not hose.
Cable, conduit and antenna entries
Every hole in a 4X box follows one rule: the assembly's rating is the lowest-rated part in it. Bring the feeder in through the bottom face with a gland or hub that carries its own 4X / IP66 rating at your cable's outside diameter, locknut set and torqued to the gland's instructions. Leave a drip loop outside so water runs off below the entry.
The charging cable is a penetration too. Charge with the door open while you attend the car, or fit a sealed pass-through sized to the plug. The sealed USB pass-through method shows how a gland over the cut edge keeps the rating where a slot loses it. Radio is the quiet one: a stainless wall shields 2.4 GHz well, so mount the antenna outside through a non-metallic gland or behind a polycarbonate window in the door. Bolt the nozzle holster to the door face with sealed studs, and carry the cable over a door-edge hook, never through an open gap.
Wiring inside the enclosure
An EV charger is a continuous load: 48 A x 1.25 = 60 A on the conductors. In the NEC's ampacity table for copper at 75 C, 6 AWG carries 65 A, so 6 AWG is the wire and a 60 A breaker protects it. With a disconnect or breaker inside the box, NEC 240.24(A) keeps the center of the highest handle no more than 2.0 m [6 ft 7 in] above the floor — that usually sets your mounting height, and the mounting guide has the working-space numbers.
Bond the door, the backplate and the body, and strip paint to bare metal at every bond contact surface, which NEC 250.12 asks for at threads and contact points. Land the grounded conductor on the isolated neutral bar and the equipment grounds on the ground bus, so neutral current stays off the steel, as NEC 250.6 intends and the grounding and bonding guide details. One habit: open the box only with the feeder off and proven dead. Day-night swings fog a sealed outdoor box, so a small thermostat-controlled heater holding the interior a few kelvin above the night low stops the condensation cycle.
What to put on the order
For a 48 A wall unit, this spec survives both the weather and the heat check:
| Item | What to order | Why |
|---|---|---|
| Material | 304 inland; 316L near salt water or road salt | Chloride pitting resistance |
| Rating | NEMA 4X / IP66, manufacturer-rated, not UL listed | Hose spray, no openings |
| Size | From 24 x 20 x 8 in for a 48 A unit plus disconnect; larger when dissipation tops 14 W | The heat arithmetic above |
| Cutouts | One bottom feeder entry, gland to the cable OD, antenna port if the unit needs one | Bottom entries stay dry |
| Door | Key-locked latch, hinges on the sheltered side | Locks the cable, saves the gasket |
| Mounting | Wall feet, stainless anchors, shade hood on a sun-hit wall | Sun is the biggest heat term |
| Inside | Backplate, ground bus, 6 AWG terminations, thermostat heater | 60 A continuous, anti-fog |
You set the material, the three dimensions and every cutout on a custom stainless box, and it is delivered in 10 business days, anywhere in the world — counted from your order, or from your approval of the drawing for custom work. Start from the NEMA 4X stainless wall-mount range or the outdoor enclosures section, and run your own numbers first in the enclosure heat calculator. The heat check comes before the order, because it is what sets the size.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 20 × 16 × 8 in | 304 stainless | 20 x 16 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Can a 48 A EV charger live inside a sealed NEMA 4X enclosure?
Yes, when the unit's full-output dissipation stays under the box's passive capacity: about 14 W for a 24 x 20 x 8 in stainless box at 35 C ambient with a 5 K rise (k = 3.7 W/m²K), or 42 W if the unit is listed for 50 C ambient. Take the watt figure from the charger's installation manual before you buy anything.
Does adding a vent or fan keep the NEMA 4X rating?
Only a part carrying its own 4X / IP66 rating keeps it. A standard fan-filter or louver is usually about IP54, and the assembly drops to that; a 3-6 mm drain opening makes it a Type 3R design. Above roughly 42 W, keep the loop closed with a heat exchanger or a 4X-rated air conditioner instead of a vent.
What wire size goes to a 48 A charger inside the enclosure?
Copper at 75 C: 6 AWG, which carries 65 A, covers the 60 A that a continuous 48 A load needs (48 x 1.25). Protect it with a 60 A breaker, and keep the center of the highest handle no more than 2.0 m [6 ft 7 in] above the floor if the disconnect lives in the box.
Is 304 stainless fine outdoors, or should I order 316L?
304 serves inland walls. Order 316L near salt water or where winter road salt sprays the box: its molybdenum lifts pitting and crevice resistance. Both grades share the chloride stress-corrosion threshold near 60 C [140 F], and 304 can pit under a salt deposit even at room temperature, so coastal means 316L.
Will the charger's WiFi work through a stainless door?
Poorly, and predictably: a stainless wall shields 2.4 GHz well. Mount the antenna outside through a non-metallic gland, or leave a polycarbonate window in the door with the antenna behind it. With an internal antenna and a router one wall away, expect dropouts at setup time.