Making a motor control center (MCC) waterproof usually arrives bundled with two other asks: IP20 protection inside the cubicles and padlockable circuit breakers. Treat them as three separate boundaries, because only one of the three is an enclosure rating. The outer boundary carries the water: Type 4X / IP66 for hose-directed washdown, Type 6P only where the line-up can stand in water. IP20 lives at the components behind the cubicle door, and the padlock rides on the breaker operator as a maker's accessory. The heat example in the outer-enclosure section runs on labelled assumptions, so replace its inputs with your line-up's numbers before you order anything.
Can an MCC actually be made waterproof?
An MCC becomes water resistant, never waterproof, until the whole line-up sits behind a rated boundary: Type 4X / IP66 handles hose-directed washdown water, and true waterproof means a Type 6P design rated for prolonged submersion.
The IP code has two numerals (IEC 60529). The first runs 0 to 6 against solids and access: 5 is dust-protected, 6 is dust-tight. The second runs 0 to 9 against water: 4 is splashing, 5 is a 6.3 mm nozzle at 12.5 L/min, 6 is a 12.5 mm nozzle at 100 L/min, 7 is 1 m of immersion for 30 min, and 8 is continuous immersion under conditions agreed between manufacturer and user. A code ending in 0, as in IP20, tests no water at all. The digit meanings live in the IP rating chart guide.
Spoken strictly, waterproof means the second digit 8 or a Type 6P rating, and it always carries the maker's stated depth, duration and fluid. Water resistant is the honest word for jet protection: IPX5 or IPX6 water, NEMA Type 4 for hose-directed water, Type 4X once corrosion rides along. The corrosion step is real: Table 5-1D of NEMA 250 gives Type 4X another 200 hours of salt spray, judged against an AISI 304 stainless specimen, and the Type 4 vs 4X comparison guide walks that test.
Keep the two systems apart on the specification. In US installations, NEC 110.28 requires the enclosure Type number to be marked and used; the IP code does not replace it. A box carrying both a Type and an IP code satisfies a Type-4X line and an IP66 line at once. Our stainless wall-mount enclosures are rated NEMA 4X / IP66 by the manufacturer; not UL listed — the listed-versus-manufacturer-rated difference is set out in the listing guide. Hot, high-pressure close-range cleaning is its own test (IPX9), and a standard Type 4X box is not rated for it.
| Exposure at the line-up | NEMA Type that matches it | Decision |
|---|---|---|
| Rain and sleet | 3R | outdoor shelter with drains designed in |
| Hose-directed washdown | 4 | gasketed boundary, no corrosion duty |
| Washdown plus chlorides | 4X | 304 walls for routine duty, 316L for brine and sanitizers |
| Temporary immersion, 1 m for 30 min | 6 (nearest IP67) | custom design review |
| Prolonged immersion | 6P (nearest IP68) | custom design review |
What does IP20 actually protect against?
IP20 protects fingers only: the first digit tests the jointed test finger of IEC 61032 against live parts, the second digit is 0, and 0 means the code tests no water protection at all.
The scale steps up quickly. At digit 1, a 50 mm diameter probe must not pass through the opening. At digit 2, the probe becomes the jointed test finger of IEC 61032 (Test Probe B), and the code passes when that finger cannot touch live parts. IPXXB marks the same finger test on its own. Nothing in IP20 says a word about droplets, sprays or rain.
In an MCC, the door-closed state is the cubicle's own boundary. The condition you engineer for is the door open with the starter face exposed, and IP20 then lives at the components. The same planning as an IP20 drive in a rated box applies — see planning protection for an IP20 drive.
Where does the water get in?
Water reaches a dry-looking MCC through four paths: the door gasket line, a conduit arriving from higher up, cable strands that wick water, and a bottom pan that holds whatever the first three admit.
- The door gasket line. Gaskets take a compression set with age and heat; walk the full gasket path once a year and replace by the MCC builder's condition criteria rather than the calendar. Window kits, extra operators and field-added hardware all sit in this line.
- A conduit arriving from above. A riser that collects roof water delivers it by gravity into a dry cabinet. Trace every raceway to its source, fix the entry up there, and close the cabinet penetration with a rated gland and a drip loop — the gland details are in making an enclosure waterproof with glands.
- The conductors. Concentric- and compact-stranded cable wicks water along the strand gaps. A run that has taken water keeps delivering it after the source is fixed, so replace it with water-blocking cable.
- The bottom pan. Blocked or buried drains leave standing water against the lowest gasket, and corrosion follows the water. Stop the entry, dry the box, then treat the rust — the order in stopping corrosion inside an enclosure.
When the marks point nowhere obvious, work through finding water inside a sealed electrical enclosure before you spend on seals. Tighter gaskets cut liquid entry but can trap vapour that condenses on the next cold night.
Does a drilled drain hole keep the rating?
A field-drilled drain hole puts the cabinet outside the design its rating describes: a rating belongs to the assembly as the manufacturer builds and tests it, penetrations included, so every hole goes on the drawing first.
Drains are a design feature. Type 3R designs carry drain provisions as part of what the standard tests. For small boxes and conduit bodies, NEC 314.15 permits drainage openings of 3 mm to 6 mm (1/8 to 1/4 in) in damp and wet locations; an MCC cabinet sits outside that box world, and its drain belongs on the builder's drawing before the rating is applied.
Anything added on site sits outside the tested design. What one hole does to a Type 4 rating is the subject of the vent-hole article, and the same logic covers a hasp screwed through a door, a field-cut window or a pan drilled after delivery.
The working rule is to put every hole on the drawing. On a custom build you set the material, the dimensions and every cutout, the maker rates that exact design, and it is delivered in 10 business days from drawing approval — see the custom enclosure builder.
How do you get IP20 inside the cubicles?
You get IP20 inside a cubicle with the breaker maker's terminal covers, insulated bus shrouds, filler plates in every spare way, and closed wireway covers, so the jointed test finger reaches no live part with the door open.
- Fit the maker's finger-safe terminal covers on every breaker and starter.
- Shroud bus and line-side lugs with insulated barriers.
- Fill every spare way: a removed starter leaves a live-stab window straight onto the bus.
- Close gland plates and wireway covers; a missing cover is an open invitation to the test finger.
- Re-run the check with the compartment door in its service position, passing the jointed finger over every reachable part.
Order covers, shrouds and filler plates by breaker and starter variant, exactly as you order the lock accessories below. The accessory lists are variant-specific, and a cover from a neighbouring frame rarely seats.
How do you padlock the breakers?
Padlock a breaker with the lock accessory built for its exact frame and handle: it clamps the operator so the handle parks in OFF under the padlock, and you order it by breaker variant, not by amperage alone.
Many accessory sets lock the ON position too, for run-time lockout, and the door-interlock version holds the cubicle door shut while the breaker is ON. Which positions lock is on the maker's accessory page for the exact frame and handle version, so order by that variant and not by amperage alone.
Keep the lock off the gasket line. The accessory rides on the operator itself; a hasp screwed through the door cuts a hole into the water boundary for the sake of a lock that clips on without one. Padlocking is personnel protection, the third boundary in this article, and it shares nothing with IP20 or the Type rating. Before covers come off anywhere: lock out the feeder and check absence of voltage at the terminals with a proven tester.
When does the MCC go inside a rated outer enclosure?
The whole MCC goes inside a rated outer enclosure when the room itself gets washed or hosed: as a worked example, a line-up losing 120 W inside a sealed 36 × 96 × 20 in box rises only 6.3 K above a 30 °C room.
Nested boundaries work. The outer box carries water, corrosion and sun, while the MCC keeps its cubicle structure and its IP20 work inside it. Every raceway crossing the outer wall lands on a rated gland. Access changes: the cubicle doors open only after the outer door does, so plan the swing and the cable bends. If a breaker moves out to its own box, carry over the checks in breaker in a separate enclosure.
Worked example — assumed inputs, each to be replaced with your line-up's numbers:
- One section at the industry's common frame, about 20 in wide × 90 in high × 15 in deep, dissipating 120 W under load (read the real figure from the starter and feeder device data).
- Outer enclosure at 36 × 96 × 20 in exterior (0.914 × 2.438 × 0.508 m), 316L stainless, wall heat transfer k = 3.7 W/m²K.
- Dissipating area: front 0.914 × 2.438 = 2.23 m²; two sides 2 × 0.508 × 2.438 = 2.48 m²; top 0.914 × 0.508 = 0.46 m²; total A = 5.17 m².
- Rise: ΔT = P ÷ (k × A) = 120 W ÷ (3.7 W/m²K × 5.17 m²) = 120 ÷ 19.1 = 6.3 K.
- At a 30 °C room the inside sits at 36.3 °C, inside the 40 °C ambient rating most starter electronics carry.
- At a 35 °C room the same 120 W lands at 41.3 °C and that rating fails.
- Turned around, the loss budget at 35 °C is 5 K × 19.1 W/K ≈ 95 W.
So the sealed outer box suits a room near 30 °C at these losses, or a line-up under about 95 W in a 35 °C room. Past that, cool actively: an air conditioner through a rated collar keeps the outer Type intact, and a breather hole would surrender it. Sealed boxes also hold vapour, so handle the condensation side with the humidity measures for electronics near water.
By environment:
- Dry indoor room, splashes only: keep the MCC as built; do the IP20 work and the lock accessories, and fix the entry paths listed above.
- Rain over an outdoor pad: an outer Type 3R shelter or relocation; the indoor line-up stays as built.
- Washdown room: an outer Type 4X / IP66 boundary, or move the line-up out of the wash zone; individual duty groups can sit in their own stainless wall-mount enclosures rated NEMA 4X / IP66.
- Flood or immersion: a Type 6P design review stating depth, duration, fluid and every penetration; and any breaker or electronic device that has been under water is replaced, because an insulation test does not return it to service.
What do you put on the order?
Put three lines on the order: the outer enclosure with its rating and every cutout drawn in, the IP20 accessory kit for each breaker and starter variant, and the lock accessories keyed to the exact breakers in the line-up.
- Outer boundary: material by chemistry — 304 stainless for routine washdown, 316L for brine, salt air and chloride sanitizers — with the Type 4X / IP66 rating stated on the drawing, every cutout and gland drawn in, and gaskets matched to the wash chemicals, as on the washdown enclosure page.
- IP20 kit: finger-safe terminal covers, bus shrouds and filler plates, ordered per breaker and starter variant.
- Lock kit: the maker's lock accessory for each breaker variant, in the positions the accessory allows.
- Entries: one rated gland per cable crossing the outer wall, sized to the cable OD, with drip loops outside.
- Immersion: only through a Type 6P design review that states depth, duration, fluid and penetrations.
Three boundaries, three order lines. The line-up then says exactly what it is: IP20 at the components, padlocks on the operators, and a water rating carried by the enclosure that actually faces the hose.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 60 × 36 × 16 in | 304 stainless | 60 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 48 × 36 × 16 in | 304 stainless | 48 x 36 x 16 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 60 × 36 × 12 in | 304 stainless | 60 x 36 x 12 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is an IP68 MCC truly waterproof?
Only for the conditions the maker states. A second digit of 8 means continuous immersion under conditions agreed between manufacturer and user, so the depth and duration live on the datasheet, not in the code. The matching NEMA Type is 6P for prolonged submersion. Our stock stainless boxes are not immersion rated; an MCC boundary for flood water starts as a Type 6P design review that states depth, duration and every penetration.
Can a Type 12 MCC stay outdoors with a drain fitted?
Plan a rated boundary instead. Type 12 covers indoor dust, dirt and dripping liquids, and a drain cut in the field sits outside the design the manufacturer tested. Outdoor rain is what Type 3R is built for, with drains designed in from the start. Keep the Type 12 line-up indoors or put a Type 3R or 4X outer enclosure around it, with every penetration on the drawing before the rating is applied.
What padlock fits a motor-protective circuit breaker?
The lock accessory made for that breaker variant. It clamps the toggle so the handle parks in OFF under the padlock, and many sets also lock the ON position for run-time lockout. Order by the exact frame and handle version, because the accessory clips to that operator. Keep the padlock off the door gasket line: the lock rides on the operator, not on a hole drilled through the sheet metal.
Can breakers be reused after an MCC has taken water?
Replace them. Molded-case breakers, fuses and electronic devices that have been under water are replaced, and an insulation resistance test does not return them to service — the water-damaged equipment guidance the industry follows. Dry the structure, fit new devices, and find the entry path before the replacements see the same water.
Which stainless steel faces a washdown with sanitizers?
304 stainless handles routine washdown; 316L is the choice for brine, chlorine sanitizers and salt air. Chloride stress-corrosion cracking becomes a risk around 60 °C (140 °F) for both grades, so hot sanitizer lines want the molybdenum grade and gaskets matched to the chemical. The outer boundary carries the Type 4X / IP66 rating; the cubicles keep their IP20 boundaries inside it.





