How to read the NEMA enclosure type selection table

Find the condition rows your application needs, then take the first type column with an X in every one of them. For incidental contact with enclosed equipment, rain and snow, windblown dust and hose-down, Type 4 is the first column with all four X marks; Type 3R stops at rain and sleet.

NEMA4 Enclosure engineering team · Published November 9, 2026 · 6 min read

Short answer: walk NEC Table 110.28 down its condition rows, mark every row your application needs, then take the first type column with an X in all of them. For a panel that sees incidental contact, rain and snow, windblown dust and hose-down, Type 4 is the first column with all four X marks. Where sanitizers, salt or solvents join the washdown, step one column further to Type 4X.

How do you read the NEMA enclosure type table?

You read the table the way the code intends it: find the rows that describe your conditions, then take the first type column — Type 1 through 6P — that carries an X in every one of those rows, not the column with the most X marks.

The table lives in NEC 110.28, which covers enclosures for switchboards, panelboards, industrial control panels and similar equipment rated 1000 V nominal or less. Equipment built for the locations the table names carries an enclosure type number from that table. Each column is one type; each row is one condition of protection; an X means the enclosure is built to deliver that degree of protection.

The first passing column is the minimum. Everything to its right that also passes is an upgrade you buy for corrosion, submersion or hazardous duty, not a different answer. The NEMA enclosure types guide defines each type's wording; the walk below reads the columns.

Which conditions does the table list as rows?

The rows fall into three bands: access to hazardous parts, meaning incidental contact with the enclosed equipment; ingress of solids, which splits indoor falling dirt from outdoor windblown dust; and ingress of water, laddering from dripping liquid down to hose-directed spray, with external icing as its own line.

The incidental-contact X runs down the enclosure columns from Type 1 through 6P, so it rarely decides anything. The decision lives in the solids and water bands, where the X marks fall away fast. NEC Table 110.28 pairs each type with the conditions it serves. Watch two traps while you read: Type 5 carries the dust X but sits indoors with no hose X, and the outdoor family is Types 3, 4 and 6.

Which type covers incidental contact, rain, dust and hose-down?

Type 4 is the first column with an X in all four rows your washdown panel needs — incidental contact, rain and snow, windblown dust and hose-directed water — so Type 4 is the table's minimum answer, and Type 4X is the same column with a corrosion duty added.

Work a real panel: a 16 x 12 x 8 in [400 x 300 x 200 mm] stainless box on the outside wall of a dairy bottling room. An interlocked door guards live terminals (contact), the wall takes weather (rain and sleet), yard dust blows in summer (windblown dust), and the crew hoses everything down at shift end (hose-directed water). Walk the columns from the left:

Condition row Type 1 Type 2 Type 3R Type 4
Incidental contact with enclosed equipment X X X X
Dripping water and light splashing – X – X
Falling rain and sleet – – X X
Windblown dust – – – X
Hose-directed water – – – X

Type 1 and Type 2 stop at the rain row. Type 3R clears rain and sleet and dies at windblown dust; Type 4 keeps that X and adds snow, dust and hose spray. Type 4 carries all five X marks, so it is the first passing column and the minimum you write on the drawing. The sanitizer spray and chloride brine on this line step you right once more, to Type 4X in 316L.

Why does Type 3R fail the hose-down row?

Type 3R earns its X only in the falling-water rows — rain, sleet and external ice — so a shift-end washdown jet arrives sideways, at line pressure, and drives straight through the openings a rain-tight box is allowed to have.

A 3R box is built to shed what falls into it. NEMA 250 and UL 50E expect drain openings on Types 3R and 3RX, cut at 3 to 6 mm [1/8 to 1/4 in], because some rain is designed to enter and leave; a Type 4 box has a continuous door gasket, sealed entries and no drain. The fork between the two ratings gets its own page at NEMA 3R vs NEMA 4: rain or hose?, and the rain, sleet and ice standards behind Type 3R list exactly which tests the 3R column stands on — hose-down is not among them.

What does the type rating actually test?

A type column stands on laboratory tests, not field history: NEMA 250 backs Type 4's hose X by spraying the box with a 1 in [25 mm] nozzle at about 65 US gal/min [246 L/min] from 10 ft [3 m] for 5 min.

Do the unit check and the difference between the standards shows up: 65 gal/min is 65 × 3.785 = 246 L/min, about 4.1 L/s. IEC 60529 backs the IPX6 jet with a 12.5 mm nozzle at 100 L/min from 2.5 to 3 m for at least 3 min. Similar water, different plumbing, and one code does not convert to the other. That is why NEC 110.28 states, for US installations, that an IP rating does not replace the enclosure type number — decode the digits with how to read an IP rating and pair the codes in the IP rating chart.

Behind the other X marks sit a windblown-dust test and a gasket and door-seal check. The X in 4X is a duty of its own: Table 5-1D gives Types 4X, 3X, 3RX, 3SX and 6P another 200 hours of salt spray, checked beside an AISI 304 stainless specimen. A UL listed enclosure has been evaluated by a testing laboratory to UL 50E — the listing guide covers when a project needs one — while ours are rated NEMA 4X / IP66 by the manufacturer; not UL listed.

What does the rating not cover in a real panel?

The X marks rate the empty enclosure as built; your assembly adds glands, windows and filters, each with its own rating, and the finished panel runs at the lowest one — so one IP54 connector turns a Type 4X cabinet into an IP54 cabinet.

Fit every gland and window accessory at Type 4X / IP66 or better, onto flat sealed lands, and enter from below where the layout allows — the wall-mount orientation page shows why. A sealed box still cycles with temperature: an 11 C [20 F] evening drop on humid air leaves condensate on the roof by morning, which a small anti-condensation heater or desiccant manages better than a drain hole ever will.

Hazardous columns need their own read: Types 7, 8, 9 and 10 serve Class I and Class II atmospheres, and their X marks cover explosion duty, not weather — a NEMA 7 or 9 box is not automatically raintight. We build no hazardous-location enclosures; that equipment carries its own class and division rating. Corrosion moves with chemistry, so 316L buys pitting resistance in sanitizer and salt service where 304 stalls.

Which type do you put on the order?

Write the type, the grade and the rating basis on one line — "Enclosure Type 4X to NEMA 250, 316L stainless, manufacturer-rated NEMA 4X-type / IP66; not UL listed" — and list the condition rows that forced the choice.

Your panel and site First passing column What to order
Indoor, touch-safe only Type 1 painted steel, ungasketed
Indoor, dripping oil or falling dirt Type 2 gasketed steel
Outdoor wall, rain and sleet only Type 3R 3R shell with its drain path
Outdoor, windblown dust plus rain Type 3 sealed 3X where the air turns corrosive
Washdown or driven spray Type 4 sealed Type 4, stainless where chlorides bite
Washdown with sanitizer, salt or solvent Type 4X 316L, manufacturer-rated NEMA 4X-type / IP66
Puddles or temporary submersion Type 6 custom design review; not a stock rating

We build the 4X line to order: 304 or 316L stainless, your width, height, depth and every cutout, delivered in 10 business days — for custom work, from your approval of the drawing. Pick a stock size among 316L wall-mount enclosures or take the environment, listing and module count to the enclosure selector, which flags high-pressure or hot washdown and outdoor HMI duty for an application review before you commit.

Catalog dimensions to compare

Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.

EnclosureMaterialOutside H x W x D / displayRating
16 × 12 × 8 in304 stainless16 x 12 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 14 × 8 in304 stainless16 x 14 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
16 × 14 × 8 in316L stainless16 x 14 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed
24 × 20 × 8 in316L stainless24 x 20 x 8 inRated NEMA 4X / IP66 by the manufacturer; not UL listed

Questions

Does a Type 4X rating mean the box survives underwater?

Not underwater. Type 4X tops out at hose-directed water, and submersion is a different column: temporary submersion belongs to Type 6, the nearest IP pairing being IP67 at 1 m [3.3 ft] for 30 min, while continuous immersion is Type 6P on depth and duration conditions agreed with the manufacturer. Our stock 4X-type boxes carry no immersion rating, so a submerged install starts as a custom design.

Can an IP66 code replace the NEMA type on a US submittal?

In US installations it cannot: NEC 110.28 states that IP ratings are not a substitute for enclosure type ratings, so the submittal needs the type number from Table 110.28. A nameplate carrying both codes — as ours do, NEMA 4X-type / IP66 — satisfies a US type specification and an international IP specification at once.

Is Type 4X corrosion-proof in a food plant with sanitizer spray?

Treat it as corrosion-resistant, not corrosion-proof. The 4X column's corrosion X stands on 200 hours of salt spray, and molybdenum in 316L lifts pitting and crevice resistance, but the chloride stress-cracking threshold sits near 60 C [140 F] for 304 and 316L alike. Specify 316L for sanitizer and salt service and keep hot caustic lines from baking the gasket.

Do I drill a drain hole in a Type 4 enclosure?

Leave it sealed. Drain openings of 3 to 6 mm [1/8 to 1/4 in] belong on Types 3R and 3RX, which are built to shed water; a Type 4 assembly is built to seal it out. A field-drilled hole drops the whole assembly below its column, so control condensation with an anti-condensation heater or desiccant instead.

How do the hazardous-location columns change how I read the table?

As a separate family. Types 7, 8, 9 and 10 serve Class I and Class II atmospheres, and their X marks cover explosion duty, not weather; none of those columns carries the rain, dust or hose X that Type 4 does. Hazardous locations take equipment rated for the class and division — equipment we do not build.

Checklist before you order

Specify it once, built to your drawing

  • Environment and NEMA type: Type 1, Type 3R, Type 4, Type 4X, Type 6P, Type 12, Type 13 (manufacturer ratings, not UL listed)
  • Material: 304 stainless steel, 316L stainless steel, Powder-coated carbon steel, Aluminum, Polycarbonate, Fiberglass (FRP)
  • Size: inside or outside height, width and depth, with the depth your deepest component needs
  • Cutouts, glands and windows, dimensioned from one datum on each face
  • Mounting and access: wall, pole or stand, hinge side, mounting panel
  • Quantity: from one piece

Delivered in 10 business days, anywhere in the world. Counted from your order; for custom work, from your approval of the drawing.

Start from the washdown control panel buildRequest a custom quote

Washdown enclosures: sizes for this job

Keep reading

More on ratings and standards

All articles

Buying guides

The guides behind this answer

All guides