Short answer: total the batch energy first, then read the chiller's capacity at the coolant temperature you will actually run. A 20 kg water batch falling from 37 °C to 8 °C in 30 minutes sheds 2,424 kJ, an average of 1.35 kW. A unit that delivers 0.8 kW at 0 °C coolant fails that screen before any coil enters the argument. When the screen passes, the coil decides the schedule: this duty needs about 90 W/K of U×A at the coolant setpoint chosen below to land inside the half hour. Below are the calculation, the rating points that matter, and the checks that prove the unit on the floor.
How much heat must the batch give up?
Twenty kilograms of water cooling from 37 °C to 8 °C must shed 20 × 4.179 × 29 = 2,424 kJ. A 20 L fill of water weighs about 20 kg, and water's specific heat at around 40 °C is 4.179 kJ/(kg·K). The fill volume, the fluid and the two temperatures are the only inputs. If the vessel holds brine, oil or product, swap in its mass and specific heat from the property table over the working range. The arithmetic does not change.
| Quantity | Value | Basis |
|---|---|---|
| Batch mass | 20 kg | 20 L fill, water at about 1 kg/L |
| Specific heat | 4.179 kJ/(kg·K) | water at around 40 °C |
| Temperature drop | 29 K | 37 °C down to 8 °C |
| Energy to remove | 2,424 kJ | m × cp × ΔT |
| Window | 1,800 s | 30 minutes |
| Average duty | 1.35 kW | 2,424 kJ ÷ 1,800 s |
A watt is a joule per second, so 2,424 kJ over 1,800 s lands at 1.347 kW with no detour through calories. The batch is only the first term. The vessel shell, the agitator and heat leaking through insulation ride on top, and the step list below adds them.
What does the kW figure on the chiller actually rate?
The 0.5 kW and 0.8 kW figures are heat-removal ratings tied to the coolant temperatures printed beside them, here 0.5 kW at -20 °C and 0.8 kW at 0 °C. They compare with the batch only after you move to your own operating point. Decide first which table the figure came from: capacity tables list heat removed, and electrical tables list power drawn. The two differ by the unit's efficiency. Then check the rating conditions: chiller makers publish recirculating capacity in their standard tables at a 20 °C coolant delivery temperature and a 20 °C ambient. This two-point curve is something you move along, not stand on. A hot plant room trims an air-cooled condenser further, and that shows up as less capacity at the same setpoint.
Which temperature do you read the capacity at?
Read capacity at the coolant supply setpoint you will actually run, which must sit below the 8 °C endpoint; 3 °C is a sensible choice for this duty. Interpolating the published pair gives 0.8 kW + (3 K × 0.015 kW/K) = 0.85 kW. The two published points set the slope: 0.3 kW across 20 K is 0.015 kW/K, so every kelvin of setpoint is worth 15 W. The classic error is reading at the batch endpoint. The coolant has to run colder than 8 °C for the batch to arrive at 8 °C at all.
| Coolant setpoint | Capacity on this curve | Against the 1.35 kW average |
|---|---|---|
| 20 °C, the catalog basis | 1.10 kW | passes, and misleads |
| 0 °C | 0.80 kW | short by 0.55 kW |
| 3 °C, the planned run | 0.85 kW | short by 0.50 kW |
| -20 °C | 0.50 kW | short by 0.85 kW |
A buffer reservoir cannot rescue the gap. At 0.5 kW short, the run accumulates 900 kJ of deficit over 1,800 s. A 10 L reservoir lifted 10 K stores only about 419 kJ. The refrigeration circuit itself has to cover the average.
How do you run the numbers step by step?
You need five inputs before the arithmetic starts. Collect the batch mass and its fluid, the two temperatures, the window, the vessel weight, and the chiller's capacity table with its rating temperatures.
- Compute the batch energy: 20 kg × 4.179 kJ/(kg·K) × 29 K = 2,424 kJ.
- Divide by the window: 2,424 kJ ÷ 1,800 s = 1.35 kW average.
- Add the vessel and the gains. A 10 kg stainless shell at about 0.50 kJ/(kg·K) contributes 10 × 0.50 × 29 = 145 kJ, and 100 W leaking through insulation for 1,800 s adds 180 kJ. The duty rises to 2,749 kJ, or 1.53 kW.
- Choose the coolant setpoint below the endpoint (the table above), and read or interpolate capacity there: 0.85 kW on this curve.
- Reject the unit when capacity sits below the margined average. Here 0.85 kW falls about 45% short of 1.53 kW.
- When the screen passes, size the coil before ordering: the 90 W/K figure in the next section is the second gate.
The shell mass and the leak are example values, so weigh the vessel and take the leak from your own insulation. Together they added 13% in this example, enough to flip a marginal pass into a fail.
How much coil does the 30-minute window need?
Holding this batch on a 30-minute schedule takes about 90 W/K of U×A at the setpoint coolant. That comes from t = (m × cp ÷ U×A) × ln[(37 - 3) ÷ (8 - 3)] set against 1,800 s, so a generous chiller on a stingy coil still misses the endpoint. Work it backwards: m × cp is 83.58 kJ/K and the log term is ln 6.8 = 1.92. So U×A = 83.58 kJ/K × 1.92 ÷ 1,800 s = 0.089 kW/K, or 89 W/K. The units check because kJ ÷ kW leaves seconds.
The log-mean driving force between 34 K and 5 K is 15.1 K, and 89 W/K × 15.1 K = 1.35 kW, which matches the energy balance; that agreement is the proof the numbers hang together. The instantaneous rate starts at 89 W/K × 34 K = 3.0 kW and decays to 89 W/K × 5 K = 445 W at the end. The compressor never sees the full 3 kW as load when the reservoir is sized to buffer it, but the reservoir must be big enough to matter. The constant setpoint is a simplification; a real loop warms along the coil, so treat 89 W/K as the floor and have the chiller maker confirm the transfer at its flow.
Does a 50/50 glycol mix rescue an undersized unit?
No: a 50/50 ethylene glycol mix carries about 3.4 kJ/(kg·K) at 1.077 kg/L, roughly 12% less heat per litre than water at 27 °C. It trims the loop's capacity slightly and earns its place as freeze protection rather than extra cooling. The batch stays water either way, so the load calculation above is untouched: changing the chiller's circulating fluid never changes the vessel's energy. Property tables give the 50% solution a specific heat 0.815 times water's and a specific gravity of 1.077 at 27 °C. It is also thicker, so the pump moves less of it and the coil's film coefficient drops with the flow. A plain-water loop at that setpoint runs close to freezing at the evaporator, so glycol buys margin at a small capacity cost, and the curve should then be read for glycol, not water.
What do you check once the unit runs?
Run one timed batch and watch three numbers: the supply temperature holds within 2 K of setpoint through the run, the reservoir swings less than about 5 K, and the batch reaches 8 °C inside the 30 minutes.
- Supply temperature. A supply drifting 2 K or more above setpoint mid-batch means the compressor is at its limit; re-read the curve at the drifting temperature, not the setpoint.
- Batch clock. Stamp 37 °C to 8 °C. A batch landing at 33 minutes points at the coil, the flow or the reservoir, in that order.
- Reservoir swing. More than about 5 K of rise across a run means stored cooling is doing work the refrigeration cannot sustain, and back-to-back batches will creep.
- Condensation. A coolant line near 0 °C sweats in almost any plant room. The coil condensate estimate sizes the water you must route to a drain before it drips onto the floor.
- Condenser air. If the unit removes 1.35 kW and draws 0.85 kW, its condenser rejects about 2.2 kW (1.35 + 0.85) into the room. A walkthrough on sizing an air-cooled chiller from measured load data covers the air-side arithmetic.
- Room and neighbours. Keep the hot exhaust off nearby panels: a cabinet beside hot discharge picks up load, the same problem the outdoor enclosure guide works through for hot shops. A hot room trims the condenser just as it trims a cabinet cooler.
- The wet corner. If washdown reaches the chiller's own cabinet, spec stainless there too: rated NEMA 4X / IP66 by the manufacturer; not UL listed, cut for the disconnect and the pump leads, delivered in 10 business days. The NEMA 4X vs IP66 guide covers what that rating does and does not cover, and the enclosure selector sorts candidates by environment and inside dimensions.
Which mistakes sink the batch?
The recurring failures all carry a number: a rating read at -20 °C instead of at the planned setpoint, a catalog figure taken at 20 °C, electrical watts counted as cooling, a 13% vessel margin dropped, and refrigeration sized to the 445 W tail rather than the 3.0 kW start.
- Reading the nameplate cold. The batch never runs at -20 °C. From there to the setpoint lie 0.35 kW of phantom credit or shortfall, depending which point you quote.
- Quoting the catalog basis. Capacity at the 20 °C catalog basis reads 1.10 kW on this curve; the loop runs at the setpoint and sees 0.85 kW, so 0.25 kW exists only on paper.
- Counting electrical watts as cooling. Input power and heat removed differ by the unit's efficiency; compare heat with heat.
- Dropping the vessel margin. 2,749 kJ against 2,424 kJ is the whole difference between a pass and a fail on a marginal unit.
- Sizing to the tail. The final minutes pull 445 W, the first pull 3.0 kW. Refrigeration and reservoir must survive the start, not the finish.
- Trusting glycol for capacity. It carries about 12% less heat per litre and buys freeze margin, nothing else.
The decision in one line: screen the refrigeration at your coolant setpoint against the margined average (1.53 kW here), then screen the coil at 90 W/K for the 30-minute window, and reject this example unit, which offers 0.85 kW at the setpoint against a 1.53 kW duty. Pick a curve that clears 1.5 kW at the setpoint and a flow that delivers the transfer, then prove it with the timed-batch checks. The panel side runs the same balance: run the heat-load calculation on your cabinet's watts before you pick its cooling, and how to size an electrical enclosure shows how the heat check fits the overall size decision.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 30 × 24 × 10 in | 304 stainless | 30 x 24 x 10 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is the watt figure on a chiller plate cooling capacity or electrical input?
Look at which table the figure sits in: capacity tables list heat removed, and electrical tables list power drawn. A unit removing 0.8 kW of heat while drawing 0.5 kW works at a coefficient of performance of 1.6 and rejects about 1.3 kW at its condenser (0.8 + 0.5). Compare only the heat-removed figure with the 1.35 kW batch average, read at the coolant temperature you will run.
What changes when the vessel holds brine instead of water?
Swap the density and specific heat, then keep the arithmetic. A fluid at 1,100 kg/m³ with a specific heat of 3.5 kJ/(kg·K) fills 20 L with 22 kg, and the same 29 K drop sheds 22 × 3.5 × 29 = 2,233 kJ, an average of 1.24 kW. Take both values from the fluid's property table over the working range; water's numbers never carry across.
Can one chiller serve two 20 L vessels?
Count simultaneous batches, not litres. Two vessels cooled together double the duty to 2.7 kW average and need about 180 W/K of coil at the same coolant setpoint. Two staggered batches can share a 1.5 kW-class unit if the reservoir returns to setpoint between runs; time that recovery on the supply gauge and add it to the cycle before promising a schedule.
Why does the last few kelvin take so much longer than the first?
With a setpoint 5 K below the 8 °C endpoint, the driving force starts at 34 K and ends at 5 K, so the instantaneous rate falls about sevenfold while the average holds at 1.35 kW. The time constant, m × cp ÷ U×A, is about 940 s here, which puts roughly half the batch energy in the first 600 s. The tail is physics, so judge the unit on the whole curve, never on its slowest minute.





