Short answer: the hot bar is the anti-condensation heater, and its thermostat is set far above any condensation-control duty. Trace the two leads from the bar to the dial, then set it 5-10 C (9-18 F) above the dew point of the air inside the box. A heater held near its top mark runs continuously and bakes the harness around it; the same heater on a dew-point setting cycles a few minutes an hour and keeps a washdown box dry. While you are in there, remake every discolored termination and land the loose ground wire on its stud.
Why is the metal bar under my PLC getting hot?
That bar is an anti-condensation heater, a resistance strip built to run warm, and it is burning hot because the thermostat feeding it sits near its top mark of 60 C (140 F), roughly 35 C above any useful condensation-control setting.
It looks like a busbar because it bolts to standoffs behind the controller, but the two thin leads give it away. Trace them: they land on the strip at one end and on the dial at the other. A 50 W strip on 120 V draws 50/120 = 0.42 A whether the machine runs or not, so its heat has nothing to do with the program or the load. The thermostat senses air at its own location, and a bare element in still air always runs hotter than the box around it. Heat then conducts through the mounting brackets into everything bolted nearby, which is why the plate behind the controller feels cooked.
Which symptoms point at the heater and not the controller?
Localized heat on a bolted metal strip while the machine works points at the heater circuit, and the symptoms below separate heater trouble from controller trouble or a plain loose termination.
- Hot strip bolted behind the controller, thin leads to a dial thermostat: the heater is the source and the dial is the control.
- Box still hot with the controller unpowered: the heater circuit is fed separately, or the thermostat contacts are welded closed.
- Dial parked at its top mark: the set point is a dry-out temperature, far above the dew point this box needs.
- Brown, brittle insulation where conductors touch or pass the strip: long hours of contact heating; plan to rewire that run.
- One brown termination on an otherwise cool strip: a bad joint at that lug, not a heater problem.
- Fog on the inside of the door glass after washdown: the heater is undersized or set below the local dew point.
What makes an anti-condensation heater overheat a panel?
The most likely cause is the set point: a dial left near its maximum holds the element on continuously, and the close second is a thermostat whose contacts welded closed after years of switching a resistive load.
- Set point far above the dew point. A heating thermostat closes whenever the sensed air sits below the dial, so a top-mark dial on a warm box never opens. Read the dial, in the units it is marked in, against the dew point you compute below.
- Welded or bypassed contacts. Resistive loads arc on opening and pits weld them shut. Turn the dial to minimum with the panel live and guarded: a strip that never cools has stuck contacts or a jumper around the thermostat.
- Heater mismatched to the box. An enclosure-heater maker's sizing paper pairs every heater above 150 W with a circulation fan, sized CFM = (3.17 x P) / ΔT °F with P in watts; a fanless strip above that class dumps its heat in one corner. Compare the heater's rated watts with the heat-loss figure below, and the article on heater wattage sizing for a sealed enclosure works the same sum for bigger boxes.
- Element mounted against the harness. The strip's own instructions carry its clearance; hold conductors outside it with duct or ties.
- Loose termination in the heater circuit itself. Contact resistance adds local heat even with the right dial; an infrared thermometer on the lugs finds it in seconds.
How do I check the heater circuit safely?
Isolate the panel, lock it out and verify absence of voltage at the heater terminals before touching anything, because the heater circuit stays live from its own supply even with the controller switched off.
Then work in this order:
- Trace the two element leads to the thermostat and to their supply, and record the heater's rated watts and voltage from its marking.
- Read the dial and its units; dials marked in F get misread as C and the other way round.
- Re-energize with the live parts guarded, and measure the air at the thermostat sensor plus the strip surface with an infrared thermometer from a hand's length.
- Turn the dial down and watch: the strip should cycle, resting most of each hour once the set point sits near the dew point.
- Fix anything that fails these checks before the machine returns to service.
What should the anti-condensation thermostat be set to?
Set the thermostat 5-10 C above the dew point of the air in the enclosure, measured in the damp condition the box sees; after a washdown, air at 25 C and 70% RH has a dew point near 19 C, so a 24-29 C (75-84 F) setting covers it.
A heating thermostat closes when the air drops below the dial, so the right dial sits just above the temperature you want, not at the hottest mark. Condensation forms on any surface below the dew point, and holding the interior a few degrees above it keeps every wall dry; the margin covers the gap between the sensor's air and the cold metal it protects. The condensation guide works this comparison out in full, and the dew-point-versus-heater-watts article shows the same check from the heater side. In hot humid climates, where the dew point sits close to ambient all year, read that article before choosing a number.
Worked example: a 12 x 10 x 6 in washdown box
Take a 12 x 10 x 6 in stainless box hosed down each morning.
- Air after hose-down: 25 C at 70% RH. Field check: dew point ≈ 25 − (100 − 70)/5 = 19 C; dew-point tables give the same value.
- Target: 19 C plus a 5 C margin = 24 C; choose 26 C (79 F) to cover the cold bottom wall, inside the 24-29 C band.
- Wall area: 2 × (12 × 10 + 12 × 6 + 10 × 6) = 504 in² = 0.325 m².
- Heat to hold 26 C against a 10 C night: 3.7 W/m²K (stainless) × 0.325 m² × 16 K = 19 W. A 30 W or 50 W fanless strip covers it with cycling margin, and small-box heater selection uses exactly this arithmetic.
- The old 60 C mark against 20 C shop air: 3.7 × 0.325 × 40 = 48 W, the whole element, day and night. Its surface runs above the air, and insulation resting on it browns and embrittles; common PVC control wire is rated 75 C or 90 C at the conductor, the ratings the NEC ampacity table uses.
For a box that gets hosed or lives outdoors, a hygrostat beats a plain dial: it closes when the interior air turns damp, runs the element after each washdown and leaves it off in dry heat, which cuts running hours sharply. A humidity-sensor condensation control strategy does the same job with readings you can log.
What do I do about wiring the heat has damaged?
Replace the runs, do not trim them: cut out any conductor with brittle, discolored or cracked insulation at least back to sound material, remake every termination to the terminal's strip length and torque, and crimp ferrules on fine-stranded ends where the terminal design accepts them.
Contact heat and heater heat look different up close. A bad joint browns one lug and its conductor end; the strip browns everything resting on it. Work from the cable entry to each termination, replace the damaged lengths, and torque each screw to the value printed on its block; 0.5-0.6 Nm covers most M3 terminal screws. Fit a gland sealed for the actual cable diameter at the entry so the conductor cannot saw on the wall edge, and route the new harness away from the strip with duct or ties. Land the ground wire on its stud while you are there, and clean paint off the contact faces: NEC 250.12 requires paint, lacquer and enamel removed from threads and contact surfaces at grounding and bonding connections. Where several circuits share one box, the article on grounding a metal box with multiple circuit splices shows how to land them.
How do I keep the box from cooking itself again?
Write the set point and the date on a label inside the door, feed the heater so it dies with the panel disconnect, and check the dial at each washdown season, because dials get nudged and contacts wear.
Seasonal sites need a small adjustment: the heater earns its keep on cold damp nights and idles in dry summer heat, and the article on when an outdoor enclosure needs an anti-condensation heater walks through that call. The cold-start heater and thermostat selection article pairs the heater with its control so a January morning starts dry. On a washdown box, a hygrostat with a thermostat back-stop near 40 C (104 F), the ambient most panel electronics are rated for, gives control that cannot cook the harness even if one contact fails closed. A motor's own winding heater is a separate circuit with its own controls; the guide to preventing motor condensation with anti-condensation heaters covers that side. At each inspection, confirm the strip cycles, the door glass stays clear and no new discoloration spreads.
When should I re-specify the enclosure instead of the heater?
Re-specify when the heater has scorched the enclosure interior, when the layout gives no way to keep the harness clear of the element, or when the box needs a size class up to hold its dew point with the harness in a safe position.
Watts climb with wall area, so a bigger box takes a bigger element, not a smaller one: a 16 x 14 x 8 in stainless box has 0.599 m² of wall and needs 3.7 × 0.599 × 16 ≈ 35 W to hold 26 C against a 10 C night. The gain is geometry; the element sits farther from the wiring and the larger air volume smooths the swings. For washdown duty, order a stainless box rated NEMA 4X / IP66 by the manufacturer (not UL listed), with the heater at the bottom of the back plate and terminal space above it. 304 handles routine washdown; 316L is the grade for brine and chlorine sanitizers. We build these to your width, height, depth and cutouts and deliver in 10 business days from drawing approval; the stainless washdown enclosures page shows the range.
Catalog dimensions to compare
Compare these catalog dimensions with your component layout. Open each enclosure for its rating, material and usable space, then check those specifications against your application.
| Enclosure | Material | Outside H x W x D / display | Rating |
|---|---|---|---|
| 12 × 10 × 6 in | 304 stainless | 12 x 10 x 6 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 14 × 8 in | 304 stainless | 16 x 14 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 16 × 12 × 8 in | 304 stainless | 16 x 12 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
| 24 × 20 × 8 in | 304 stainless | 24 x 20 x 8 in | Rated NEMA 4X / IP66 by the manufacturer; not UL listed |
Questions
Is 140 F a normal setting for an enclosure heater thermostat?
No. That dial mark is 60 C, which holds a 50 W heater on continuously and overheats the wiring routed beside it. Condensation control needs the interior only 5-10 C above the dew point: for air at 25 C and 70% RH, a 24-29 C (75-84 F) setting. Keep any high mark for a supervised one-off dry-out.
How many watts does a small enclosure heater actually need?
For the 12 x 10 x 6 in stainless box in the worked example: wall area 0.325 m², stainless at 3.7 W/m²K, holding 26 C against a 10 C night costs 19 W of continuous loss. A 40 W fanless strip covers it with cycling margin; a 16 x 14 x 8 in box of the same grade needs about 35 W.
Can I remove the heater if the panel keeps running too hot?
Removing it trades overheating for condensation: a washdown or outdoor box that cools overnight will sweat on the next damp cycle, and moisture on a live controller is worse than warmth. Fix the set point, separate the harness from the element, and order the next size if the box is too cramped for both.
Should a hygrostat control the heater instead of a thermostat?
On a washdown or outdoor box, usually yes. A hygrostat closes when the air inside turns damp, so the element runs after each washdown or humid night and stays off in dry heat, which cuts running hours on the same heater. Keep a thermostat back-stop near 40 C (104 F), the ambient most panel electronics are rated for, so a stuck hygrostat cannot cook the panel.





